docs: clarify S7 counter evidence and fixture limits
This commit is contained in:
@@ -1465,7 +1465,7 @@ public sealed class S7Driver
|
||||
{
|
||||
// AREA precedence first (before the DataType switch): a Timer (T{n}) decodes its 2-byte
|
||||
// S5TIME word to a duration in SECONDS via S7.Net's Timer.FromByteArray (returns double);
|
||||
// a Counter (C{n}) decodes its 2-byte word to a COUNT via Counter.FromByteArray (returns
|
||||
// a Counter (C{n}) exposes its 2-byte RAW WORD via Counter.FromByteArray (returns
|
||||
// ushort, surfaced as a non-negative int to match the tag's Int32 type). Routing on Area
|
||||
// here is essential: a Timer tag is typed Float64, so letting it fall to the Float64 arm
|
||||
// below would ReadDoubleBigEndian over a 2-byte block = garbage/throw. Boxed explicitly so
|
||||
@@ -1474,11 +1474,12 @@ public sealed class S7Driver
|
||||
return (object)global::S7.Net.Types.Timer.FromByteArray(block);
|
||||
if (addr.Area is S7Area.Counter)
|
||||
{
|
||||
// NOTE: S7.Net Counter.FromByteArray returns the RAW big-endian word ((bytes[0]<<8)|bytes[1]),
|
||||
// NOT a BCD decode. On classic S7-300/400 the C-area word is BCD (0-999), so on that hardware
|
||||
// this raw value can differ from the displayed count; S7-1200/1500 use IEC/DB counters (plain
|
||||
// ints), where it is correct. Surfacing S7.Net's value verbatim is the faithful choice; BCD
|
||||
// reinterpretation for legacy C-area counters is a live-hardware-gated follow-up.
|
||||
// S7.Net Counter.FromByteArray returns the raw big-endian word ((bytes[0]<<8)|bytes[1]),
|
||||
// without BCD reinterpretation. This preserves the raw value, not a verified PLC count:
|
||||
// S7comm C-area response encoding still needs independent raw bytes and PLC-side
|
||||
// count/binary/BCD references (#616). CPU family alone does not prove that encoding.
|
||||
// IEC counter integers in DB memory take the DB type codec, not this C-area path;
|
||||
// S7-1500 also has legacy SIMATIC counters. See docs/drivers/S7.md for the evidence gate.
|
||||
return (object)(int)global::S7.Net.Types.Counter.FromByteArray(block);
|
||||
}
|
||||
|
||||
|
||||