feat(modbus-rtu): add ModbusTransportMode enum (Tcp | RtuOverTcp)
Claude-Session: https://claude.ai/code/session_01GASWkNEi68FSCtvr6rLoEW
This commit is contained in:
@@ -0,0 +1,17 @@
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
|
||||
/// <summary>
|
||||
/// Wire transport for a Modbus driver instance. <see cref="Tcp"/> = Modbus/TCP (MBAP + TxId);
|
||||
/// <see cref="RtuOverTcp"/> = RTU framing (address + CRC-16, no MBAP) tunnelled over a socket to
|
||||
/// a serial→Ethernet gateway. Default <see cref="Tcp"/> — existing configs omit the field.
|
||||
/// A direct-serial <c>Rtu</c> member is intentionally NOT reserved here (descoped 2026-07-15);
|
||||
/// do not number-squat it.
|
||||
/// </summary>
|
||||
public enum ModbusTransportMode
|
||||
{
|
||||
/// <summary>Modbus/TCP — 7-byte MBAP header + transaction id (the historical default).</summary>
|
||||
Tcp,
|
||||
|
||||
/// <summary>RTU framing (<c>[addr][PDU][CRC-16]</c>) tunnelled over a socket to a serial→Ethernet gateway.</summary>
|
||||
RtuOverTcp,
|
||||
}
|
||||