Phase 3 PR 52 -- Modbus exception-code -> OPC UA StatusCode translation. Before this PR every server-side Modbus exception AND every transport-layer failure collapsed to BadInternalError (0x80020000) in the driver's Read/Write results, making field diagnosis 'is this a tag misconfig or a driver bug?' impossible from the OPC UA client side. PR 52 adds a MapModbusExceptionToStatus helper that translates per spec: 01 Illegal Function -> BadNotSupported (0x803D0000); 02 Illegal Data Address -> BadOutOfRange (0x803C0000); 03 Illegal Data Value -> BadOutOfRange; 04 Server Failure -> BadDeviceFailure (0x80550000); 05/06 Acknowledge/Busy -> BadDeviceFailure; 0A/0B Gateway -> BadCommunicationError (0x80050000); unknown -> BadInternalError fallback. Non-Modbus failures (socket drop, timeout, malformed frame) in ReadAsync are now distinguished from tag-level faults: they map to BadCommunicationError so operators check network/PLC reachability rather than tag definitions. Why per-DL205: docs/v2/dl205.md documents DL205/DL260 returning only codes 01-04 with specific triggers -- exception 04 specifically means 'CPU in PROGRAM mode during a protected write', which is operator-recoverable by switching the CPU to RUN; surfacing it as BadDeviceFailure (not BadInternalError) makes the fix obvious. Changes in ModbusDriver: Read catch-chain now ModbusException first (-> mapper), generic Exception second (-> BadCommunicationError); Write catch-chain same pattern but generic Exception stays BadInternalError because write failures can legitimately come from EncodeRegister (out-of-range value) which is a driver-layer fault. Unit tests: MapModbusExceptionToStatus theory exercising every code in the table including the 0xFF fallback; Read_surface_exception_02_as_BadOutOfRange with an ExceptionRaisingTransport that forces code 02; Write_surface_exception_04_as_BadDeviceFailure for CPU-mode faults; Read_non_modbus_failure_maps_to_BadCommunicationError with a NonModbusFailureTransport that raises EndOfStreamException. 115/115 Modbus.Tests pass. Integration test: DL205ExceptionCodeTests.DL205_FC03_at_unmapped_register_returns_BadOutOfRange reads HR[16383] which is beyond the seeded uint16 cells on the dl205.json profile; pymodbus returns exception 02 and the driver surfaces BadOutOfRange. 11/11 DL205 integration tests pass with MODBUS_SIM_PROFILE=dl205.
This commit is contained in:
@@ -0,0 +1,53 @@
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.DL205;
|
||||
|
||||
/// <summary>
|
||||
/// Verifies the driver's Modbus-exception → OPC UA StatusCode translation end-to-end
|
||||
/// against the dl205.json pymodbus profile. pymodbus returns exception 02 (Illegal Data
|
||||
/// Address) for reads outside the configured register ranges, matching real DL205/DL260
|
||||
/// firmware behavior per <c>docs/v2/dl205.md</c> §exception-codes. The driver must surface
|
||||
/// that as <c>BadOutOfRange</c> (0x803C0000) — not <c>BadInternalError</c> — so the
|
||||
/// operator sees a tag-config diagnosis instead of a generic driver-fault message.
|
||||
/// </summary>
|
||||
[Collection(ModbusSimulatorCollection.Name)]
|
||||
[Trait("Category", "Integration")]
|
||||
[Trait("Device", "DL205")]
|
||||
public sealed class DL205ExceptionCodeTests(ModbusSimulatorFixture sim)
|
||||
{
|
||||
[Fact]
|
||||
public async Task DL205_FC03_at_unmapped_register_returns_BadOutOfRange()
|
||||
{
|
||||
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
||||
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "dl205",
|
||||
StringComparison.OrdinalIgnoreCase))
|
||||
{
|
||||
Assert.Skip("MODBUS_SIM_PROFILE != dl205 — skipping.");
|
||||
}
|
||||
|
||||
// Address 16383 is the last cell of hr-size=16384 in dl205.json; address 16384 is
|
||||
// beyond the configured HR range. pymodbus validates and returns exception 02
|
||||
// (Illegal Data Address).
|
||||
var options = new ModbusDriverOptions
|
||||
{
|
||||
Host = sim.Host,
|
||||
Port = sim.Port,
|
||||
UnitId = 1,
|
||||
Timeout = TimeSpan.FromSeconds(2),
|
||||
Tags =
|
||||
[
|
||||
new ModbusTagDefinition("Unmapped",
|
||||
ModbusRegion.HoldingRegisters, Address: 16383,
|
||||
DataType: ModbusDataType.UInt16, Writable: false),
|
||||
],
|
||||
Probe = new ModbusProbeOptions { Enabled = false },
|
||||
};
|
||||
await using var driver = new ModbusDriver(options, driverInstanceId: "dl205-exc");
|
||||
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
|
||||
var results = await driver.ReadAsync(["Unmapped"], TestContext.Current.CancellationToken);
|
||||
results[0].StatusCode.ShouldBe(0x803C0000u,
|
||||
"DL205 returns exception 02 for an FC03 at an unmapped register; driver must translate to BadOutOfRange (not BadInternalError)");
|
||||
}
|
||||
}
|
||||