review(Driver.Modbus.Addressing): fix misleading byte-order hint + drop dead overflow guard
Re-review at 7286d320. -010 (Low): TryParseByteOrder no longer lists REAL/DINT/UINT as type
codes (gave wrong 'field 2' advice -> second parse error); generic byte-order error instead.
-011 (Low): remove unreachable offsetWithinBank>ushort.MaxValue guard (DecodeOctalVAddress
caps at 0xFFFF). + TDD.
This commit is contained in:
@@ -4,8 +4,8 @@
|
|||||||
|---|---|
|
|---|---|
|
||||||
| Module | `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.Modbus.Addressing` |
|
| Module | `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.Modbus.Addressing` |
|
||||||
| Reviewer | Claude Code |
|
| Reviewer | Claude Code |
|
||||||
| Review date | 2026-05-22 |
|
| Review date | 2026-06-19 |
|
||||||
| Commit reviewed | `76d35d1` |
|
| Commit reviewed | `7286d320` |
|
||||||
| Status | Reviewed |
|
| Status | Reviewed |
|
||||||
| Open findings | 0 |
|
| Open findings | 0 |
|
||||||
|
|
||||||
@@ -263,3 +263,83 @@ state precisely that the check is reached only by the 6-digit form in practice,
|
|||||||
both for safety rather than relying on the digit-count invariant. Pure documentation change —
|
both for safety rather than relying on the digit-count invariant. Pure documentation change —
|
||||||
no behavioural change; the existing `ModbusModiconAddressTests` already pin the cross-region
|
no behavioural change; the existing `ModbusModiconAddressTests` already pin the cross-region
|
||||||
5-digit ranges (00001..09999 / 10001..19999 / 30001..39999 / 40001..49999).
|
5-digit ranges (00001..09999 / 10001..19999 / 30001..39999 / 40001..49999).
|
||||||
|
|
||||||
|
## Re-review 2026-06-19 (commit 7286d320)
|
||||||
|
|
||||||
|
All nine prior findings (-001 through -009) are Resolved. The diff since `76d35d1` consists
|
||||||
|
entirely of the fixes for those findings plus XML doc additions. This re-review covers all
|
||||||
|
10 checklist categories at HEAD for the 7 src files (1227 LOC) and the 4 test files.
|
||||||
|
|
||||||
|
#### Re-review checklist
|
||||||
|
|
||||||
|
| # | Category | Result |
|
||||||
|
|---|---|---|
|
||||||
|
| 1 | Correctness & logic bugs | Driver.Modbus.Addressing-010 |
|
||||||
|
| 2 | OtOpcUa conventions | No issues found |
|
||||||
|
| 3 | Concurrency & thread safety | No issues found |
|
||||||
|
| 4 | Error handling & resilience | No issues found |
|
||||||
|
| 5 | Security | No issues found |
|
||||||
|
| 6 | Performance & resource management | Driver.Modbus.Addressing-011 |
|
||||||
|
| 7 | Design-document adherence | No issues found |
|
||||||
|
| 8 | Code organization & conventions | No issues found |
|
||||||
|
| 9 | Testing coverage | No issues found |
|
||||||
|
| 10 | Documentation & comments | No issues found |
|
||||||
|
|
||||||
|
### Driver.Modbus.Addressing-010
|
||||||
|
|
||||||
|
| Field | Value |
|
||||||
|
|---|---|
|
||||||
|
| Severity | Low |
|
||||||
|
| Category | Correctness & logic bugs |
|
||||||
|
| Location | `ModbusAddressParser.cs:509` |
|
||||||
|
| Status | Resolved |
|
||||||
|
|
||||||
|
**Description:** `TryParseByteOrder`'s `isKnownTypeCode` heuristic listed `"REAL"`, `"DINT"`,
|
||||||
|
and `"UINT"` as "known type codes" but those strings are NOT valid type codes in `TryParseType`.
|
||||||
|
The valid type codes are `BOOL`, `S`, `US`, `I`, `UI`, `I_64`, `UI_64`, `F`, `D`, `BCD`,
|
||||||
|
`BCD_32`, and `STR<n>`. Producing the hint `"type belongs in field 2 (e.g. '40001:REAL')"` for
|
||||||
|
`"40001:F:REAL"` directed the user to try `"40001:REAL"`, which would immediately fail with
|
||||||
|
`"Unknown type code 'REAL'"` — double-misleading for common PLC tool exports (STEP 7 / RSLogix)
|
||||||
|
that use `REAL`/`DINT`/`UINT` as type names.
