feat(twincat): array and STRING writes through the codecs (U9)
Array tags were advertised writable but every write threw InvalidCastException in ConvertForWrite (reported BadTypeMismatch); STRING writes went through the Beckhoff marshaller with no length check against STRING(n) and the host's ANSI code page, which the read side deliberately avoids. - Array write: TwinCATArrayCodec.ToWriteElements converts exactly ArrayLength elements to the declared type (CLR lists convert - ScadaBridge writes int[] to Int16 nodes; a length mismatch or out-of-range element is BadOutOfRange, a scalar value BadTypeMismatch) before any wire traffic; the ADS client plans the layout from the resolved PLC array (TwinCATTypeGuard.CheckArray, as the read does), encodes with TwinCATArrayCodec.Encode - the exact inverse of Decode - and writes the raw bytes (new ITwinCATClient.WriteArrayAsync). - STRING / WSTRING write: encoded at the PLC's declared width by TwinCATStringCodec.EncodeString/EncodeWString (Windows-1252 or UTF-8 per target, NUL-padded, strict: an over-long value or unrepresentable character is OverflowException -> BadOutOfRange) and written as raw bytes. - TwinCAT CLI read/write gain --array-length (+ --separator) for the hardware gate. Refs #739 Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
This commit is contained in:
+20
@@ -184,4 +184,24 @@ public sealed class WriteCommandParseValueTests
|
||||
{
|
||||
ReadCommand.SynthesiseTagName(symbol, type).ShouldBe(expected);
|
||||
}
|
||||
|
||||
/// <summary>An array value splits on the separator and parses each element per --type (#739 U9 gate tooling).</summary>
|
||||
[Fact]
|
||||
public void ParseArrayValue_parses_each_element()
|
||||
{
|
||||
WriteCommand.ParseArrayValue("1, -2,3", TwinCATDataType.Int, 3, ",")
|
||||
.ShouldBe(new object[] { (short)1, (short)-2, (short)3 });
|
||||
WriteCommand.ParseArrayValue("a b|c", TwinCATDataType.String, 2, "|")
|
||||
.ShouldBe(new object[] { "a b", "c" });
|
||||
}
|
||||
|
||||
/// <summary>A count that differs from --array-length is refused before the PLC is touched.</summary>
|
||||
[Fact]
|
||||
public void ParseArrayValue_refuses_a_count_mismatch()
|
||||
{
|
||||
Should.Throw<CliFx.Exceptions.CommandException>(
|
||||
() => WriteCommand.ParseArrayValue("1,2", TwinCATDataType.Int, 3, ","));
|
||||
Should.Throw<CliFx.Exceptions.CommandException>(
|
||||
() => WriteCommand.ParseArrayValue("1", TwinCATDataType.Int, 0, ","));
|
||||
}
|
||||
}
|
||||
|
||||
Reference in New Issue