fix(s7): a CPU refusal is per-tag Bad and counts as answered (R07:H4)
A deterministic PLC refusal (object does not exist, address out of range,
type inconsistent...) degraded driver health, and an all-refused driver (a
wrong DB number) sat Degraded with LastSuccessfulRead frozen, so the 90 s
comms-loss watchdog reconnected it forever against a reachable PLC.
- IsRefusal / IsAccessDenied classify over the whole exception chain. Live
probe on the snap7 fixture: S7.Net's READ paths raise the item error as a
BARE Exception ("Received error from PLC: ..."), its write paths as
PlcException(WriteData). The old PlcException-only match missed the read
shape entirely, so a real read access-denied was BadCommunicationError +
Degraded instead of the Faulted PUT/GET alert; the Test Connect probe had
the same blind spot.
- A refusal (read or write) is BadDeviceFailure with a once-per-tag Warning,
no health write and no reopen; it counts as answered, so it advances
LastSuccessfulRead and restores Healthy after a comms fault. An undecodable
buffer (S7ValueRangeException) also counts as answered.
- A write batch the CPU answered without a failure advances
LastSuccessfulRead and retires a Degraded the write side itself published.
- Tests that used ReadData as their generic "device fault" now use SendData
so their Degraded leg is still exercised.
Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
This commit is contained in:
@@ -208,6 +208,19 @@ public sealed class S7Driver
|
||||
/// Guarded by <see cref="_gate"/>.
|
||||
/// </summary>
|
||||
private (DriverState State, string Message)? _writeFault;
|
||||
|
||||
/// <summary>
|
||||
/// The message of the last Degraded the WRITE side published, or null. A clean write batch
|
||||
/// retires a Degraded carrying exactly this message (a good write proves the comms fault it
|
||||
/// reported is gone) and leaves any other Degraded to the read pass. Guarded by <see cref="_gate"/>.
|
||||
/// </summary>
|
||||
private string? _writeOwnedError;
|
||||
|
||||
/// <summary>
|
||||
/// Tags whose refusal has already been logged this generation — the once-per-tag Warning. Cleared
|
||||
/// by every initialize publish.
|
||||
/// </summary>
|
||||
private readonly ConcurrentDictionary<string, byte> _refusalWarned = new(StringComparer.Ordinal);
|
||||
private bool _disposed;
|
||||
|
||||
/// <inheritdoc />
|
||||
@@ -797,7 +810,7 @@ public sealed class S7Driver
|
||||
}
|
||||
catch (Exception ex)
|
||||
{
|
||||
results[i] = new DataValueSnapshot(null, RecordReadFailure(ex, outcome), null, now);
|
||||
results[i] = new DataValueSnapshot(null, RecordReadFailure(ex, outcome, [resolved[i]!.Name]), null, now);
|
||||
}
|
||||
}
|
||||
}
|
||||
@@ -903,6 +916,13 @@ public sealed class S7Driver
|
||||
/// <summary>Records that one tag read successfully.</summary>
|
||||
public void RecordSuccess() => AnySuccess = true;
|
||||
|
||||
/// <summary>
|
||||
/// Records that the CPU answered for one tag without serving it (a refusal, an undecodable
|
||||
/// buffer). Not a failure — it ranks nothing — but it IS proof of a live device, so it
|
||||
/// advances <c>LastSuccessfulRead</c> exactly like a success.
|
||||
/// </summary>
|
||||
public void RecordAnswered() => AnySuccess = true;
|
||||
|
||||
/// <summary>
|
||||
/// Records one failed tag, keeping the worst state and the message that explains it.
|
||||
/// </summary>
|
||||
@@ -1098,7 +1118,7 @@ public sealed class S7Driver
|
||||
{
|
||||
// Decoding is pure and synchronous — no cancellation can surface here, so there
|
||||
// is deliberately no OperationCanceledException arm to shadow the request one.
