Phase 6.1 Stream A.5/A.6 — WriteIdempotent flag on DriverAttributeInfo + Modbus/S7 tag records + FlakeyDriver integration tests
Per-tag opt-in for write-retry per docs/v2/plan.md decisions #44, #45, #143. Default is false — writes never auto-retry unless the driver author has marked the tag as safe to replay. Core.Abstractions: - DriverAttributeInfo gains `bool WriteIdempotent = false` at the end of the positional record (back-compatible; every existing call site uses the default). Driver.Modbus: - ModbusTagDefinition gains `bool WriteIdempotent = false`. Safe candidates documented in the param XML: holding-register set-points, configuration registers. Unsafe: edge-triggered coils, counter-increment addresses. - ModbusDriver.DiscoverAsync propagates t.WriteIdempotent into DriverAttributeInfo.WriteIdempotent. Driver.S7: - S7TagDefinition gains `bool WriteIdempotent = false`. Safe candidates: DB word/dword set-points, configuration DBs. Unsafe: M/Q bits that drive edge-triggered program routines. - S7Driver.DiscoverAsync propagates the flag. Stream A.5 integration tests (FlakeyDriverIntegrationTests, 4 new) exercise the invoker + flaky-driver contract the plan enumerates: - Read with 5 transient failures succeeds on the 6th attempt (RetryCount=10). - Non-idempotent write with RetryCount=5 configured still fails on the first failure — no replay (decision #44 guard at the ExecuteWriteAsync surface). - Idempotent write with 2 transient failures succeeds on the 3rd attempt. - Two hosts on the same driver have independent breakers — dead-host trips its breaker but live-host's first call still succeeds. Propagation tests: - ModbusDriverTests: SetPoint WriteIdempotent=true flows into DriverAttributeInfo; PulseCoil default=false. - S7DiscoveryAndSubscribeTests: same pattern for DBx SetPoint vs M-bit. Full solution dotnet test: 947 passing (baseline 906, +41 net across Stream A so far). Pre-existing Client.CLI Subscribe flake unchanged. Stream A's remaining work (wiring CapabilityInvoker into DriverNodeManager's OnReadValue / OnWriteValue / History / Subscribe dispatch paths) is the server-side integration piece + needs DI wiring for the pipeline builder — lands in the next PR on this branch. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -92,6 +92,14 @@ public sealed class ModbusProbeOptions
|
||||
/// AutomationDirect DirectLOGIC (DL205/DL260) and a few legacy families pack the first
|
||||
/// character in the low byte instead — see <c>docs/v2/dl205.md</c> §strings.
|
||||
/// </param>
|
||||
/// <param name="WriteIdempotent">
|
||||
/// Per <c>docs/v2/plan.md</c> decisions #44, #45, #143 — flag a tag as safe to replay on
|
||||
/// write timeout / failure. Default <c>false</c>; writes do not auto-retry. Safe candidates:
|
||||
/// holding-register set-points for analog values and configuration registers where the same
|
||||
/// value can be written again without side-effects. Unsafe: coils that drive edge-triggered
|
||||
/// actions (pulse outputs), counter-increment addresses on PLCs that treat writes as deltas,
|
||||
/// any BCD / counter register where repeat-writes advance state.
|
||||
/// </param>
|
||||
public sealed record ModbusTagDefinition(
|
||||
string Name,
|
||||
ModbusRegion Region,
|
||||
@@ -101,7 +109,8 @@ public sealed record ModbusTagDefinition(
|
||||
ModbusByteOrder ByteOrder = ModbusByteOrder.BigEndian,
|
||||
byte BitIndex = 0,
|
||||
ushort StringLength = 0,
|
||||
ModbusStringByteOrder StringByteOrder = ModbusStringByteOrder.HighByteFirst);
|
||||
ModbusStringByteOrder StringByteOrder = ModbusStringByteOrder.HighByteFirst,
|
||||
bool WriteIdempotent = false);
|
||||
|
||||
public enum ModbusRegion { Coils, DiscreteInputs, InputRegisters, HoldingRegisters }
|
||||
|
||||
|
||||