fix(ablegacy): opaque replies are neither answers nor faults; round-2 minors
Review r1 N1 (Important): the I1 fix made IsDeviceRefusal default-open and mapped libplctag's ERR_REMOTE_ERR to an answer. libplctag folds EVERY non-zero PCCC STS and CIP status into that code, including a routing hop's "unconnected send timed out" / "connection lost" / "remote node missing", and native BadReply covers truncated / mismatched / unmapped replies - so a powered-off PLC behind a bridge read as reachable: Healthy, LastSuccessfulRead advancing, the comms-loss watchdog unable to fire. Three classes now, each pinned both ways: - no reply (Timeout/BadConnection/Abort/Pending/unknown): comms fault; - answered - an ALLOW-LIST again (NotFound/NotAllowed/OutOfBounds/TooLarge/ TooSmall/TypeMismatch/DeviceStateConflict): proves reachability; - OPAQUE (BadReply/Partial; ERR_REMOTE_ERR/ERR_BAD_STATUS now translate to the existing BadReply, OPC UA BadCommunicationError as before r0): per-tag Bad, handle kept, coalescing fallback, never fail-fast, never an answer. Option (a): a device whose pass/call produced only opaque outcomes is Degraded with LastSuccessfulRead not advanced, so the watchdog reaches a dead routed PLC. The probe and index reads classify the same way. Minors: - N2: a mismatched array (type vs data file) READS BadTypeMismatch instead of decoding the file at the wrong width as Good. - N3: a swept indirect resolution is never reconnected under a forgotten gate; that one call answers neutrally. - N4: an index read answered Unsupported is neutral, not a transport fault. - N5: ArrayFileMismatch checks indirect addresses (the file letter is static). - Test nit: the evicted-while-waiting test signals gate arrival via a seam instead of sleeping. Live: 51/51 on ab_server (slc500/micrologix/plc5 x both transports), incl. an opaque-only libplctag device staying Degraded with LastSuccessfulRead frozen. Refs #738 Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
This commit is contained in:
@@ -123,6 +123,21 @@ public sealed class AbLegacyArrayWriteTests
|
||||
.ShouldContain(w => w.Contains("element width")); // and the deploy gate names it
|
||||
}
|
||||
|
||||
/// <summary>Review 07 r1 N5: the file letter of an indirect address is static, so the deploy gate checks it too.</summary>
|
||||
[Theory]
|
||||
[InlineData("N7:[N7:0]", "Float", true)]
|
||||
[InlineData("F[N7:0]:2", "Int", true)]
|
||||
[InlineData("N7:[N7:0]", "Int", false)]
|
||||
[InlineData("F[N7:0]:2", "Float", false)]
|
||||
public void An_indirect_array_type_file_mismatch_is_reported_at_the_gate(string address, string dataType, bool mismatch)
|
||||
{
|
||||
var json = $$"""{"address":"{{address}}","dataType":"{{dataType}}","isArray":true,"arrayLength":2}""";
|
||||
Enum.TryParse<AbLegacyDataType>(dataType, out var type).ShouldBeTrue();
|
||||
|
||||
(AbLegacyTagDefinitionFactory.ArrayFileMismatch(type, address) is not null).ShouldBe(mismatch);
|
||||
AbLegacyTagDefinitionFactory.Inspect(json).Any(w => w.Contains("element width")).ShouldBe(mismatch);
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task Positive_control_a_Float_array_on_an_F_file_is_written()
|
||||
{
|
||||
|
||||
Reference in New Issue