|
||||
results[index] = new DataValueSnapshot(null, RecordReadFailure(ex, outcome), null, now);
|
||||
results[index] = new DataValueSnapshot(null, RecordReadFailure(ex, outcome, [tag.Name]), null, now);
|
||||
}
|
||||
}
|
||||
}
|
||||
@@ -1195,7 +1215,7 @@ public sealed class S7Driver
|
||||
}
|
||||
catch (Exception ex)
|
||||
{
|
||||
var status = RecordReadFailure(ex, outcome);
|
||||
var status = RecordReadFailure(ex, outcome, span.Members.Select(m => m.Tag.Name));
|
||||
foreach (var member in span.Members)
|
||||
results[member.OriginalIndex] = new DataValueSnapshot(null, status, null, now);
|
||||
return;
|
||||
@@ -1214,7 +1234,7 @@ public sealed class S7Driver
|
||||
// Decoding is pure and synchronous — no cancellation can surface here, so there is
|
||||
// deliberately no OperationCanceledException arm to shadow the block-read one above.
|
||||
results[member.OriginalIndex] =
|
||||
new DataValueSnapshot(null, RecordReadFailure(ex, outcome), null, now);
|
||||
new DataValueSnapshot(null, RecordReadFailure(ex, outcome, [member.Tag.Name]), null, now);
|
||||
}
|
||||
}
|
||||
}
|
||||
@@ -1289,8 +1309,10 @@ public sealed class S7Driver
|
||||
/// </remarks>
|
||||
/// <param name="ex">The exception observed on a read.</param>
|
||||
/// <param name="outcome">The pass's outcome accumulator this failure is recorded into.</param>
|
||||
/// <param name="tagNames">The tags the failure belongs to (every member of a failed span), for the
|
||||
/// once-per-tag refusal Warning.</param>
|
||||
/// <returns>The OPC UA status code every affected tag must be stamped with.</returns>
|
||||
private uint RecordReadFailure(Exception ex, ReadPassOutcome outcome)
|
||||
private uint RecordReadFailure(Exception ex, ReadPassOutcome outcome, IEnumerable<string> tagNames)
|
||||
{
|
||||
switch (ex)
|
||||
{
|
||||
@@ -1299,19 +1321,33 @@ public sealed class S7Driver
|
||||
|
||||
case S7ValueRangeException:
|
||||
// A PLC buffer the type codec refuses (uninitialised DTL, non-BCD S5TIME…) is a data
|
||||
// problem, not a transport fault — no health change, no connection teardown.
|
||||
// problem, not a transport fault — no health change, no connection teardown. The
|
||||
// bytes came off the wire, so the CPU answered.
|
||||
outcome.RecordAnswered();
|
||||
return StatusBadOutOfRange;
|
||||
|
||||
case PlcException pex when IsAccessDenied(pex):
|
||||
case var _ when IsAccessDenied(ex):
|
||||
// PUT/GET-disabled (S7-1200/1500) / access-protection — a permanent configuration
|
||||
// fault, NOT a transient one. Blind retry is wasted effort, so map it to
|
||||
// BadNotSupported and flag the driver as a config alert (Faulted) rather than
|
||||
// Degraded — per driver-specs.md §5.
|
||||
// Degraded — per driver-specs.md §5. Matched over the whole chain: S7.Net's READ
|
||||
// paths raise the CPU's item error as a bare Exception, not a PlcException.
|
||||
outcome.RecordFailure(DriverState.Faulted,
|
||||
"S7 access denied — enable PUT/GET communication in TIA Portal " +
|
||||
$"(Protection & Security) for this CPU. PLC reported: {pex.Message}");
|
||||
$"(Protection & Security) for this CPU. PLC reported: {ex.Message}");
|
||||
return StatusBadNotSupported;
|
||||
|
||||
case var _ when IsRefusal(ex):
|
||||
// The CPU answered and refused the item (object does not exist, address out of
|
||||
// range, type inconsistent...) — deterministic, so a retry, a reopen or a Degraded
|
||||
// would all be wrong: per-tag Bad, a once-per-tag Warning, no health write, and it
|
||||
// counts as answered so LastSuccessfulRead advances (R07:H4). An all-refused driver
|
||||
// (wrong DB number) used to sit Degraded with a frozen timestamp and trip the
|
||||
// comms-loss watchdog every 90 s against a reachable PLC.
