Phase 3 PR 45 -- DL205 string byte-order quirk (low-byte-first ASCII packing). Adds ModbusStringByteOrder enum {HighByteFirst, LowByteFirst} + StringByteOrder field on ModbusTagDefinition (default HighByteFirst, the standard Modbus convention). DecodeRegister + EncodeRegister String branches now respect per-tag byte order. Under LowByteFirst each register packs the first char in the low byte instead of the high byte -- the AutomationDirect DirectLOGIC DL205/DL260/DL350 family's headline string quirk. Without the flag the driver decodes 'eHllo' garbage from HR[1040..1042] even though wire bytes are identical. Unit tests: String_LowByteFirst_decodes_DL205_packed_Hello (5 chars across 3 regs with nul pad), String_LowByteFirst_decode_truncates_at_first_nul, String_LowByteFirst_encode_round_trips_with_decode (asserts exact DL205-documented byte sequence {0x65,0x48,0x6C,0x6C,0x00,0x6F} + symmetric encode->decode), String_HighByteFirst_and_LowByteFirst_differ_on_same_wire (control: same wire, different flag => different decode). 56/56 Modbus.Tests pass. Integration test: DL205StringQuirkTests.DL205_string_low_byte_first_decodes_Hello_from_HR1040 against the dl205.json pymodbus profile; reads HR[1040..1042] with both flags on the same tag map and asserts LowByteFirst='Hello' + HighByteFirst!='Hello'. Gated on MODBUS_SIM_PROFILE=dl205 since the standard profile doesn't seed HR[1040..1042]. Verified 2/2 integration tests pass against running pymodbus dl205 simulator. Baseline for PR 46 (BCD decoder), PR 47 (V-memory octal helper), PR 48 (CDAB float order), PR 49 (FC03/FC16 per-device caps) -- each lands its own DL205_<behavior> test class in tests/.../DL205/.
This commit is contained in:
@@ -55,6 +55,12 @@ public sealed class ModbusProbeOptions
|
||||
/// <param name="ByteOrder">Word ordering for multi-register types. Ignored for Bool / Int16 / UInt16 / BitInRegister / String.</param>
|
||||
/// <param name="BitIndex">For <c>DataType = BitInRegister</c>: which bit of the holding register (0-15, LSB-first).</param>
|
||||
/// <param name="StringLength">For <c>DataType = String</c>: number of ASCII characters (2 per register, rounded up).</param>
|
||||
/// <param name="StringByteOrder">
|
||||
/// Per-register byte order for <c>DataType = String</c>. Standard Modbus packs the first
|
||||
/// character in the high byte (<see cref="ModbusStringByteOrder.HighByteFirst"/>).
|
||||
/// AutomationDirect DirectLOGIC (DL205/DL260) and a few legacy families pack the first
|
||||
/// character in the low byte instead — see <c>docs/v2/dl205.md</c> §strings.
|
||||
/// </param>
|
||||
public sealed record ModbusTagDefinition(
|
||||
string Name,
|
||||
ModbusRegion Region,
|
||||
@@ -63,7 +69,8 @@ public sealed record ModbusTagDefinition(
|
||||
bool Writable = true,
|
||||
ModbusByteOrder ByteOrder = ModbusByteOrder.BigEndian,
|
||||
byte BitIndex = 0,
|
||||
ushort StringLength = 0);
|
||||
ushort StringLength = 0,
|
||||
ModbusStringByteOrder StringByteOrder = ModbusStringByteOrder.HighByteFirst);
|
||||
|
||||
public enum ModbusRegion { Coils, DiscreteInputs, InputRegisters, HoldingRegisters }
|
||||
|
||||
@@ -95,3 +102,17 @@ public enum ModbusByteOrder
|
||||
BigEndian,
|
||||
WordSwap,
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Per-register byte order for ASCII strings packed 2 chars per register. Standard Modbus
|
||||
/// convention is <see cref="HighByteFirst"/> — the first character of each pair occupies
|
||||
/// the high byte of the register. AutomationDirect DirectLOGIC (DL205, DL260, DL350) and a
|
||||
/// handful of legacy controllers pack <see cref="LowByteFirst"/>, which inverts that within
|
||||
/// each register. Word ordering across multiple registers is always ascending address for
|
||||
/// strings — only the byte order inside each register flips.
|
||||
/// </summary>
|
||||
public enum ModbusStringByteOrder
|
||||
{
|
||||
HighByteFirst,
|
||||
LowByteFirst,
|
||||
}
|
||||
|
||||