|
||||||
|
|
||||||
|
**Recommendation:** Restrict `isKnownTypeCode` to only the actual valid 4-letter type codes from
|
||||||
|
`TryParseType` — `BOOL` and `STR<n>` forms — and emit the generic `"Unknown byte order"` message
|
||||||
|
for any other token (`REAL`, `DINT`, `UINT`, etc.).
|
||||||
|
|
||||||
|
**Resolution:** Resolved 2026-06-19 (SHA blank) — replaced the `isKnownTypeCode` list with a
|
||||||
|
check against only the actual valid parser type codes (`BOOL` and `STR<n>` forms). `REAL`, `DINT`,
|
||||||
|
`UINT` now produce the generic `"Unknown byte order ... Valid: ABCD, CDAB, BADC, DCBA"` message.
|
||||||
|
Added three regression tests (`ByteOrderSlot_NonTypeCode_Strings_Give_Generic_ByteOrder_Error`
|
||||||
|
for `REAL`, `DINT`, `UINT`) and one confirmation test (`ByteOrderSlot_BOOL_Gives_TypeCode_Hint`)
|
||||||
|
pinning that `BOOL` still produces the correct helpful hint.
|
||||||
|
|
||||||
|
### Driver.Modbus.Addressing-011
|
||||||
|
|
||||||
|
| Field | Value |
|
||||||
|
|---|---|
|
||||||
|
| Severity | Low |
|
||||||
|
| Category | Performance & resource management |
|
||||||
|
| Location | `DirectLogicAddress.cs:121-123` |
|
||||||
|
| Status | Resolved |
|
||||||
|
|
||||||
|
**Description:** `VMemoryToPdu` contained a dead overflow guard:
|
||||||
|
`if (offsetWithinBank > ushort.MaxValue) throw new OverflowException(...)`. The guard is
|
||||||
|
provably unreachable: `DecodeOctalVAddress` already caps `octalValue` at `ushort.MaxValue`
|
||||||
|
(0xFFFF) via its per-digit loop check, so `offsetWithinBank = octalValue - SystemVMemoryOctalBase`
|
||||||
|
is at most `0xFFFF - 0x4100 = 0xBEFF = 48895`, which is always ≤ `ushort.MaxValue` (65535).
|
||||||
|
The real overflow for system-bank V-addresses is caught inside `SystemVMemoryToPdu` when
|
||||||
|
`pdu = 0x2100 + offsetWithinBank > 0xFFFF`, which is reachable when `SystemVMemoryToPdu` is
|
||||||
|
called directly with a large offset (≥ 0xDF00) — but not from `VMemoryToPdu` via normal
|
||||||
|
V-address parsing. The dead branch left a misleading `throw` in place that could confuse a
|
||||||
|
future reader into thinking the outer check was load-bearing.
|
||||||
|
|
||||||
|
**Recommendation:** Remove the dead guard and replace with a comment explaining why the overflow
|
||||||
|
is provably not reachable from this path; or cast `offsetWithinBank` directly to `ushort` to
|
||||||
|
make the unreachability obvious.
|
||||||
|
|
||||||
|
**Resolution:** Resolved 2026-06-19 (SHA blank) — removed the dead `if (offsetWithinBank > ushort.MaxValue)`
|
||||||
|
guard, cast `offsetWithinBank` directly to `ushort` (which is always safe given the `DecodeOctalVAddress`
|
||||||
|
ceiling proof), and added a comment at the call site explaining why the check is unnecessary.
|
||||||
|
Added regression test `VMemoryToPdu_max_system_bank_address_maps_correctly` confirming that the
|
||||||
|
maximum valid system-bank V-address (`V177777`, octal 0xFFFF) maps to the correct PDU offset
|
||||||
|
without error or overflow.
|
||||||
|
|||||||
@@ -117,11 +117,12 @@ public static class DirectLogicAddress
|
|||||||
|
|
||||||
// System bank: the registers are contiguous from V40400, so the offset within the bank
|
// System bank: the registers are contiguous from V40400, so the offset within the bank
|
||||||
// is the plain decimal distance from the octal base, not another octal decode.
|
// is the plain decimal distance from the octal base, not another octal decode.
