fix(alarms): #647 re-review — re-statement needs the same message; CNC refusal is not comms loss; worst-of health
R1: NativeAlarmProjector treats Raise-on-Active as a re-statement only when the message matches what
the condition shows; a different alarm appearing during a respawn un-acks and writes its alerts row.
FOCAS condition messages are a deterministic function of the matched set (tested across fresh driver
instances and reordered lists); Runtime E2E now covers both the same alarm and a new one during a
respawn. Residual (source message determinism) documented in AlarmTracking.md.
R2: a non-OK cnc_rdalmmsg2 return is thrown as FocasWireException{Rc} and classified as a CNC
refusal: conditions get a quality-only BadNotSupported once, one Warning, polling continues, and
driver health is untouched (no 90 s watchdog reconnect loop on a production control). Only transport
faults degrade (falsification control in the test).
R3: alarm-path health is tracked apart from the value path and combined in GetHealth: worst state,
later LastSuccessfulRead. A good value read can no longer mask a failing alarm read (no per-poll
/hosts flip) and a good alarm read cannot mask a value Degraded.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
This commit is contained in:
@@ -12,7 +12,7 @@ namespace ZB.MOM.WW.OtOpcUa.Runtime.Drivers;
|
||||
/// </summary>
|
||||
public sealed class NativeAlarmProjector
|
||||
{
|
||||
private readonly Dictionary<string, (bool Active, bool Acked)> _prior = new(StringComparer.Ordinal);
|
||||
private readonly Dictionary<string, (bool Active, bool Acked, string? Message)> _prior = new(StringComparer.Ordinal);
|
||||
|
||||
/// <summary>Project an alarm transition onto the full condition snapshot for <paramref name="nodeId"/>.</summary>
|
||||
/// <param name="nodeId">The materialised condition node's id (the projection's state key).</param>
|
||||
@@ -22,7 +22,8 @@ public sealed class NativeAlarmProjector
|
||||
|
||||
/// <summary>
|
||||
/// Project an alarm transition, reporting whether it was a <b>re-statement</b> (Gitea #647 review): a
|
||||
/// <see cref="AlarmTransitionKind.Raise"/> on a condition already projected Active. That is what a driver
|
||||
/// <see cref="AlarmTransitionKind.Raise"/> on a condition already projected Active WITH THE SAME MESSAGE
|
||||
/// (re-review R1 — a different message is a different alarm, and un-acks). That is what a driver
|
||||
/// whose told-record died with its instance sends after a deploy respawns it — the alarm it re-reads is the
|
||||
/// one the server already shows, so the acknowledgement is KEPT and the host writes no second "Activated"
|
||||
/// row. Only <see cref="AlarmTransitionKind.Retrigger"/> (or inactive → active) un-acknowledges; a source
|
||||
@@ -34,19 +35,25 @@ public sealed class NativeAlarmProjector
|
||||
/// <returns>The full Part 9 condition snapshot to write to the node.</returns>
|
||||
public AlarmConditionSnapshot Project(string nodeId, AlarmEventArgs e, out bool restatement)
|
||||
{
|
||||
var prev = _prior.TryGetValue(nodeId, out var p) ? p : (Active: false, Acked: true);
|
||||
var prev = _prior.TryGetValue(nodeId, out var p) ? p : (Active: false, Acked: true, Message: (string?)null);
|
||||
// #626: a source with a finer scale than the four buckets supplies the exact Part 9 severity.
|
||||
var sev = e.OpcUaSeverity is { } exact ? (ushort)Math.Clamp(exact, 1, 1000) : MapSeverity(e.Severity);
|
||||
restatement = e.Kind == AlarmTransitionKind.Raise && prev.Active;
|
||||
// Gitea #647 re-review R1: only a Raise saying the SAME thing the condition already shows is a re-statement.
|
||||
// A respawned driver cannot tell "the alarm I was showing" from "a different one that appeared while I was
|
||||
// down", so a different message is treated as a new statement — un-acked, with its alerts row. Comparing the
|
||||
// message is conservative: any difference (a sources' messages are deterministic for an unchanged statement)
|
||||
// errs toward showing the operator an unacknowledged alarm, never toward hiding one behind a stale ack.
|
||||
restatement = e.Kind == AlarmTransitionKind.Raise && prev.Active
|
||||
&& string.Equals(prev.Message?.Trim(), e.Message.Trim(), StringComparison.Ordinal);
|
||||
var (active, acked) = e.Kind switch
|
||||
{
|
||||
AlarmTransitionKind.Raise when prev.Active => (true, prev.Acked),
|
||||
AlarmTransitionKind.Raise when restatement => (true, prev.Acked),
|
||||
AlarmTransitionKind.Raise or AlarmTransitionKind.Retrigger => (true, false),
|
||||
AlarmTransitionKind.Acknowledge => (prev.Active, true),
|
||||
AlarmTransitionKind.Clear => (false, prev.Acked),
|
||||
_ => (prev.Active, prev.Acked),
|
||||
};
|
||||
_prior[nodeId] = (active, acked);
|
||||
_prior[nodeId] = (active, acked, e.Message);
|
||||
return new AlarmConditionSnapshot(
|
||||
Active: active, Acknowledged: acked, Confirmed: true, Enabled: true,
|
||||
Shelving: AlarmShelvingKind.Unshelved, Severity: sev, Message: e.Message,
|
||||
@@ -64,7 +71,7 @@ public sealed class NativeAlarmProjector
|
||||
/// <param name="nodeId">The acknowledged condition node id.</param>
|
||||
public void MarkAcknowledged(string nodeId)
|
||||
{
|
||||
if (_prior.TryGetValue(nodeId, out var p)) _prior[nodeId] = (p.Active, true);
|
||||
if (_prior.TryGetValue(nodeId, out var p)) _prior[nodeId] = (p.Active, true, p.Message);
|
||||
}
|
||||
|
||||
/// <summary>Clears all tracked per-node state.</summary>
|
||||
|
||||
Reference in New Issue