test(s7): live-pin the Timer/Counter multi-var exclusion against a TM/CT-seeded s7_1500 fixture
This commit is contained in:
+29
-1
@@ -1,5 +1,5 @@
|
||||
{
|
||||
"_description": "S7-1500 profile — single DB1 (1024 bytes) + MB (256 bytes) with well-known seeds at named offsets for the smoke + byte-order + string tests. Big-endian Siemens wire order throughout.",
|
||||
"_description": "S7-1500 profile — DB1 (1024 bytes) + MB (256 bytes) + TM/CT (64 bytes each) with well-known seeds at named offsets for the smoke + byte-order + string + Timer/Counter tests. Big-endian Siemens wire order throughout.",
|
||||
"areas": [
|
||||
{
|
||||
"area": "DB",
|
||||
@@ -59,6 +59,34 @@
|
||||
{ "_desc": "MW10 — span-planner gate: a narrow scalar in a DIFFERENT area from the DB1 leftovers. A block read can never merge across (area, DB); the multi-var pass can, so this pins that the leftover batching crosses the boundary.",
|
||||
"offset": 10, "type": "u16", "value": 4097 }
|
||||
]
|
||||
},
|
||||
{
|
||||
"_desc": "TM (timers) — 64 bytes = 32 timer cells. A timer is a 2-byte S5TIME word and timer number N lives at byte offset 2*N, so the offsets below ARE the timer numbers doubled. Values are S5TIME-encoded (bits 12..13 = time base, the remaining three nibbles = a BCD 0..999 count) and each decodes to a distinct NON-ZERO duration, because a zero-valued timer reads the same as a timer that was never served at all (the #536 trap). ⚠️ Only T0 is readable through this fixture — see the CT note below and Docker/README.md §'Timer / Counter (TM / CT) areas'.",
|
||||
"area": "TM",
|
||||
"index": 0,
|
||||
"size": 64,
|
||||
"seeds": [
|
||||
{ "_desc": "T0 @ byte 0 — 0x2456: base 2 (×1s), BCD 456 ⇒ 456.0 seconds. Device 0 is the one cell where snap7's address resolution and a real CPU's agree, so this is the seed S7_1500SpanReadTests asserts on.",
|
||||
"offset": 0, "type": "u16", "value": 9302 },
|
||||
{ "_desc": "T5 @ byte 10 — 0x1123: base 1 (×0.1s), BCD 123 ⇒ 12.3 seconds. Reachable only from a real CPU (S7_TIMER_NUMBER_ADDRESSING=1).",
|
||||
"offset": 10, "type": "u16", "value": 4387 },
|
||||
{ "_desc": "T9 @ byte 18 — 0x0250: base 0 (×0.01s), BCD 250 ⇒ 2.5 seconds. Real CPU only, as above.",
|
||||
"offset": 18, "type": "u16", "value": 592 }
|
||||
]
|
||||
},
|
||||
{
|
||||
"_desc": "CT (counters) — 64 bytes = 32 counter cells, counter number N at byte offset 2*N. The driver surfaces a counter as the RAW big-endian word (S7Driver.DecodeScalarBlock via S7.Net's Counter.FromByteArray), so these seeds are plain u16 counts; distinct + non-zero for the same reason as the timers. ⚠️ snap7's server resolves the TM/CT request address as a BIT address (byte = addr>>3) instead of as a device NUMBER, while S7.Net (and a real CPU) put the device number there — so a read of C{n} lands on byte n>>3, and device 0 is the only n where the two conventions coincide. Live-probed 2026-08-17; see Docker/README.md.",
|
||||
"area": "CT",
|
||||
"index": 0,
|
||||
"size": 64,
|
||||
"seeds": [
|
||||
{ "_desc": "C0 @ byte 0 — count 4711. The device-0 cell both conventions agree on; asserted by S7_1500SpanReadTests.",
|
||||
"offset": 0, "type": "u16", "value": 4711 },
|
||||
{ "_desc": "C7 @ byte 14 — count 31337. Reachable only from a real CPU (S7_TIMER_NUMBER_ADDRESSING=1).",
|
||||
"offset": 14, "type": "u16", "value": 31337 },
|
||||
{ "_desc": "C11 @ byte 22 — count 1234. Real CPU only, as above.",
|
||||
"offset": 22, "type": "u16", "value": 1234 }
|
||||
]
|
||||
}
|
||||
]
|
||||
}
|
||||
|
||||