|
||||
outcome.RecordAnswered();
|
||||
foreach (var name in tagNames) WarnRefusalOnce(name, "read", ex);
|
||||
return StatusBadDeviceFailure;
|
||||
|
||||
case PlcException pex:
|
||||
// A genuine device-layer fault (CPU error, hardware fault) — transient enough to
|
||||
// keep retrying; report BadDeviceFailure and degrade health. A connection-fatal
|
||||
@@ -1969,7 +2005,7 @@ public sealed class S7Driver
|
||||
// Client-supplied value of the wrong shape — not a device or comms fault.
|
||||
results[i] = new WriteResult(StatusBadTypeMismatch);
|
||||
}
|
||||
catch (PlcException pex) when (IsAccessDenied(pex))
|
||||
catch (Exception ex) when (IsAccessDenied(ex))
|
||||
{
|
||||
// PUT/GET-disabled / access-protection on write — same permanent
|
||||
// configuration fault as on read. BadNotSupported +
|
||||
@@ -1977,7 +2013,15 @@ public sealed class S7Driver
|
||||
results[i] = new WriteResult(StatusBadNotSupported);
|
||||
outcome.RecordFailure(DriverState.Faulted,
|
||||
"S7 access denied — enable PUT/GET communication in TIA Portal " +
|
||||
$"(Protection & Security) for this CPU. PLC reported: {pex.Message}");
|
||||
$"(Protection & Security) for this CPU. PLC reported: {ex.Message}");
|
||||
}
|
||||
catch (Exception ex) when (IsRefusal(ex))
|
||||
{
|
||||
// The CPU answered and refused the item — per-tag Bad, once-per-tag Warning, no
|
||||
// Degraded, and it counts as answered (R07:H4).
|
||||
results[i] = new WriteResult(StatusBadDeviceFailure);
|
||||
outcome.RecordAnswered();
|
||||
WarnRefusalOnce(tag.Name, "write", ex);
|
||||
}
|
||||
catch (PlcException pex)
|
||||
{
|
||||
@@ -2029,16 +2073,24 @@ public sealed class S7Driver
|
||||
else if (outcome.AnySuccess)
|
||||
_writeFault = null; // a write got through — the protection fault is gone
|
||||
|
||||
var answeredAt = outcome.AnyAnswered ? DateTime.UtcNow : (DateTime?)null;
|
||||
if (worst == DriverState.Healthy)
|
||||
{
|
||||
// Success-only batch: no health write, except to retire a Faulted that WE (the write
|
||||
// side) were holding — a clean write is the only evidence the alert has cleared.
|
||||
// Only a Faulted the write side owns: a read-side Faulted (e.g. access denied on another DB) is the
|
||||
// read pass's to clear, and Health still carries the write fault's own message iff it is ours.
|
||||
if (outcome.AnySuccess && _writeFault is null && priorWriteFault is { } owned)
|
||||
TryUpdateHealth(gen, h => h.State == DriverState.Faulted && h.LastError == owned.Message
|
||||
? new DriverHealth(DriverState.Healthy, h.LastSuccessfulRead, null)
|
||||
: null);
|
||||
// Clean batch (successes and/or refusals): the CPU answered, so LastSuccessfulRead
|
||||
// advances, and a non-Healthy state the WRITE side owns is retired — a Faulted only by a
|
||||
// real success (a refusal does not prove PUT/GET is enabled), a write-side comms Degraded
|
||||
// by any answer. A state the read side owns (its own message) is the read pass's to clear.
