feat(alarms): condition Quality tracks source connectivity (#477)
v2-ci / build (pull_request) Successful in 4m49s
v2-ci / unit-tests (pull_request) Failing after 3h11m25s

Part 9 ConditionType.Quality was never assigned; default(StatusCode)==Good
so every native + scripted condition reported Good unconditionally — a
comms-lost device still showed a healthy, inactive, Good condition (a
wrong-VALUE bug, distinct from the null-value #473/#475). Clients (and HMIs
bucketing on IsGood) could not tell "genuinely inactive" from "lost contact".

Layer 1 — make Quality a real, plumbed field:
- AlarmConditionSnapshot gains OpcUaQuality Quality (default Good).
- MaterialiseAlarmCondition sets it (native BadWaitingForInitialData, scripted Good).
- WriteAlarmCondition projects snapshot.Quality; the delta-gate gains a Quality
  member so a quality-bucket change fires a Part 9 event.

Layer 2 — drive native quality from driver connectivity (a comms-lost driver
emits no alarm transitions, and an alarm-bearing raw tag has no value variable,
so quality can't come from either existing channel):
- DriverInstanceActor Tells parent ConnectivityChanged on Connected/Reconnecting.
- DriverHostActor fans it to every native condition the driver owns as
  OpcUaPublishActor.AlarmQualityUpdate (Good on connect, Bad on disconnect).
- New dedicated IOpcUaAddressSpaceSink.WriteAlarmQuality sets ONLY Quality and
  fires only on a bucket change — never touches Active/Acked/Retain (an active
  alarm that loses comms stays active). Not a full-snapshot re-projection, so it
  can't clobber severity/message and works for a never-fired condition.
  Forwarded through DeferredAddressSpaceSink (F10b trap; auto-verified by the
  reflection forwarding guard). Ungated by redundancy role; no /alerts row.

Scripted conditions stay Good; worst-of-input quality deferred to #478 (Layer 3).

Tests: node-level (materialise/project/no-clobber/unknown-node no-op),
NativeAlarmProjector, DriverInstanceActor connectivity emission, DriverHostActor
fan-out, OpcUaPublishActor routing, and the wire-level guard
(Condition_event_Quality_tracks_source_connectivity_on_the_wire) — RED-verified
against a simulated pre-fix always-Good server. Existing DriverInstanceActor
parent probes ignore the new ConnectivityChanged.

Docs: docs/AlarmTracking.md §"Condition source-data Quality (#477)";
design doc docs/plans/2026-07-17-alarm-condition-quality-477-design.md.
This commit is contained in:
Joseph Doherty
2026-07-17 15:10:04 -04:00
parent f6a3c31b60
commit db751d12a5
30 changed files with 752 additions and 7 deletions
@@ -163,6 +163,8 @@ public sealed class AddressSpaceApplierFailureSurfaceTests
public void WriteValue(string nodeId, object? value, OpcUaQuality quality, DateTime sourceTimestampUtc, AddressSpaceRealm realm = AddressSpaceRealm.Uns) { }
public void WriteAlarmQuality(string alarmNodeId, OpcUaQuality quality, DateTime sourceTimestampUtc, AddressSpaceRealm realm) { }
public void WriteAlarmCondition(string alarmNodeId, AlarmConditionSnapshot state, DateTime sourceTimestampUtc, AddressSpaceRealm realm = AddressSpaceRealm.Uns)
{
if (ThrowOnAlarmWrite) throw new InvalidOperationException("simulated WriteAlarmCondition fault");