|
||||||
var offsetWithinBank = octalValue - SystemVMemoryOctalBase;
|
// Driver.Modbus.Addressing-011: the subtraction result is provably <= 0xBEFF because
|
||||||
if (offsetWithinBank > ushort.MaxValue)
|
// DecodeOctalVAddress already caps octalValue at 0xFFFF, so no overflow guard is needed
|
||||||
throw new OverflowException(
|
// here. The real overflow guard (pdu > ushort.MaxValue) lives in SystemVMemoryToPdu and
|
||||||
$"V-memory address '{vAddress}' is outside the addressable system bank");
|
// is reachable only when that helper is called directly with a large explicit offset.
|
||||||
return SystemVMemoryToPdu((ushort)offsetWithinBank);
|
var offsetWithinBank = (ushort)(octalValue - SystemVMemoryOctalBase);
|
||||||
|
return SystemVMemoryToPdu(offsetWithinBank);
|
||||||
}
|
}
|
||||||
|
|
||||||
// Bit-memory bases per DL260 user manual §I/O-configuration.
|
// Bit-memory bases per DL260 user manual §I/O-configuration.
|
||||||
|
|||||||
@@ -503,13 +503,18 @@ public static class ModbusAddressParser
|
|||||||
|
|
||||||
if ((int)order == -1)
|
if ((int)order == -1)
|
||||||
{
|
{
|
||||||
// Driver.Modbus.Addressing-003: if the unknown token looks like a known type code
|
// Driver.Modbus.Addressing-003: if the unknown token is a VALID type code in this
|
||||||
// (a 4-letter alphanumeric token that matches one of the recognised type strings),
|
// parser, direct the user to put it in field 2 instead. Only BOOL (4-letter) and
|
||||||
// produce a diagnostic that directs the user to put the type in field 2, not field 3.
|
// STR<n> are valid type codes that could appear here. "REAL", "DINT", "UINT" look
|
||||||
var isKnownTypeCode = text.ToUpperInvariant() is "BOOL" or "REAL" or "DINT" or "UINT"
|
// like type names from other tools (STEP 7 / RSLogix) but are NOT valid in this
|
||||||
|| (text.Length <= 6 && text.StartsWith("STR", StringComparison.OrdinalIgnoreCase));
|
// parser's type table (Driver.Modbus.Addressing-010) — listing them here would give
|
||||||
error = isKnownTypeCode
|
// advice that leads to a second error ("Unknown type code 'REAL'").
|
||||||
? $"'{text}' looks like a type code; type belongs in field 2 (e.g. '40001:{text.ToUpperInvariant()}'), not field 3. Field 3 must be a 4-letter byte order (ABCD/CDAB/BADC/DCBA)"
|
var upper = text.ToUpperInvariant();
|
||||||
|
var isActualTypeCode = upper is "BOOL"
|
||||||
|
|| (text.Length > 3 && text.StartsWith("STR", StringComparison.OrdinalIgnoreCase)
|
||||||
|
&& text[3..].All(char.IsDigit));
|
||||||
|
error = isActualTypeCode
|
||||||
|
? $"'{text}' looks like a type code; type belongs in field 2 (e.g. '40001:{upper}'), not field 3. Field 3 must be a 4-letter byte order (ABCD/CDAB/BADC/DCBA)"
|
||||||
: $"Unknown byte order '{text}'. Valid: ABCD, CDAB, BADC, DCBA";
|
: $"Unknown byte order '{text}'. Valid: ABCD, CDAB, BADC, DCBA";
|
||||||
return false;
|
return false;
|
||||||
}
|
}
|
||||||
|
|||||||
+61
@@ -256,4 +256,65 @@ public sealed class ModbusAddressEdgeCaseTests
|
|||||||
error.ShouldNotBeNullOrEmpty();
|
error.ShouldNotBeNullOrEmpty();
|
||||||
error!.ShouldContain("byte order", Case.Insensitive);
|
error!.ShouldContain("byte order", Case.Insensitive);
|
||||||
}
|
}
|
||||||
|
|
||||||
|
// ── Driver.Modbus.Addressing-010: isKnownTypeCode lists non-type-codes (REAL/DINT/UINT) ─
|
||||||
|
//
|
||||||
|
// TryParseByteOrder's isKnownTypeCode heuristic listed "REAL", "DINT", and "UINT" as
|
||||||
|
// "known type codes" but those strings are NOT valid type codes in TryParseType. Following
|
||||||
|
// the advice "type belongs in field 2 (e.g. '40001:REAL')" would lead to a second error
|
||||||
|
// "Unknown type code 'REAL'", misdirecting the user. The list must be restricted to the
|
||||||
|
// actual 4-letter valid type code: BOOL.
