Auto: s7-d1 — TIA Portal CSV + STEP 7 Classic AWL symbol import
Closes #299
This commit is contained in:
@@ -940,6 +940,32 @@ project that rejects PG and accepts OP). That test is documented in
|
||||
`tests/ZB.MOM.WW.OtOpcUa.Driver.S7.IntegrationTests` but only runs against
|
||||
real firmware — the pymodbus-style "TSAP simulator" doesn't exist for S7.
|
||||
|
||||
## Symbol import
|
||||
|
||||
PR-S7-D1 / [#299](https://github.com/dohertj2/lmxopcua/issues/299) — bulk-import
|
||||
TIA Portal "Show all tags" CSV exports and STEP 7 Classic AWL declaration files
|
||||
into the S7 driver's tag list. Operators no longer hand-edit the
|
||||
`Drivers/<instance>/Config/Tags` JSON for hundred-tag projects.
|
||||
|
||||
Two formats supported v1:
|
||||
|
||||
- **TIA Portal CSV** — `Name,Path,Data type,Logical address,Comment,Hmi accessible,…`.
|
||||
en-US (`,`) and DE-locale (`;` separator + `,` decimal) auto-detected.
|
||||
HMI-hidden symbols filter out automatically; UDT-typed rows import as
|
||||
placeholders until PR-S7-D2 ships proper UDT layout.
|
||||
- **STEP 7 Classic AWL** — `VAR_GLOBAL` + `DATA_BLOCK` declarations parsed
|
||||
best-effort with position-based offset assignment.
|
||||
|
||||
Two surface options:
|
||||
|
||||
- **CLI**: `otopcua-s7-cli import-symbols --file foo.csv --format tia` emits
|
||||
an `appsettings.json` JSON fragment for hand-merge.
|
||||
- **API**: `S7DriverOptions.AddTiaCsvImport(path, out result)` /
|
||||
`AddAwlImport(path, out result)` for server-side bootstrap paths.
|
||||
|
||||
Full reference: [`docs/drivers/S7-TIA-Import.md`](../drivers/S7-TIA-Import.md).
|
||||
CLI flag table: [`docs/Driver.S7.Cli.md` "import-symbols"](../Driver.S7.Cli.md#import-symbols).
|
||||
|
||||
## References
|
||||
|
||||
1. Siemens Industry Online Support, *Modbus/TCP Communication between SIMATIC S7-1500 / S7-1200 and Modbus/TCP Controllers with Instructions `MB_CLIENT` and `MB_SERVER`*, Entry ID 102020340, V6 (Feb 2021). https://cache.industry.siemens.com/dl/files/340/102020340/att_118119/v6/net_modbus_tcp_s7-1500_s7-1200_en.pdf
|
||||
|
||||