fix(ablegacy): Test Connect normalises the probe address like the driver (#660)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
This commit is contained in:
@@ -100,7 +100,7 @@ physical inputs and may reject the write.
|
||||
re-parses carry identical numbers. This is not a double conversion: libplctag's `pccc.c`
|
||||
(`parse_pccc_elem_num` / `parse_pccc_bit_num`) parses decimal numerals only (a FIXME there says octal is
|
||||
unsupported), so the driver must convert. Pinned by `Plc5_io_indices_are_octal` (`I:017/17` -> `I:15/15`).
|
||||
The connectivity-probe address is normalised the same way.
|
||||
The connectivity-probe address is normalised the same way — by both the driver's probe loop and the Test Connect probe, through one helper (`AbLegacyProbeAddress.Normalise`, #660); an unparseable Test Connect probe address fails cleanly ("not a valid AbLegacy address") instead of reaching the transport. Normalisation yields the canonical name; the libplctag `S:0` → `S2:0` translation (#659) happens downstream in the runtime, so the two compose.
|
||||
- ⚠️ **Behaviour change / migration.** Before this change a PLC-5 `I:`/`O:` address was passed to libplctag as
|
||||
written, i.e. read as **decimal**. An address copied from RSLogix in octal (e.g. `I:017`) therefore read the
|
||||
wrong word, and an authored decimal such as `I:1/12` now means bit 10 (octal 12). A previously "working"
|
||||
|
||||
Reference in New Issue