chore: organize solution into module folders (Core/Server/Drivers/Client/Tooling)

Group all 69 projects into category subfolders under src/ and tests/ so the
Rider Solution Explorer mirrors the module structure. Folders: Core, Server,
Drivers (with a nested Driver CLIs subfolder), Client, Tooling.

- Move every project folder on disk with git mv (history preserved as renames).
- Recompute relative paths in 57 .csproj files: cross-category ProjectReferences,
  the lib/ HintPath+None refs in Driver.Historian.Wonderware, and the external
  mxaccessgw refs in Driver.Galaxy and its test project.
- Rebuild ZB.MOM.WW.OtOpcUa.slnx with nested solution folders.
- Re-prefix project paths in functional scripts (e2e, compliance, smoke SQL,
  integration, install).

Build green (0 errors); unit tests pass. Docs left for a separate pass.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
Joseph Doherty
2026-05-17 01:55:28 -04:00
parent 69f02fed7f
commit a25593a9c6
1044 changed files with 365 additions and 343 deletions
@@ -0,0 +1,79 @@
namespace ZB.MOM.WW.OtOpcUa.Driver.AbCip;
/// <summary>
/// Maps libplctag / CIP General Status codes to OPC UA StatusCodes. Mirrors the shape of
/// <c>ModbusDriver.MapModbusExceptionToStatus</c> so Admin UI status displays stay
/// uniform across drivers.
/// </summary>
/// <remarks>
/// <para>Coverage: the CIP general-status values an AB PLC actually returns during normal
/// driver operation. Full CIP Volume 1 Appendix B lists 50+ codes; the ones here are the
/// ones that move the driver's status needle:</para>
/// <list type="bullet">
/// <item>0x00 success — OPC UA <c>Good (0)</c>.</item>
/// <item>0x04 path segment error / 0x05 path destination unknown — <c>BadNodeIdUnknown</c>
/// (tag doesn't exist).</item>
/// <item>0x06 partial data transfer — <c>GoodMoreData</c> (fragmented read underway).</item>
/// <item>0x08 service not supported — <c>BadNotSupported</c> (e.g. write on a safety
/// partition tag from a non-safety task).</item>
/// <item>0x0A / 0x13 attribute-list error / insufficient data — <c>BadOutOfRange</c>
/// (type mismatch or truncated buffer).</item>
/// <item>0x0B already in requested mode — benign, treated as <c>Good</c>.</item>
/// <item>0x0E attribute not settable — <c>BadNotWritable</c>.</item>
/// <item>0x10 device state conflict — <c>BadDeviceFailure</c> (program-mode protected
/// writes during download / test-mode transitions).</item>
/// <item>0x16 object does not exist — <c>BadNodeIdUnknown</c>.</item>
/// <item>0x1E embedded service error — unwrap to the extended status when possible.</item>
/// <item>any libplctag <c>PLCTAG_STATUS_*</c> below zero — wrapped as
/// <c>BadCommunicationError</c> until fine-grained mapping lands (PR 3).</item>
/// </list>
/// </remarks>
public static class AbCipStatusMapper
{
public const uint Good = 0u;
public const uint GoodMoreData = 0x00A70000u;
public const uint BadInternalError = 0x80020000u;
public const uint BadNodeIdUnknown = 0x80340000u;
public const uint BadNotWritable = 0x803B0000u;
public const uint BadOutOfRange = 0x803C0000u;
public const uint BadNotSupported = 0x803D0000u;
public const uint BadDeviceFailure = 0x80550000u;
public const uint BadCommunicationError = 0x80050000u;
public const uint BadTimeout = 0x800A0000u;
public const uint BadTypeMismatch = 0x80730000u;
/// <summary>Map a CIP general-status byte to an OPC UA StatusCode.</summary>
public static uint MapCipGeneralStatus(byte status) => status switch
{
0x00 => Good,
0x04 or 0x05 => BadNodeIdUnknown,
0x06 => GoodMoreData,
0x08 => BadNotSupported,
0x0A or 0x13 => BadOutOfRange,
0x0B => Good,
0x0E => BadNotWritable,
0x10 => BadDeviceFailure,
0x16 => BadNodeIdUnknown,
_ => BadInternalError,
};
/// <summary>
/// Map a libplctag return/status code (<c>PLCTAG_STATUS_*</c>) to an OPC UA StatusCode.
/// libplctag uses <c>0 = PLCTAG_STATUS_OK</c>, positive values for pending, negative
/// values for errors.
/// </summary>
public static uint MapLibplctagStatus(int status)
{
if (status == 0) return Good;
if (status > 0) return GoodMoreData; // PLCTAG_STATUS_PENDING
return status switch
{
-5 => BadTimeout, // PLCTAG_ERR_TIMEOUT
-7 => BadCommunicationError, // PLCTAG_ERR_BAD_CONNECTION
-14 => BadNodeIdUnknown, // PLCTAG_ERR_NOT_FOUND
-16 => BadNotWritable, // PLCTAG_ERR_NOT_ALLOWED / read-only tag
-17 => BadOutOfRange, // PLCTAG_ERR_OUT_OF_BOUNDS
_ => BadCommunicationError,
};
}
}