fix(alarms): populate ConditionClassId/ConditionClassName on conditions (#475)
MaterialiseAlarmCondition never assigned the mandatory Part 9 ConditionType classification fields, so every condition event — native and scripted — shipped ConditionClassId = NodeId.Null (i=0) and ConditionClassName = empty text. Same mechanism as #473: Create() builds the mandatory children from the type's embedded definition but leaves them unset, and nothing downstream synthesises them (ReportEvent / InstanceStateSnapshot copy children verbatim). An HMI bucketing alarms by condition class dropped every OtOpcUa alarm as unclassified. Report BaseConditionClassType — Part 9's "no condition class modelled" value. This is the honest report: we hold no classification at the materialise seam. Deliberately NOT ProcessConditionClassType (the SDK sample's pick), which would assert a classification we cannot back and would be actively wrong for a Galaxy alarm whose upstream category is Safety/Diagnostics — trading a detectable null for an undetectable lie. Real per-alarm classification needs the driver's AlarmCategory carried to this deploy-time seam (it lives only on the runtime AlarmEventArgs transition today) and is a separate feature. Guards, both observed RED against the pre-fix server: - NativeAlarmEventIdentityFieldDeliveryTests: wire-level, its own select clause (the #473 test's clause mirrors ScadaBridge's exactly and its indices are load-bearing, so it is left untouched). The class fields are declared on ConditionType, not BaseEventType, so they are selected against that type. - NodeManagerAlarmSourceFieldsTests: node-level, native (Raw) + scripted (Uns). Stacked on #473 (PR #474) — merge after it.
This commit is contained in:
@@ -23,6 +23,12 @@ namespace ZB.MOM.WW.OtOpcUa.OpcUaServer.Tests;
|
||||
/// scripted), matching <c>ConditionId</c>. The leaf/display name stays on <c>ConditionName</c>, so
|
||||
/// no information is lost by SourceName carrying the unique id rather than the ambiguous leaf.
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// Issue #475 — the same mechanism leaves the mandatory <c>ConditionType</c> classification fields
|
||||
/// <c>ConditionClassId</c> / <c>ConditionClassName</c> unset. The contract locked in here: a server that
|
||||
/// does not model condition classes must still report <c>BaseConditionClassType</c> (Part 9's
|
||||
/// "no class modelled" value) rather than null. See <c>docs/AlarmTracking.md</c>.
|
||||
/// </para>
|
||||
/// </summary>
|
||||
public sealed class NodeManagerAlarmSourceFieldsTests : IDisposable
|
||||
{
|
||||
@@ -144,6 +150,52 @@ public sealed class NodeManagerAlarmSourceFieldsTests : IDisposable
|
||||
|
||||
}
|
||||
|
||||
/// <summary>#475 — a NATIVE condition (Raw realm) carries the mandatory ConditionType classification fields.
|
||||
/// We do not model condition classes, so Part 9's "no class modelled" value — BaseConditionClassType — is the
|
||||
/// conformant answer; the point is that it is a resolvable class NodeId a client can bucket on rather than a
|
||||
/// null that drops the alarm into an unclassified bin.</summary>
|
||||
[Trait("Category", "Unit")]
|
||||
[Fact]
|
||||
public async Task Native_condition_carries_ConditionClassId_and_ConditionClassName()
|
||||
{
|
||||
await using var host = await BootAsync();
|
||||
var nm = host.Nm;
|
||||
|
||||
nm.EnsureFolder(RawDeviceFolder, parentNodeId: null, displayName: "dev1", realm: AddressSpaceRealm.Raw);
|
||||
nm.MaterialiseAlarmCondition(RawAlarmPath, RawDeviceFolder, "HR200", "OffNormalAlarm", 700,
|
||||
realm: AddressSpaceRealm.Raw, isNative: true);
|
||||
|
||||
var condition = nm.TryGetAlarmCondition(RawAlarmPath, AddressSpaceRealm.Raw);
|
||||
condition.ShouldNotBeNull();
|
||||
|
||||
condition.ConditionClassId.ShouldNotBeNull();
|
||||
condition.ConditionClassId.Value.ShouldBe(ObjectTypeIds.BaseConditionClassType);
|
||||
|
||||
condition.ConditionClassName.ShouldNotBeNull();
|
||||
condition.ConditionClassName.Value.ShouldNotBeNull();
|
||||
condition.ConditionClassName.Value.Text.ShouldBe("BaseConditionClass");
|
||||
}
|
||||
|
||||
/// <summary>#475 — a SCRIPTED condition (UNS realm) carries the SAME classification fields: native and scripted
|
||||
/// share the materialise path, so neither may regress independently.</summary>
|
||||
[Trait("Category", "Unit")]
|
||||
[Fact]
|
||||
public async Task Scripted_condition_carries_ConditionClassId_and_ConditionClassName()
|
||||
{
|
||||
await using var host = await BootAsync();
|
||||
var nm = host.Nm;
|
||||
|
||||
nm.EnsureFolder("eq-4", parentNodeId: null, displayName: "Station 4", realm: AddressSpaceRealm.Uns);
|
||||
nm.MaterialiseAlarmCondition("tank-dry", "eq-4", "Tank Dry", "OffNormalAlarm", 700,
|
||||
realm: AddressSpaceRealm.Uns, isNative: false);
|
||||
|
||||
var condition = nm.TryGetAlarmCondition("tank-dry", AddressSpaceRealm.Uns);
|
||||
condition.ShouldNotBeNull();
|
||||
|
||||
condition.ConditionClassId!.Value.ShouldBe(ObjectTypeIds.BaseConditionClassType);
|
||||
condition.ConditionClassName!.Value.Text.ShouldBe("BaseConditionClass");
|
||||
}
|
||||
|
||||
/// <summary>A booted server + its node manager, disposed via <c>await using</c> so an assertion failure
|
||||
/// cannot leak a live server (and its bound port) into the rest of the test run.</summary>
|
||||
private sealed class BootedServer(OpcUaApplicationHost host, OtOpcUaNodeManager nm) : IAsyncDisposable
|
||||
|
||||