GalaxyAlarmPriority, the one table live Galaxy alarms (MxAccessSeverityMapper)
and AVEVA A&E history (EventMapper, #886) map the AVEVA priority through, ranked
a higher number as more severe. AVEVA ranks priority 1 as the most urgent, so a
priority-1 alarm read 250 and a priority-999 system event 1000.
It now uses AVEVA's default priority ranges, most urgent first:
AVEVA priority AVEVA severity bucket OPC UA Severity
1-250 1 Critical Critical 1000
251-500 2 High High 750
501-750 3 Medium Medium 500
751-999 4 Low Low 250
(history only) 0 not an alarm - 1
Out-of-range priorities clamp (<= 0 Critical, > 999 Low). Evidence, vd03
Runtime.dbo.Events read-only: priority 1/100 alarms carry AVEVA severity 1,
400/500 severity 2, 600/700 severity 3, and every priority-999 System.* /
User.* row severity 0 with IsAlarm 0.
- Live and history now use the same number. GalaxyDriver passes the table's
exact value as AlarmEventArgs.OpcUaSeverity. Before, it passed only the bucket,
which NativeAlarmProjector re-mapped through its generic 200/500/700/900
ladder, so live and history disagreed even before the direction fix.
- History: a row whose AVEVA severity is 0 (System.Start/Stop/Deploy,
User.Write...) is not an alarm and reads Severity 1, below every alarm band.
For alarms AVEVA's 1-4 severity is still never the value: the live feed
carries only the priority, so it cannot use it, and history must agree.
- Docs: docs/Historian.md gains "Galaxy alarm priority -> Severity
(lmxopcua#887)"; docs/AlarmTracking.md updated.
- Live re-run of the #801/#886 harness against vd03 HistorianGateway
ea9f21c (read-only, network-only): 224 of 233 cases identical to the #886
run, the 9 others differ only in Severity (priority-700 alarm rows 750 ->
500, 19 system/user events 1000 -> 1). Record: aveva-history-801.md
"#887 re-run", report aveva-gate-sdk2-887.json.gz.
Client-visible: every OPC UA client that ranks or filters Galaxy alarms by
Severity sees the order reversed (live and HistoryReadEvents). ScadaBridge has
no code that depends on the old values; its own mixed severity directions are
ScadaBridge#129.
Tests updated because they pinned the inverted table:
- Driver.Galaxy.Tests MxAccessSeverityMapperTests (rewritten: edges 1/250/251/
500/501/750/751/999, 0/-100/int.MinValue/1000/int.MaxValue clamps,
monotonic-decreasing sweep, equals GalaxyAlarmPriority for -2..1001)
- Driver.Galaxy.Tests GatewayGalaxyAlarmFeedTests (750 and 600 -> Medium)
- Driver.Historian.Gateway.Tests EventMapperTests (band table, priority 999
-> 250, 1 -> 1000; system events -> 1)
- OpcUaServer.IntegrationTests GalaxyEquipmentEventHistoryWireTests (700 ->
500, 100 -> 1000, System.Stop -> 1; the fake now stores AVEVA's real 0-4
severity)
New tests:
- Runtime.Tests NativeAlarmRestatementEndToEndTests
.Galaxy_live_condition_severity_is_the_AVEVA_priority_band (8 rows: the real
feed -> real GalaxyDriver -> host -> projector; the same rows EventMapperTests
pins on the history path)
- EventMapperTests.Aveva_severity_zero_marks_an_event_that_is_not_an_alarm
(5 rows, incl. the priority-999 alarm positive control)
- GalaxyDriverAlarmSourceTests: OpcUaSeverity passes through
Mutation check, 8 mutants, all killed: the pre-#887 inverted table; the
driver dropping OpcUaSeverity; no not-an-alarm rule; each of the three band
edges off by one; history ignoring priority; a missing AVEVA severity read
as 0.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
mxaccessgw answers AcknowledgeAlarm OK both when the AckMsg write was
applied and when it was only sent (no OnWriteComplete; the reply then
carries a diagnostic). EvaluateReply treated both as success, so the H6
live gate saw a condition go Acknowledged while Galaxy never applied it.
- EvaluateReply returns Applied (no diagnostic) or Unconfirmed (diagnostic)
and logs the gateway diagnostic on every branch that carries one.
- GalaxyAckConfirmationTracker watches the alarm feed from before the RPC
and, for an unconfirmed reply, waits up to AlarmAck.ConfirmTimeoutMs
(default 10 s, 0 = old behaviour) for an Acknowledge/ActiveAcknowledged
transition; on timeout it refuses (BadTimeout + diagnostic).
- New optional IAlarmAcknowledgeConfirmation: DriverInstanceActor awaits it
after AcknowledgeAsync, off its mailbox and outside the resilience
pipeline; a failure is the existing #760 AlarmAckFailed revert.
