Phase 3 PR 52 -- Modbus exception-code -> OPC UA StatusCode translation. Before this PR every server-side Modbus exception AND every transport-layer failure collapsed to BadInternalError (0x80020000) in the driver's Read/Write results, making field diagnosis 'is this a tag misconfig or a driver bug?' impossible from the OPC UA client side. PR 52 adds a MapModbusExceptionToStatus helper that translates per spec: 01 Illegal Function -> BadNotSupported (0x803D0000); 02 Illegal Data Address -> BadOutOfRange (0x803C0000); 03 Illegal Data Value -> BadOutOfRange; 04 Server Failure -> BadDeviceFailure (0x80550000); 05/06 Acknowledge/Busy -> BadDeviceFailure; 0A/0B Gateway -> BadCommunicationError (0x80050000); unknown -> BadInternalError fallback. Non-Modbus failures (socket drop, timeout, malformed frame) in ReadAsync are now distinguished from tag-level faults: they map to BadCommunicationError so operators check network/PLC reachability rather than tag definitions. Why per-DL205: docs/v2/dl205.md documents DL205/DL260 returning only codes 01-04 with specific triggers -- exception 04 specifically means 'CPU in PROGRAM mode during a protected write', which is operator-recoverable by switching the CPU to RUN; surfacing it as BadDeviceFailure (not BadInternalError) makes the fix obvious. Changes in ModbusDriver: Read catch-chain now ModbusException first (-> mapper), generic Exception second (-> BadCommunicationError); Write catch-chain same pattern but generic Exception stays BadInternalError because write failures can legitimately come from EncodeRegister (out-of-range value) which is a driver-layer fault. Unit tests: MapModbusExceptionToStatus theory exercising every code in the table including the 0xFF fallback; Read_surface_exception_02_as_BadOutOfRange with an ExceptionRaisingTransport that forces code 02; Write_surface_exception_04_as_BadDeviceFailure for CPU-mode faults; Read_non_modbus_failure_maps_to_BadCommunicationError with a NonModbusFailureTransport that raises EndOfStreamException. 115/115 Modbus.Tests pass. Integration test: DL205ExceptionCodeTests.DL205_FC03_at_unmapped_register_returns_BadOutOfRange reads HR[16383] which is beyond the seeded uint16 cells on the dl205.json profile; pymodbus returns exception 02 and the driver surfaces BadOutOfRange. 11/11 DL205 integration tests pass with MODBUS_SIM_PROFILE=dl205.

This commit is contained in:
Joseph Doherty
2026-04-18 22:28:37 -04:00
parent 9892a0253d
commit cde018aec1
3 changed files with 178 additions and 1 deletions

View File

@@ -0,0 +1,88 @@
using Shouldly;
using Xunit;
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.Tests;
/// <summary>
/// Unit tests for the Modbus-exception-code → OPC UA StatusCode mapping added in PR 52.
/// Before PR 52 every server exception + every transport failure collapsed to
/// BadInternalError (0x80020000), which made field diagnosis "is this a bad tag or a bad
/// driver?" impossible. These tests lock in the translation table documented on
/// <see cref="ModbusDriver.MapModbusExceptionToStatus"/>.
/// </summary>
[Trait("Category", "Unit")]
public sealed class ModbusExceptionMapperTests
{
[Theory]
[InlineData((byte)0x01, 0x803D0000u)] // Illegal Function → BadNotSupported
[InlineData((byte)0x02, 0x803C0000u)] // Illegal Data Address → BadOutOfRange
[InlineData((byte)0x03, 0x803C0000u)] // Illegal Data Value → BadOutOfRange
[InlineData((byte)0x04, 0x80550000u)] // Server Failure → BadDeviceFailure
[InlineData((byte)0x05, 0x80550000u)] // Acknowledge (long op) → BadDeviceFailure
[InlineData((byte)0x06, 0x80550000u)] // Server Busy → BadDeviceFailure
[InlineData((byte)0x0A, 0x80050000u)] // Gateway path unavailable → BadCommunicationError
[InlineData((byte)0x0B, 0x80050000u)] // Gateway target failed to respond → BadCommunicationError
[InlineData((byte)0xFF, 0x80020000u)] // Unknown code → BadInternalError fallback
public void MapModbusExceptionToStatus_returns_informative_status(byte code, uint expected)
=> ModbusDriver.MapModbusExceptionToStatus(code).ShouldBe(expected);
private sealed class ExceptionRaisingTransport(byte exceptionCode) : IModbusTransport
{
public Task ConnectAsync(CancellationToken ct) => Task.CompletedTask;
public Task<byte[]> SendAsync(byte unitId, byte[] pdu, CancellationToken ct)
=> Task.FromException<byte[]>(new ModbusException(pdu[0], exceptionCode, $"fc={pdu[0]} code={exceptionCode}"));
public ValueTask DisposeAsync() => ValueTask.CompletedTask;
}
[Fact]
public async Task Read_surface_exception_02_as_BadOutOfRange_not_BadInternalError()
{
var transport = new ExceptionRaisingTransport(exceptionCode: 0x02);
var tag = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16);
var opts = new ModbusDriverOptions { Host = "fake", Tags = [tag], Probe = new ModbusProbeOptions { Enabled = false } };
await using var drv = new ModbusDriver(opts, "modbus-1", _ => transport);
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
var results = await drv.ReadAsync(["T"], TestContext.Current.CancellationToken);
results[0].StatusCode.ShouldBe(0x803C0000u, "FC03 at an unmapped register must bubble out as BadOutOfRange so operators can spot a bad tag config");
}
[Fact]
public async Task Write_surface_exception_04_as_BadDeviceFailure()
{
var transport = new ExceptionRaisingTransport(exceptionCode: 0x04);
var tag = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16);
var opts = new ModbusDriverOptions { Host = "fake", Tags = [tag], Probe = new ModbusProbeOptions { Enabled = false } };
await using var drv = new ModbusDriver(opts, "modbus-1", _ => transport);
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
var writes = await drv.WriteAsync(
[new WriteRequest("T", (short)42)],
TestContext.Current.CancellationToken);
writes[0].StatusCode.ShouldBe(0x80550000u, "FC06 returning exception 04 (CPU in PROGRAM mode) maps to BadDeviceFailure");
}
private sealed class NonModbusFailureTransport : IModbusTransport
{
public Task ConnectAsync(CancellationToken ct) => Task.CompletedTask;
public Task<byte[]> SendAsync(byte unitId, byte[] pdu, CancellationToken ct)
=> Task.FromException<byte[]>(new EndOfStreamException("socket closed mid-response"));
public ValueTask DisposeAsync() => ValueTask.CompletedTask;
}
[Fact]
public async Task Read_non_modbus_failure_maps_to_BadCommunicationError_not_BadInternalError()
{
// Socket drop / timeout / malformed frame → transport-layer failure. Should surface
// distinctly from tag-level faults so operators know to check the network, not the config.
var tag = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16);
var opts = new ModbusDriverOptions { Host = "fake", Tags = [tag], Probe = new ModbusProbeOptions { Enabled = false } };
await using var drv = new ModbusDriver(opts, "modbus-1", _ => new NonModbusFailureTransport());
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
var results = await drv.ReadAsync(["T"], TestContext.Current.CancellationToken);
results[0].StatusCode.ShouldBe(0x80050000u);
}
}