Task #253 follow-up — driver-side e2e debug: port fixes + HR[200] scratch register
Ran the driver CLIs against the live docker-compose fixtures to debug
what actually works. Two real bugs surfaced:
1. `e2e-config.sample.json` pointed at the wrong simulator ports:
- Modbus: 5502 → **5020** (pymodbus compose binding)
- S7: 102 → **1102** (python-snap7, non-priv port)
- AbCip: no port → now explicit **:44818**
`test-modbus.ps1` default `-ModbusHost` also shipped with 5502;
fixed to 5020.
2. Modbus loopback was off-by-2 because pymodbus `standard.json` makes
HR[100] an auto-increment register (value ticks on every poll).
Switched `test-modbus.ps1` to **HR[200]** (scratch range in the
profile) + updated sample config `bridgeNodeId` to match.
Also fixed the AbCip probe: `-t @raw_cpu_type` was rejected by the
driver's TagPath parser ("malformed TagPath"). Probe now uses the
user-supplied `-TagPath` for every family. Works against both
ab_server and real controllers.
Verified driver-side against live containers:
- Modbus 5020: probe ✓, HR[200] write+read round-trip ✓
- AB CIP 44818: probe ✓, TestDINT write+read round-trip ✓
- S7 1102: probe ✓, DB1.DBW0 write+read round-trip ✓
## Known blocker (stages 3-5)
README now flags — and the 4 child issues under umbrella #209 track —
that `src/ZB.MOM.WW.OtOpcUa.Server/Program.cs:98-104` only registers
Galaxy + FOCAS driver factories. `DriverInstanceBootstrapper` silently
skips any `DriverType` without a registered factory, so stages 3-5
(anything crossing the OPC UA server) can't work today even with a
perfect Config DB seed. Issues #210-213 scope the factory + seed SQL
work per driver.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -7,17 +7,22 @@
|
||||
Five assertions:
|
||||
1. `otopcua-modbus-cli probe` hits the simulator
|
||||
2. Driver-loopback write + read-back via modbus-cli
|
||||
3. Forward bridge: modbus-cli writes HR[100], OPC UA client reads the bridged NodeId
|
||||
4. Reverse bridge: OPC UA client writes the NodeId, modbus-cli reads HR[100]
|
||||
3. Forward bridge: modbus-cli writes HR[200], OPC UA client reads the bridged NodeId
|
||||
4. Reverse bridge: OPC UA client writes the NodeId, modbus-cli reads HR[200]
|
||||
5. Subscribe-sees-change: OPC UA subscription observes a modbus-cli write
|
||||
|
||||
Requires a running Modbus simulator on localhost:5502 (the pymodbus fixture
|
||||
default per docs/drivers/Modbus-Test-Fixture.md) and a running OtOpcUa server
|
||||
whose config DB has a Modbus DriverInstance bound to that simulator + a Tag
|
||||
at HR[100] Int16 published under the NodeId passed via -BridgeNodeId.
|
||||
Requires a running Modbus simulator on localhost:5020 (the pymodbus fixture
|
||||
default — see tests/.../Modbus.IntegrationTests/Docker/docker-compose.yml)
|
||||
and a running OtOpcUa server whose config DB has a Modbus DriverInstance
|
||||
bound to that simulator + a Tag at HR[200] UInt16 published under the
|
||||
NodeId passed via -BridgeNodeId.
|
||||
|
||||
NOTE: HR[200] (not HR[100]) — pymodbus standard.json makes HR[100] an
|
||||
auto-incrementing register that mutates every poll, so loopback writes
|
||||
can't be verified there.
|
||||
|
||||
.PARAMETER ModbusHost
|
||||
Host:port of the Modbus simulator. Default 127.0.0.1:5502.
|
||||
Host:port of the Modbus simulator. Default 127.0.0.1:5020.
|
||||
|
||||
.PARAMETER OpcUaUrl
|
||||
Endpoint URL of the OtOpcUa server. Default opc.tcp://localhost:4840.
|
||||
@@ -31,7 +36,7 @@
|
||||
#>
|
||||
|
||||
param(
|
||||
[string]$ModbusHost = "127.0.0.1:5502",
|
||||
[string]$ModbusHost = "127.0.0.1:5020",
|
||||
[string]$OpcUaUrl = "opc.tcp://localhost:4840",
|
||||
[Parameter(Mandatory)] [string]$BridgeNodeId
|
||||
)
|
||||
@@ -59,14 +64,14 @@ $results += Test-Probe `
|
||||
$writeValue = Get-Random -Minimum 1 -Maximum 9999
|
||||
$results += Test-DriverLoopback `
|
||||
-Cli $modbusCli `
|
||||
-WriteArgs (@("write") + $commonModbus + @("-r", "HoldingRegisters", "-a", "100", "-t", "UInt16", "-v", $writeValue)) `
|
||||
-ReadArgs (@("read") + $commonModbus + @("-r", "HoldingRegisters", "-a", "100", "-t", "UInt16")) `
|
||||
-WriteArgs (@("write") + $commonModbus + @("-r", "HoldingRegisters", "-a", "200", "-t", "UInt16", "-v", $writeValue)) `
|
||||
-ReadArgs (@("read") + $commonModbus + @("-r", "HoldingRegisters", "-a", "200", "-t", "UInt16")) `
|
||||
-ExpectedValue "$writeValue"
|
||||
|
||||
$bridgeValue = Get-Random -Minimum 10000 -Maximum 19999
|
||||
$results += Test-ServerBridge `
|
||||
-DriverCli $modbusCli `
|
||||
-DriverWriteArgs (@("write") + $commonModbus + @("-r", "HoldingRegisters", "-a", "100", "-t", "UInt16", "-v", $bridgeValue)) `
|
||||
-DriverWriteArgs (@("write") + $commonModbus + @("-r", "HoldingRegisters", "-a", "200", "-t", "UInt16", "-v", $bridgeValue)) `
|
||||
-OpcUaCli $opcUaCli `
|
||||
-OpcUaUrl $OpcUaUrl `
|
||||
-OpcUaNodeId $BridgeNodeId `
|
||||
@@ -78,7 +83,7 @@ $results += Test-OpcUaWriteBridge `
|
||||
-OpcUaUrl $OpcUaUrl `
|
||||
-OpcUaNodeId $BridgeNodeId `
|
||||
-DriverCli $modbusCli `
|
||||
-DriverReadArgs (@("read") + $commonModbus + @("-r", "HoldingRegisters", "-a", "100", "-t", "UInt16")) `
|
||||
-DriverReadArgs (@("read") + $commonModbus + @("-r", "HoldingRegisters", "-a", "200", "-t", "UInt16")) `
|
||||
-ExpectedValue "$reverseValue"
|
||||
|
||||
$subValue = Get-Random -Minimum 30000 -Maximum 39999
|
||||
@@ -87,7 +92,7 @@ $results += Test-SubscribeSeesChange `
|
||||
-OpcUaUrl $OpcUaUrl `
|
||||
-OpcUaNodeId $BridgeNodeId `
|
||||
-DriverCli $modbusCli `
|
||||
-DriverWriteArgs (@("write") + $commonModbus + @("-r", "HoldingRegisters", "-a", "100", "-t", "UInt16", "-v", $subValue)) `
|
||||
-DriverWriteArgs (@("write") + $commonModbus + @("-r", "HoldingRegisters", "-a", "200", "-t", "UInt16", "-v", $subValue)) `
|
||||
-ExpectedValue "$subValue"
|
||||
|
||||
Write-Summary -Title "Modbus e2e" -Results $results
|
||||
|
||||