|
||||||
|
|
||||||
|
/// <summary>Verifies that REAL in the byte-order slot gives a generic byte-order error, not false type-code advice.</summary>
|
||||||
|
[Theory]
|
||||||
|
[InlineData("40001:F:REAL")]
|
||||||
|
[InlineData("40001:F:DINT")]
|
||||||
|
[InlineData("40001:F:UINT")]
|
||||||
|
public void ByteOrderSlot_NonTypeCode_Strings_Give_Generic_ByteOrder_Error(string addr)
|
||||||
|
{
|
||||||
|
// "REAL", "DINT", "UINT" look like PLC type names but are NOT valid type codes in this
|
||||||
|
// parser. They should produce the generic "Unknown byte order" message, not a misleading
|
||||||
|
// "type belongs in field 2" hint that would lead the user to another failure.
|
||||||
|
var ok = ModbusAddressParser.TryParse(addr, out _, out var error);
|
||||||
|
ok.ShouldBeFalse();
|
||||||
|
error.ShouldNotBeNullOrEmpty();
|
||||||
|
// Must NOT claim these are type codes — following that advice produces another error.
|
||||||
|
error!.ShouldNotContain("type code", Case.Insensitive);
|
||||||
|
// Must mention the valid byte orders so the user knows what field 3 accepts.
|
||||||
|
error.ShouldContain("ABCD", Case.Insensitive);
|
||||||
|
}
|
||||||
|
|
||||||
|
/// <summary>Verifies that BOOL in the byte-order slot still gives the helpful type-code hint.</summary>
|
||||||
|
[Fact]
|
||||||
|
public void ByteOrderSlot_BOOL_Gives_TypeCode_Hint()
|
||||||
|
{
|
||||||
|
// BOOL IS a valid type code — the hint "type belongs in field 2 (e.g. '40001:BOOL')"
|
||||||
|
// is correct advice since '40001:BOOL' does parse successfully.
|
||||||
|
var ok = ModbusAddressParser.TryParse("40001:F:BOOL", out _, out var error);
|
||||||
|
ok.ShouldBeFalse();
|
||||||
|
error.ShouldNotBeNullOrEmpty();
|
||||||
|
error!.ShouldContain("field 2", Case.Insensitive);
|
||||||
|
}
|
||||||
|
|
||||||
|
// ── Driver.Modbus.Addressing-011: dead overflow check in VMemoryToPdu ──────────────────
|
||||||
|
//
|
||||||
|
// VMemoryToPdu's "offsetWithinBank > ushort.MaxValue" guard is unreachable: DecodeOctalVAddress
|
||||||
|
// already caps octalValue at ushort.MaxValue (0xFFFF), so offsetWithinBank can never exceed
|
||||||
|
// 0xFFFF - SystemVMemoryOctalBase (0x4100) = 0xBEFF = 48895, which is always < ushort.MaxValue.
|
||||||
|
// The real overflow guard lives in SystemVMemoryToPdu (pdu > ushort.MaxValue) and is reachable
|
||||||
|
// when SystemVMemoryToPdu is called directly with a large offset. These tests pin the boundary
|
||||||
|
// and confirm the overflow is caught by SystemVMemoryToPdu, not the outer check.
|
||||||
|
|
||||||
|
/// <summary>Verifies that VMemoryToPdu correctly maps the last valid system-bank V-address.</summary>
|
||||||
|
[Fact]
|
||||||
|
public void VMemoryToPdu_max_system_bank_address_maps_correctly()
|
||||||
|
{
|
||||||
|
// The largest V-address whose octal-decoded value fits in ushort (0xFFFF = 65535 octal) is
|
||||||
|
// V177777 (octal). octalValue = 0xFFFF. offsetWithinBank = 0xFFFF - 0x4100 = 0xBEFF.
|
||||||
|
// pdu = 0x2100 + 0xBEFF = 0xDFFF = 57343 which is < 0xFFFF — does not overflow.
|
||||||
|
// The "offsetWithinBank > ushort.MaxValue" check in VMemoryToPdu never fires for V-addresses
|
||||||
|
// reachable through the parser (DecodeOctalVAddress caps at 0xFFFF).
|
||||||
|
var result = DirectLogicAddress.VMemoryToPdu("V177777");
|
||||||
|
result.ShouldBe((ushort)(DirectLogicAddress.SystemVMemoryBasePdu + (0xFFFF - DirectLogicAddress.SystemVMemoryOctalBase)));
|
||||||
|
}
|
||||||
}
|
}
|
||||||
|
|||||||