fix(s7): numeric TSAP loads in form, shared TSAP conflict error, Test Connect read detects PUT/GET disabled, pin Int32 ms rounding (#632 #638)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
This commit is contained in:
@@ -80,7 +80,15 @@ public sealed class S7DriverProbe : IDriverProbe
|
||||
sw.Stop();
|
||||
|
||||
if (plc.IsConnected)
|
||||
{
|
||||
// A handshake alone passes on a CPU with PUT/GET disabled (S7-1200/1500 default) — every
|
||||
// later read would fail. One minimal read proves data access.
|
||||
if (await CheckDataAccessAsync(
|
||||
t => plc.ReadBytesAsync(global::S7.Net.DataType.Memory, 0, 0, 2, t), handshakeCts.Token)
|
||||
is { } denied)
|
||||
return denied;
|
||||
return new(true, $"S7 connected (CPU {opts.CpuType}, PDU {plc.MaxPDUSize} bytes)", sw.Elapsed);
|
||||
}
|
||||
|
||||
return new(false, $"Reachable at {host}:{port} but S7 handshake failed: not connected", null);
|
||||
}
|
||||
@@ -104,6 +112,38 @@ public sealed class S7DriverProbe : IDriverProbe
|
||||
}
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Runs one minimal read after the handshake. Returns null when data access works — including when the
|
||||
/// CPU merely rejects that particular address (MB0 not present / out of range: the connection is fine).
|
||||
/// PUT/GET-disabled yields the actionable message; any other fault is a probe failure with its message.
|
||||
/// </summary>
|
||||
/// <param name="read">The minimal read.</param>
|
||||
/// <param name="ct">Cancellation token.</param>
|
||||
/// <returns>A failure result, or null on success.</returns>
|
||||
internal static async Task<DriverProbeResult?> CheckDataAccessAsync(Func<CancellationToken, Task<byte[]>> read, CancellationToken ct)
|
||||
{
|
||||
try
|
||||
{
|
||||
await read(ct).ConfigureAwait(false);
|
||||
return null;
|
||||
}
|
||||
catch (OperationCanceledException) { throw; }
|
||||
catch (PlcException pex) when (S7Driver.IsAccessDenied(pex))
|
||||
{
|
||||
return new(false,
|
||||
"S7 connected but data access is denied — enable PUT/GET communication in TIA Portal " +
|
||||
$"(Protection & Security) for this CPU. PLC reported: {pex.Message}", null);
|
||||
}
|
||||
catch (PlcException pex) when (pex.ErrorCode == ErrorCode.ReadData)
|
||||
{
|
||||
return null; // address not available on this CPU — not a connection problem
|
||||
}
|
||||
catch (Exception ex)
|
||||
{
|
||||
return new(false, $"S7 connected but a test read failed: {ex.Message}", null);
|
||||
}
|
||||
}
|
||||
|
||||
private static (string host, int port) ExtractTarget(S7DriverOptions opts)
|
||||
=> (opts.Host, opts.Port);
|
||||
}
|
||||
|
||||
Reference in New Issue