|
||||
var ownedFault = outcome.AnySuccess && _writeFault is null ? priorWriteFault?.Message : null;
|
||||
var ownedDegraded = _writeOwnedError;
|
||||
_writeOwnedError = null;
|
||||
TryUpdateHealth(gen, h =>
|
||||
{
|
||||
var lsr = answeredAt ?? h.LastSuccessfulRead;
|
||||
if ((h.State == DriverState.Faulted && ownedFault is not null && h.LastError == ownedFault)
|
||||
|| (h.State == DriverState.Degraded && ownedDegraded is not null && h.LastError == ownedDegraded))
|
||||
return new DriverHealth(DriverState.Healthy, lsr, null);
|
||||
return lsr == h.LastSuccessfulRead ? null : h with { LastSuccessfulRead = lsr };
|
||||
});
|
||||
return;
|
||||
}
|
||||
|
||||
@@ -2050,7 +2102,8 @@ public sealed class S7Driver
|
||||
state = wf.State;
|
||||
error = wf.Message;
|
||||
}
|
||||
TryUpdateHealth(gen, h => new DriverHealth(state, h.LastSuccessfulRead, error));
|
||||
if (state == DriverState.Degraded) _writeOwnedError = error;
|
||||
TryUpdateHealth(gen, h => new DriverHealth(state, answeredAt ?? h.LastSuccessfulRead, error));
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
@@ -2068,10 +2121,18 @@ public sealed class S7Driver
|
||||
public DriverState WorstFailure => _inner.WorstFailure;
|
||||
/// <summary>The message explaining <see cref="WorstFailure"/>.</summary>
|
||||
public string? WorstError => _inner.WorstError;
|
||||
/// <summary>True once the batch observed a success or a failure.</summary>
|
||||
public bool HasObservations => _inner.HasObservations;
|
||||
/// <summary>True once the batch observed a success, a refusal or a failure.</summary>
|
||||
public bool HasObservations => _inner.HasObservations || AnyAnswered;
|
||||
/// <summary>True once the CPU answered any item (a success or a refusal) — proof of a live device.</summary>
|
||||
public bool AnyAnswered { get; private set; }
|
||||
/// <summary>Records one successful write.</summary>
|
||||
public void RecordSuccess() => _inner.RecordSuccess();
|
||||
public void RecordSuccess()
|
||||
{
|
||||
_inner.RecordSuccess();
|
||||
AnyAnswered = true;
|
||||
}
|
||||
/// <summary>Records a write the CPU answered by refusing it: not a success, not a failure.</summary>
|
||||
public void RecordAnswered() => AnyAnswered = true;
|
||||
/// <summary>Records one failed write.</summary>
|
||||
/// <param name="state">The state the failure would have stamped alone.</param>
|
||||
/// <param name="message">The operator-facing message.</param>
|
||||
@@ -2407,19 +2468,82 @@ public sealed class S7Driver
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Detects an S7 PUT/GET-disabled / access-protection fault inside an S7.Net
|
||||
/// <see cref="PlcException"/>. S7.Net's read/write paths wrap every PLC-side error in a
|
||||
/// <c>PlcException</c> with <see cref="ErrorCode.ReadData"/> / <see cref="ErrorCode.WriteData"/>;
|
||||
/// the response-code validator throws a plain <see cref="Exception"/> for the S7
|
||||
/// <c>AccessingObjectNotAllowed</c> status, which lands as the inner exception. There is
|
||||
/// no typed error code for it, so the inner message is the only discriminator
|
||||
/// S7.Net exposes.
|
||||
/// True when <paramref name="ex"/> is a deterministic PLC REFUSAL of the item: the CPU answered
|
||||
/// with an S7 item error (object does not exist, address out of range, data type inconsistent /
|
||||
/// not supported, hardware fault, or an unknown status), or S7.Net raised a
|
||||
/// <see cref="ErrorCode.ReadData"/> / <see cref="ErrorCode.WriteData"/> over a response it could
|
||||
/// not use. Excludes the access-denied refusal (its own sticky Faulted config alert) and
|
||||
/// anything carrying a socket / timeout / framing / cancellation fault in its chain — those
|
||||
/// wrap a transport failure, not an answer.
