- Start the ack confirmation with Task.Run + ConfigureAwait(false) so it never
depends on the ReceiveAsync handler's ActorTaskScheduler (the PostStop
abandon-and-revert report must run after the actor stopped).
- DriverInstanceActorAckConfirmationTests: a confirmation that faults after the
handler returned is reported; one pending at actor stop is reported; a
confirmed ack reports nothing (positive control).
- Deterministic tracker matching test (Raise/Clear/Retrigger/other alarm do not
confirm; case-insensitive match does).
- AdminUI min/max on the confirm-timeout field; Galaxy.md documents the
reconnect, UNACK_RTN-as-Clear and RPC-budget limits.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
mxaccessgw answers AcknowledgeAlarm OK both when the AckMsg write was
applied and when it was only sent (no OnWriteComplete; the reply then
carries a diagnostic). EvaluateReply treated both as success, so the H6
live gate saw a condition go Acknowledged while Galaxy never applied it.
- EvaluateReply returns Applied (no diagnostic) or Unconfirmed (diagnostic)
and logs the gateway diagnostic on every branch that carries one.
- GalaxyAckConfirmationTracker watches the alarm feed from before the RPC
and, for an unconfirmed reply, waits up to AlarmAck.ConfirmTimeoutMs
(default 10 s, 0 = old behaviour) for an Acknowledge/ActiveAcknowledged
transition; on timeout it refuses (BadTimeout + diagnostic).
- New optional IAlarmAcknowledgeConfirmation: DriverInstanceActor awaits it
after AcknowledgeAsync, off its mailbox and outside the resilience
pipeline; a failure is the existing #760 AlarmAckFailed revert.
- AdminUI Galaxy form carries the new knob; docs updated.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk