fix(scripting): give scripted-alarm predicates the configured run budget, not 250 ms (lmxopcua#779)
DriverHostActor built ScriptedAlarmEngine without a scriptTimeout, so every
production alarm predicate fell back to TimedScriptEvaluator.DefaultTimeout
(250 ms) while virtual tags and Calculation tags ran on 2 s. History shows no
decision behind it: 250 ms is the generic Phase-7 A.4 default, the VT
evaluator moved to 2 s in F8b (219d10a2) and the alarm engine was simply never
given a value.
- New node-wide Scripting:RunTimeout (default 2 s, clamped to (0, 60 s],
non-positive -> default, each clamp a startup Warning) on ScriptingOptions.
- The VT evaluator and the alarm engine default to it; DriverHostActor now
builds the engine through CreateScriptedAlarmEngine, which passes it
explicitly. Calculation keeps its per-driver runTimeoutMs.
- Docs: ScriptEditor (config table), ScriptedAlarms, VirtualTags.
Tests: ScriptedAlarmEngineBudgetTests (a 600 ms predicate now completes and
activates; default and configured budgets), ScriptedAlarmEngineBudgetWiringTests
(the host-built engine), ScriptingOptionsBindingTests (bind + clamps). The
engine and wiring tests fail with the old 250 ms default restored.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
This commit is contained in:
@@ -57,7 +57,8 @@ public sealed class RoslynVirtualTagEvaluator : IVirtualTagEvaluator, IScriptCac
|
||||
/// <summary>Initializes a new RoslynVirtualTagEvaluator with the given loggers and optional timeout.</summary>
|
||||
/// <param name="logger">Logger for recording compilation and execution errors (host diagnostics).</param>
|
||||
/// <param name="scriptRoot">Root script logger; user <c>ctx.Logger.*</c> output flows through this to the Script-log page.</param>
|
||||
/// <param name="runTimeout">Maximum execution time for each script; defaults to 2 seconds if not specified.</param>
|
||||
/// <param name="runTimeout">Maximum execution time for each script; null ⇒ <see cref="ScriptingOptions.RunTimeout"/>
|
||||
/// of <paramref name="scripting"/> (2 s by default).</param>
|
||||
/// <param name="scripting">Run-guard budget + quarantine threshold (the <c>Scripting</c> section); null ⇒ defaults.</param>
|
||||
public RoslynVirtualTagEvaluator(
|
||||
ILogger<RoslynVirtualTagEvaluator> logger,
|
||||
@@ -67,7 +68,7 @@ public sealed class RoslynVirtualTagEvaluator : IVirtualTagEvaluator, IScriptCac
|
||||
{
|
||||
_logger = logger;
|
||||
_scriptRoot = (scriptRoot ?? throw new ArgumentNullException(nameof(scriptRoot))).Logger;
|
||||
_runTimeout = runTimeout ?? TimeSpan.FromSeconds(2);
|
||||
_runTimeout = runTimeout ?? (scripting ?? new ScriptingOptions()).Sanitized(out _).RunTimeout;
|
||||
_guard = new ScriptRunGuard(scripting, _scriptRoot);
|
||||
}
|
||||
|
||||
|
||||
@@ -367,8 +367,9 @@ if (hasDriver)
|
||||
// F8b — production virtual-tag evaluator (Roslyn-compiled scripts cached per expression).
|
||||
// Replaces the F8-default NullVirtualTagEvaluator so VirtualTagActor evaluates real user
|
||||
// scripts at runtime.
|
||||
// Node-wide script run-guard knobs (Scripting:MaxAllocBytesPerRun / QuarantineAfterConsecutiveTimeouts /
|
||||
// StuckOrphanQuarantineFactor). Bound once and clamped into sane ranges here, so an absurd value is a startup
|
||||
// Node-wide script run-guard knobs (Scripting:RunTimeout / MaxAllocBytesPerRun / QuarantineAfterConsecutiveTimeouts /
|
||||
// StuckOrphanQuarantineFactor). RunTimeout is the per-run budget of virtual tags and scripted-alarm predicates
|
||||
// (lmxopcua#779 — the alarm engine used to fall back to a 250 ms default instead). Bound once and clamped into sane ranges here, so an absurd value is a startup
|
||||
// Warning rather than an OverflowException inside a script run. The one instance is shared by every script
|
||||
// seam on the node: the virtual-tag evaluator below, the scripted-alarm engine (DriverHostActor, via
|
||||
// WithOtOpcUaRuntimeActors) and every Calculation driver (DriverFactoryBootstrap).
|
||||
|
||||