Phase 3 PR 58 -- Mitsubishi MELSEC pymodbus profile + smoke integration test. Adds tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/Pymodbus/mitsubishi.json modelling a representative MELSEC Modbus Device Assignment block: D0..D1023 -> HR[0..1023], M-relay marker at coil 512 (cell 32) and X-input marker at DI 528 (cell 33). Covers the canonical MELSEC quirks from docs/v2/mitsubishi.md: D0 fingerprint at HR[0]=0x1234 so clients can verify the assignment parameter block is in effect, scratch HR 200..209 mirroring dl205/s7_1500/standard scratch range for uniform smoke tests, Float32 1.5f at HR[100..101] in CDAB word order (HR[100]=0, HR[101]=0x3FC0) -- same as DL260, OPPOSITE of S7 ABCD, confirms MELSEC-family driver profile default must be ByteOrder.WordSwap. Int32 0x12345678 CDAB at HR[300..301]. D10 = binary 1234 (0x04D2) proves MELSEC is BINARY-by-default (opposite of DL205 BCD-by-default quirk) -- reading D10 with Bcd16 data type would throw InvalidDataException on nibble 0xD. M-relay marker cell moved to address 32 (coil 512) to avoid shared-block collision with D0 uint16 marker at cell 0; pymodbus shared-blocks=true semantics allow only one type per cell index, so Modbus-coil-0 can't coexist with Modbus-HR-0 on the same sim. Same pattern we applied to dl205 profile (X-input bank at cell 1, not cell 0, to coexist with V0 marker). Adds Mitsubishi/ test directory with MitsubishiProfile.cs (SmokeHoldingRegister=200, SmokeHoldingValue=7890, BuildOptions with probe-disabled + 2s timeout) and MitsubishiSmokeTests.cs (Mitsubishi_roundtrip_write_then_read_of_holding_register single fact that writes 7890 at HR[200] then reads back, gated on MODBUS_SIM_PROFILE=mitsubishi). csproj copies Mitsubishi/** as PreserveNewest. Per-model differences (FX5U firmware gate, QJ71MT91 FC22/23 absence, FX/iQ-F octal vs Q/L/iQ-R hex X-addressing) are handled in the MelsecAddress helper (PR 59) + per-model test classes (PR 60). Verified: smoke 1/1 passes against live mitsubishi sim. Prior S7 tests 4/4 still green when swapped back. Modbus.Tests unit suite 143/143.
This commit is contained in:
@@ -0,0 +1,83 @@
|
||||
{
|
||||
"_comment": "mitsubishi.json -- Mitsubishi MELSEC Modbus TCP quirk simulator covering QJ71MT91, iQ-R, iQ-F/FX5U, and FX3U-ENET-P502 behaviors documented in docs/v2/mitsubishi.md. MELSEC CPUs store multi-word values in CDAB order (opposite of S7 ABCD, same family as DL260). The Modbus-module 'Modbus Device Assignment Parameter' block is per-site, so this profile models one *representative* assignment mapping D-register D0..D1023 -> HR 0..1023, M-relay M0..M511 -> coil 0..511, X-input X0..X15 -> DI 0..15 (X-addresses are HEX on Q/L/iQ-R, so X10 = decimal 16; on FX/iQ-F they're OCTAL like DL260). pymodbus bit-address semantics are the same as dl205.json and s7_1500.json (FC01/02/05/15 address N maps to cell index N/16).",
|
||||
|
||||
"server_list": {
|
||||
"srv": {
|
||||
"comm": "tcp",
|
||||
"host": "0.0.0.0",
|
||||
"port": 5020,
|
||||
"framer": "socket",
|
||||
"device_id": 1
|
||||
}
|
||||
},
|
||||
|
||||
"device_list": {
|
||||
"dev": {
|
||||
"setup": {
|
||||
"co size": 4096,
|
||||
"di size": 4096,
|
||||
"hr size": 4096,
|
||||
"ir size": 1024,
|
||||
"shared blocks": true,
|
||||
"type exception": false,
|
||||
"defaults": {
|
||||
"value": {"bits": 0, "uint16": 0, "uint32": 0, "float32": 0.0, "string": " "},
|
||||
