docs(modbus-rtu): record Wave-1 RTU-over-TCP live /run gate result (PASSED)
Claude-Session: https://claude.ai/code/session_01GASWkNEi68FSCtvr6rLoEW
This commit is contained in:
@@ -30,7 +30,7 @@ it reaches 📝.
|
|||||||
| Wave | Deliverable | Design | Impl. plan | Status | Effort | Fixture / hardware |
|
| Wave | Deliverable | Design | Impl. plan | Status | Effort | Fixture / hardware |
|
||||||
|---|---|---|---|---|---|---|
|
|---|---|---|---|---|---|---|
|
||||||
| **0** | Universal Discover-backed browser | [design](2026-07-15-universal-discovery-browser-design.md) | [plan](2026-07-15-universal-discovery-browser-implementation.md) · [tasks](2026-07-15-universal-discovery-browser-implementation.md.tasks.json) | 🟡 **Live gate open** | S–M | none (retrofits shipped drivers) |
|
| **0** | Universal Discover-backed browser | [design](2026-07-15-universal-discovery-browser-design.md) | [plan](2026-07-15-universal-discovery-browser-implementation.md) · [tasks](2026-07-15-universal-discovery-browser-implementation.md.tasks.json) | 🟡 **Live gate open** | S–M | none (retrofits shipped drivers) |
|
||||||
| **1** | Modbus RTU (extend Modbus) | [design](2026-07-15-modbus-rtu-driver-design.md) | [plan](2026-07-24-modbus-rtu-driver.md) · [tasks](2026-07-24-modbus-rtu-driver.md.tasks.json) | 📝 **Plan ready** (11 tasks) | **S (lowest)** | `pymodbus` `rtu_over_tcp` — CI-simulatable, no new infra |
|
| **1** | Modbus RTU (extend Modbus) | [design](2026-07-15-modbus-rtu-driver-design.md) | [plan](2026-07-24-modbus-rtu-driver.md) · [tasks](2026-07-24-modbus-rtu-driver.md.tasks.json) | 🟢 **Built — live gate PASSED** (11 tasks, branch `feat/modbus-rtu-driver`, pending merge) | **S (lowest)** | `pymodbus` `rtu_over_tcp` — CI-simulatable, no new infra |
|
||||||
| **1** | SQL poll | [design](2026-07-15-sql-poll-driver-design.md) | [plan](2026-07-24-sql-poll-driver.md) · [tasks](2026-07-24-sql-poll-driver.md.tasks.json) | 📝 **Plan ready** (22 tasks) | S–M | **existing central SQL Server** `10.100.0.35,14330` + SQLite unit |
|
| **1** | SQL poll | [design](2026-07-15-sql-poll-driver-design.md) | [plan](2026-07-24-sql-poll-driver.md) · [tasks](2026-07-24-sql-poll-driver.md.tasks.json) | 📝 **Plan ready** (22 tasks) | S–M | **existing central SQL Server** `10.100.0.35,14330` + SQLite unit |
|
||||||
| **2** | MTConnect Agent | [design](2026-07-15-mtconnect-driver-design.md) | [plan](2026-07-24-mtconnect-driver.md) · [tasks](2026-07-24-mtconnect-driver.md.tasks.json) | 📝 **Plan ready** (23 tasks) | S–M | Dockerized `mtconnect/cppagent` — CI-simulatable |
|
| **2** | MTConnect Agent | [design](2026-07-15-mtconnect-driver-design.md) | [plan](2026-07-24-mtconnect-driver.md) · [tasks](2026-07-24-mtconnect-driver.md.tasks.json) | 📝 **Plan ready** (23 tasks) | S–M | Dockerized `mtconnect/cppagent` — CI-simulatable |
|
||||||
| **2** | MQTT / Sparkplug B | [design](2026-07-15-mqtt-sparkplug-driver-design.md) | [plan](2026-07-24-mqtt-sparkplug-driver.md) · [tasks](2026-07-24-mqtt-sparkplug-driver.md.tasks.json) | 📝 **Plan ready** (27 tasks, P1+P2) | M–L | Mosquitto/EMQX + C# Sparkplug sim — CI-simulatable |
|
| **2** | MQTT / Sparkplug B | [design](2026-07-15-mqtt-sparkplug-driver-design.md) | [plan](2026-07-24-mqtt-sparkplug-driver.md) · [tasks](2026-07-24-mqtt-sparkplug-driver.md.tasks.json) | 📝 **Plan ready** (27 tasks, P1+P2) | M–L | Mosquitto/EMQX + C# Sparkplug sim — CI-simulatable |
|
||||||
@@ -92,16 +92,30 @@ marginal cost.
|
|||||||
Both are **fully CI-simulatable with zero new hardware**; Modbus RTU needs no new infra at all, and
|
Both are **fully CI-simulatable with zero new hardware**; Modbus RTU needs no new infra at all, and
|
||||||
SQL poll reuses the always-on central SQL Server. This is the recommended next build.
