feat(alarms): condition Quality tracks source connectivity (#477)
Part 9 ConditionType.Quality was never assigned; default(StatusCode)==Good so every native + scripted condition reported Good unconditionally — a comms-lost device still showed a healthy, inactive, Good condition (a wrong-VALUE bug, distinct from the null-value #473/#475). Clients (and HMIs bucketing on IsGood) could not tell "genuinely inactive" from "lost contact". Layer 1 — make Quality a real, plumbed field: - AlarmConditionSnapshot gains OpcUaQuality Quality (default Good). - MaterialiseAlarmCondition sets it (native BadWaitingForInitialData, scripted Good). - WriteAlarmCondition projects snapshot.Quality; the delta-gate gains a Quality member so a quality-bucket change fires a Part 9 event. Layer 2 — drive native quality from driver connectivity (a comms-lost driver emits no alarm transitions, and an alarm-bearing raw tag has no value variable, so quality can't come from either existing channel): - DriverInstanceActor Tells parent ConnectivityChanged on Connected/Reconnecting. - DriverHostActor fans it to every native condition the driver owns as OpcUaPublishActor.AlarmQualityUpdate (Good on connect, Bad on disconnect). - New dedicated IOpcUaAddressSpaceSink.WriteAlarmQuality sets ONLY Quality and fires only on a bucket change — never touches Active/Acked/Retain (an active alarm that loses comms stays active). Not a full-snapshot re-projection, so it can't clobber severity/message and works for a never-fired condition. Forwarded through DeferredAddressSpaceSink (F10b trap; auto-verified by the reflection forwarding guard). Ungated by redundancy role; no /alerts row. Scripted conditions stay Good; worst-of-input quality deferred to #478 (Layer 3). Tests: node-level (materialise/project/no-clobber/unknown-node no-op), NativeAlarmProjector, DriverInstanceActor connectivity emission, DriverHostActor fan-out, OpcUaPublishActor routing, and the wire-level guard (Condition_event_Quality_tracks_source_connectivity_on_the_wire) — RED-verified against a simulated pre-fix always-Good server. Existing DriverInstanceActor parent probes ignore the new ConnectivityChanged. Docs: docs/AlarmTracking.md §"Condition source-data Quality (#477)"; design doc docs/plans/2026-07-17-alarm-condition-quality-477-design.md.
This commit is contained in:
@@ -76,6 +76,26 @@ public sealed class OpcUaPublishActorTests : RuntimeActorTestBase
|
||||
}, duration: TimeSpan.FromMilliseconds(500));
|
||||
}
|
||||
|
||||
/// <summary>#477 — AlarmQualityUpdate routes to sink.WriteAlarmQuality with the quality + realm.</summary>
|
||||
[Fact]
|
||||
public void AlarmQualityUpdate_routes_to_sink_WriteAlarmQuality()
|
||||
{
|
||||
var sink = new RecordingSink();
|
||||
var actor = Sys.ActorOf(OpcUaPublishActor.PropsForTests(sink: sink));
|
||||
|
||||
actor.Tell(new OpcUaPublishActor.AlarmQualityUpdate(
|
||||
"Plant/Modbus/dev1/temp_hi", OpcUaQuality.Bad, DateTime.UtcNow, Realm: AddressSpaceRealm.Raw));
|
||||
|
||||
AwaitAssert(() =>
|
||||
{
|
||||
sink.AlarmQualityQueue.Count.ShouldBe(1);
|
||||
sink.AlarmQualityQueue.TryPeek(out var q).ShouldBeTrue();
|
||||
q.AlarmNodeId.ShouldBe("Plant/Modbus/dev1/temp_hi");
|
||||
q.Quality.ShouldBe(OpcUaQuality.Bad);
|
||||
q.Realm.ShouldBe(AddressSpaceRealm.Raw);
|
||||
}, duration: TimeSpan.FromMilliseconds(500));
|
||||
}
|
||||
|
||||
/// <summary>Builds a test <see cref="AlarmConditionSnapshot"/> with sensible defaults so each test
|
||||
/// only specifies the fields it cares about.</summary>
|
||||
private static AlarmConditionSnapshot Snapshot(
|
||||
@@ -577,6 +597,8 @@ public sealed class OpcUaPublishActorTests : RuntimeActorTestBase
|
||||
public ConcurrentQueue<(string NodeId, object? Value, OpcUaQuality Quality, DateTime Ts)> ValueQueue { get; } = new();
|
||||
/// <summary>Gets the queue of recorded alarm condition updates.</summary>
|
||||
public ConcurrentQueue<(string AlarmNodeId, AlarmConditionSnapshot State, DateTime Ts)> AlarmQueue { get; } = new();
|
||||
/// <summary>Gets the queue of recorded alarm-quality annotations (#477).</summary>
|
||||
public ConcurrentQueue<(string AlarmNodeId, OpcUaQuality Quality, DateTime Ts, AddressSpaceRealm Realm)> AlarmQualityQueue { get; } = new();
|
||||
/// <summary>Count of rebuild calls.</summary>
|
||||
public int RebuildCalls;
|
||||
/// <summary>Gets the queue of recorded EnsureFolder calls.</summary>
|
||||
@@ -616,6 +638,10 @@ public sealed class OpcUaPublishActorTests : RuntimeActorTestBase
|
||||
public void WriteAlarmCondition(string alarmNodeId, AlarmConditionSnapshot state, DateTime ts, AddressSpaceRealm realm = AddressSpaceRealm.Uns) =>
|
||||
AlarmQueue.Enqueue((alarmNodeId, state, ts));
|
||||
|
||||
/// <summary>Records an alarm-quality annotation (#477).</summary>
|
||||
public void WriteAlarmQuality(string alarmNodeId, OpcUaQuality quality, DateTime ts, AddressSpaceRealm realm = AddressSpaceRealm.Uns) =>
|
||||
AlarmQualityQueue.Enqueue((alarmNodeId, quality, ts, realm));
|
||||
|
||||
/// <summary>Materialises an alarm condition (no-op in test).</summary>
|
||||
/// <param name="alarmNodeId">The alarm node ID.</param>
|
||||
/// <param name="equipmentNodeId">The equipment folder node ID.</param>
|
||||
|
||||