"action": {"bits": null, "uint16": null, "uint32": null, "float32": null, "string": null}
|
||||
}
|
||||
},
|
||||
"invalid": [],
|
||||
"write": [
|
||||
[0, 0],
|
||||
[10, 10],
|
||||
[100, 101],
|
||||
[200, 209],
|
||||
[300, 301],
|
||||
[500, 500]
|
||||
],
|
||||
|
||||
"uint16": [
|
||||
{"_quirk": "D0 fingerprint marker. MELSEC D0 is the first data register; Modbus Device Assignment typically maps D0..D1023 -> HR 0..1023. 0x1234 is the fingerprint operators set in GX Works to prove the mapping parameter block is in effect.",
|
||||
"addr": 0, "value": 4660},
|
||||
|
||||
{"_quirk": "Scratch HR range 200..209 -- mirrors the dl205/s7_1500/standard scratch range so smoke tests (MitsubishiProfile.SmokeHoldingRegister=200) round-trip identically against any profile.",
|
||||
"addr": 200, "value": 0},
|
||||
{"addr": 201, "value": 0},
|
||||
{"addr": 202, "value": 0},
|
||||
{"addr": 203, "value": 0},
|
||||
{"addr": 204, "value": 0},
|
||||
{"addr": 205, "value": 0},
|
||||
{"addr": 206, "value": 0},
|
||||
{"addr": 207, "value": 0},
|
||||
{"addr": 208, "value": 0},
|
||||
{"addr": 209, "value": 0},
|
||||
|
||||
{"_quirk": "Float32 1.5f in CDAB word order (MELSEC Q/L/iQ-R/iQ-F default, same as DL260). HR[100]=0x0000=0 low word, HR[101]=0x3FC0=16320 high word. Decode with ByteOrder.WordSwap returns 1.5f; BigEndian decode returns a denormal.",
|
||||
"addr": 100, "value": 0},
|
||||
{"addr": 101, "value": 16320},
|
||||
|
||||
{"_quirk": "Int32 0x12345678 in CDAB word order. HR[300]=0x5678=22136 low word, HR[301]=0x1234=4660 high word. Contrasts with the S7 profile's ABCD encoding at the same address.",
|
||||
"addr": 300, "value": 22136},
|
||||
{"addr": 301, "value": 4660},
|
||||
|
||||
{"_quirk": "D10 = decimal 1234 stored as BINARY (NOT BCD like DL205). 0x04D2 = 1234 decimal. Caller reading with Bcd16 data type would decode this as binary 1234's BCD nibbles which are non-BCD and throw InvalidDataException -- proves MELSEC is binary-by-default, opposite of DL205's BCD-by-default quirk.",
|
||||
"addr": 10, "value": 1234},
|
||||
|
||||
{"_quirk": "Modbus Device Assignment boundary marker. HR[500] represents the last register in an assigned D-range D500. Beyond this (HR[501..4095]) would be Illegal Data Address on a real QJ71MT91 with this specific parameter block; pymodbus returns default 0 because its shared cell array has space -- real-PLC parity is documented in docs/v2/mitsubishi.md §device-assignment, not enforced here.",
|
||||
"addr": 500, "value": 500}
|
||||
],
|
||||
|
||||
"bits": [
|
||||
{"_quirk": "M-relay marker cell at cell 32 = Modbus coil 512 = MELSEC M512 (coils 0..15 collide with the D0 uint16 marker cell, so we place the M marker above that). Cell 32 bit 0 = 1 and bit 2 = 1 (value = 0b101 = 5) = M512=ON, M513=OFF, M514=ON. Matches the Y0/Y2 marker pattern in dl205 and s7_1500 profiles.",
|
||||
"addr": 32, "value": 5},
|
||||
|
||||
{"_quirk": "X-input marker cell at cell 33 = Modbus DI 528 (= MELSEC X210 hex on Q/L/iQ-R). Cell 33 bit 0 = 1 and bit 3 = 1 (value = 0x9 = 9). Chosen above cell 1 so it doesn't collide with any uint16 D-register. Proves the hex-parsing X-input helper on Q/L/iQ-R family; FX/iQ-F families use octal X-addresses tested separately.",
|
||||
"addr": 33, "value": 9}
|
||||
],
|
||||
|
||||
"uint32": [],
|
||||
"float32": [],
|
||||
"string": [],
|
||||
"repeat": []
|
||||
}
|
||||
}
|
||||
}
|
||||