|
SQL poll reuses the always-on central SQL Server. This is the recommended next build.
|
||||||
|
|
||||||
### Modbus RTU — 📝 Plan ready
|
### Modbus RTU — 🟢 Built, live gate PASSED (branch `feat/modbus-rtu-driver`, pending merge)
|
||||||
- **Design:** [`2026-07-15-modbus-rtu-driver-design.md`](2026-07-15-modbus-rtu-driver-design.md)
|
- **Design:** [`2026-07-15-modbus-rtu-driver-design.md`](2026-07-15-modbus-rtu-driver-design.md)
|
||||||
- **Implementation plan:** [`2026-07-24-modbus-rtu-driver.md`](2026-07-24-modbus-rtu-driver.md) · [`.tasks.json`](2026-07-24-modbus-rtu-driver.md.tasks.json) — **11 tasks** (1 trivial / 5 small / 2 standard / 3 high-risk).
|
- **Implementation plan:** [`2026-07-24-modbus-rtu-driver.md`](2026-07-24-modbus-rtu-driver.md) · [`.tasks.json`](2026-07-24-modbus-rtu-driver.md.tasks.json) — **11 tasks** (1 trivial / 5 small / 2 standard / 3 high-risk), all complete via subagent-driven-development.
|
||||||
- **Scope:** extend the existing Modbus driver with a `Transport` selector (RTU CRC-16 + FC-aware
|
- **Scope:** extend the existing Modbus driver with a `Transport` selector (RTU CRC-16 + FC-aware
|
||||||
length, no TxId) + a `rtu_over_tcp` `pymodbus` docker profile + the AdminUI selector.
|
length, no TxId) + a `rtu_over_tcp` `pymodbus` docker profile + the AdminUI selector.
|
||||||
**Direct-serial transport is descoped** (user, 2026-07-15) — RTU-over-TCP via a serial→Ethernet
|
**Direct-serial transport is descoped** (user, 2026-07-15) — RTU-over-TCP via a serial→Ethernet
|
||||||
gateway is the only shipped mode, so there is no serial hardware gate.
|
gateway is the only shipped mode, so there is no serial hardware gate.
|
||||||
- **Fixture:** add an `rtu_over_tcp` profile to the existing Modbus integration fixture. First P1
|
- **Fixture:** added the `rtu_over_tcp` profile (`framer=rtu`, host `:5021`, co-runs with `standard`)
|
||||||
step is confirming the pymodbus simulator exposes the RTU framer on a TCP server.
|
to the Modbus integration fixture. **Unknown confirmed:** pymodbus 3.13's simulator DOES honour
|
||||||
- **Effort:** **S — the lowest on the roadmap.** Recommended first.
|
`framer=rtu` on a TCP server (wire-probed a pure RTU FC03 response, no MBAP) — so the simple profile
|
||||||
|
path was taken; **no stdlib fallback server was needed.**
|
||||||
|
- **Verification (all green):** unit suite **344/344**; full solution build 0 errors; the 2 RTU
|
||||||
|
integration tests pass **live** against the real `framer=rtu` fixture (read HR5→5, write+readback
|
||||||
|
HR200←4242). Per-task review chain (spec + code reviewers) + a final whole-branch review, all
|
||||||
|
approved-to-merge.
|
||||||
|
- **Live `/run` gate — PASSED (2026-07-24, docker-dev rebuilt from this branch):**
|
||||||
|
- AdminUI `/raw` Modbus **driver** config modal renders the new **Transport** selector (with the
|
||||||
|
operator hint) — set to `RtuOverTcp`, saved.
|
||||||
|
- **Device Test Connect → `OK · 23 MS`** — the probe built a `ModbusRtuOverTcpTransport` via the
|
||||||
|
factory and spoke **FC03 over real RTU framing** to `10.100.0.35:5021`.
|
||||||
|
- Authored raw tags HR5 (r/o) + HR200 (r/w) → **deployment `06ec1632` Sealed** (all 6 nodes acked).
|
||||||
|
- Client.CLI on `opc.tcp://localhost:4840` (`multi-role`/`password`): **read** `ns=2;s=rtu-gate/Device1/HR5`
|
||||||
|
→ **5, Good**; **write** `ns=2;s=rtu-gate/Device1/HR200` = 4242 → readback **4242, Good**.
|
||||||
|
- **Effort:** **S — the lowest on the roadmap.** Delivered first, as recommended.
|
||||||
|
|
||||||
### SQL poll — 📝 Plan ready
|
### SQL poll — 📝 Plan ready
|
||||||
- **Design:** [`2026-07-15-sql-poll-driver-design.md`](2026-07-15-sql-poll-driver-design.md)
|
- **Design:** [`2026-07-15-sql-poll-driver-design.md`](2026-07-15-sql-poll-driver-design.md)
|
||||||
|
|||||||
Reference in New Issue