- AdminUI Galaxy form carries the new knob; docs updated.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
mxaccessgw 488649c+ acknowledges by AuthenticateUser as the operator and
writing <alarm>.AckMsg, so AcknowledgeAlarmRequest now needs a real Galaxy
operator_user + operator_domain + operator_password. The OPC UA data plane is
API-key/anonymous and carries no Galaxy password, so the driver resolves the
account per ack:
1. the session's API key's Galaxy ack identity, set on AdminUI /apikeys and
held ONLY in the encrypted Secrets store
(otopcua/apikeys/<keyId>/galaxy-ack-{user,password}); a key with a user but
no password secret is refused, never silently downgraded;
2. else the driver instance's AlarmAck fallback account (DriverConfig
FallbackUser/FallbackDomain/FallbackPasswordSecretRef; secret:/${secret:}/
env:/file:/dev: only — a literal is refused);
3. else DriverOperationRefusedException: nothing is sent, never an empty
operator_user. Refusals are excluded from the resilience retry/breaker.
- Pins ZB.MOM.WW.MxGateway.Client/Contracts 0.2.1 -> 0.3.0 (vendored into
nuget-packages/ from the Gitea feed, per the local-mxgw source mapping).
- The session ApiKeyId (not a secret) rides NativeAlarmAck ->
RouteNativeAlarmAck -> RouteAlarmAck -> AlarmAcknowledgeRequest; the password
is resolved in the driver and never travels through actor messages.
- The OPC UA principal + key id are appended to the AckMsg comment
("[OPC UA: <principal>, key <id>]") and logged, so a shared fallback
account does not lose who acknowledged.
- Password never logged: GalaxyAckCredential.ToString omits it, the
acknowledger scrubs it from every gateway message it echoes and withholds
any exception that echoes it; audit rows carry only the key id.
- AdminUI: /apikeys "Ack identity" editor (set/remove; delete-key clears it),
Galaxy driver form gains the fallback section.
- Synchronous OPC UA status for a refusal is follow-up #760 (the native ack
path is fire-and-forget after the Part 9 method returns).
Tests: request mapping (password populated), password absent from logs and
exception text (mutation-checked), key-mapped / fallback / refused paths at
resolver and driver level, breaker non-trip, key-id propagation through node
manager and DriverHostActor, AdminUI service + form round-trip.
Closes#749
GalaxyDriver's StreamAlarms feed is session-less and survives an in-place
reconnect, so DriverInstanceActor re-subscribed on every Connected re-entry
(after dropping its own cached handle without an Unsubscribe — sync teardown).
The re-subscribe was additive: _alarmSubscriptions.Add grew the list by one
untracked handle per reconnect cycle — a slow unbounded leak. Functionally
harmless (the gate is Count>0 and OnAlarmFeedTransition only reads [0], firing
once regardless), but it accumulated forever.
Fix: SubscribeAlarmsAsync clears the set before adding, collapsing to a single
live handle (under the existing _alarmHandlersLock, atomic w.r.t. the fan-out
reader). There is exactly one consumer per driver instance (factory-per-actor
lifecycle), so replacing the set with the latest handle is faithful. Chosen
over making the actor's sync DetachAlarmSource call UnsubscribeAlarmsAsync
async/fire-and-forget — disproportionate for a minor leak.
Regression test Re_subscribe_collapses_to_a_single_handle_no_accumulation
(TDD-verified: FAILS without the Clear — releasing the latest handle leaves
the feed open because stale handles remain; PASSES with the fix). Galaxy tests
263 pass / 3 skip; Runtime native-alarm 24 pass. Code-reviewed (approved).
Adds <summary>, <param>, <typeparam>, and <inheritdoc/> tags to public
members surfaced by commentchecker — resolves 5,847 of 5,869 issues
(99.6%) across three /fixdocs passes.
The mxaccessgw updated alarms to a session-less central monitor:
AcknowledgeAlarm dropped SessionId and alarm transitions now come from
the session-less StreamAlarms feed instead of the per-session worker
StreamEvents stream. The GalaxyDriver no longer compiled against the
updated client.
- GatewayGalaxyAlarmAcknowledger: session-less rewrite — no GalaxyMxSession;
outcome read from ProtocolStatus (throw) and Hresult (warn).
- New IGalaxyAlarmFeed seam + GatewayGalaxyAlarmFeed: background consumer
of StreamAlarms that decodes the active-alarm snapshot plus live
transitions into GalaxyAlarmTransition and reopens the stream on
transport faults.
- EventPump: drop the dead per-session OnAlarmTransition path; the
per-session stream no longer carries alarms.
- GalaxyDriver: bridge the feed onto IAlarmSource.OnAlarmEvent; the feed
starts on SubscribeAlarmsAsync, independent of data subscriptions.
- Tests: replace EventPumpAlarmTests with GatewayGalaxyAlarmFeedTests;
move the driver alarm-source tests onto the IGalaxyAlarmFeed seam.
Browse needed no change — GatewayGalaxyHierarchySource consumes the
unchanged DiscoverHierarchy contract.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Group all 69 projects into category subfolders under src/ and tests/ so the
Rider Solution Explorer mirrors the module structure. Folders: Core, Server,
Drivers (with a nested Driver CLIs subfolder), Client, Tooling.
- Move every project folder on disk with git mv (history preserved as renames).
- Recompute relative paths in 57 .csproj files: cross-category ProjectReferences,
the lib/ HintPath+None refs in Driver.Historian.Wonderware, and the external
mxaccessgw refs in Driver.Galaxy and its test project.
- Rebuild ZB.MOM.WW.OtOpcUa.slnx with nested solution folders.
- Re-prefix project paths in functional scripts (e2e, compliance, smoke SQL,
integration, install).
Build green (0 errors); unit tests pass. Docs left for a separate pass.