|
||||
/// </summary>
|
||||
/// <param name="pex">The exception raised by S7.Net.</param>
|
||||
/// <returns><see langword="true"/> when the PLC refused access to the object.</returns>
|
||||
internal static bool IsAccessDenied(PlcException pex)
|
||||
/// <remarks>
|
||||
/// Live-probed against the snap7 fixture (2026-10-22): S7.Net's READ paths
|
||||
/// (<c>ReadAsync(string)</c>, <c>ReadBytesAsync</c>) raise the item error as a BARE
|
||||
/// <see cref="Exception"/> — "Received error from PLC: Object does not exist." — not wrapped in
|
||||
/// a <see cref="PlcException"/>; its write paths wrap whatever they hit in a
|
||||
/// <c>PlcException(WriteData)</c>. Both shapes are matched.
|
||||
/// </remarks>
|
||||
/// <param name="ex">The exception raised by S7.Net.</param>
|
||||
/// <returns><see langword="true"/> when the CPU answered and refused.</returns>
|
||||
internal static bool IsRefusal(Exception ex)
|
||||
{
|
||||
for (Exception? e = pex; e is not null; e = e.InnerException)
|
||||
if (IsAccessDenied(ex) || IsS7ConnectionFatal(ex) || HasCancellationInChain(ex)) return false;
|
||||
if (ex is PlcException { ErrorCode: ErrorCode.ReadData or ErrorCode.WriteData }) return true;
|
||||
for (Exception? e = ex; e is not null; e = e.InnerException)
|
||||
if (IsS7ItemError(e)) return true;
|
||||
return false;
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// True for the bare <see cref="Exception"/> S7.Net's response-code validator raises for an S7
|
||||
/// item error ("Received error from PLC: …" / "Invalid response from PLC: statusCode=…").
|
||||
/// Exact type only: a derived exception carrying similar words is not S7.Net's validator.
|
||||
/// </summary>
|
||||
/// <param name="e">One exception of a chain.</param>
|
||||
/// <returns><see langword="true"/> for the validator's item-error shape.</returns>
|
||||
private static bool IsS7ItemError(Exception e)
|
||||
=> e.GetType() == typeof(Exception)
|
||||
&& (e.Message.StartsWith("Received error from PLC", StringComparison.Ordinal)
|
||||
|| e.Message.StartsWith("Invalid response from PLC", StringComparison.Ordinal));
|
||||
|
||||
/// <summary>True when a cancellation is buried in the exception chain (a half-read PDU, not a refusal).</summary>
|
||||
/// <param name="ex">The exception to inspect.</param>
|
||||
/// <returns><see langword="true"/> when any inner exception is an <see cref="OperationCanceledException"/>.</returns>
|
||||
private static bool HasCancellationInChain(Exception ex)
|
||||
{
|
||||
for (var e = ex.InnerException; e is not null; e = e.InnerException)
|
||||
if (e is OperationCanceledException) return true;
|
||||
return false;
|
||||
}
|
||||
|
||||
/// <summary>Logs a refusal once per tag per generation.</summary>
|
||||
/// <param name="tagName">The refused tag.</param>
|
||||
/// <param name="operation">"read" or "write".</param>
|
||||
/// <param name="ex">The refusal.</param>
|
||||
private void WarnRefusalOnce(string tagName, string operation, Exception ex)
|
||||
{
|
||||
if (!_refusalWarned.TryAdd(tagName, 0)) return;
|
||||
_logger.LogWarning(
|
||||
"S7 CPU refused the {Operation} of tag {Tag} ({Reason}); it reads Bad until the tag or the PLC program is fixed. " +
|
||||
"Driver health is unaffected. Further refusals of this tag are not logged. Driver={DriverInstanceId}",
|
||||
operation, tagName, ex.InnerException?.Message ?? ex.Message, _driverInstanceId);
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Detects an S7 PUT/GET-disabled / access-protection fault. S7.Net's response-code validator
|
||||
/// throws a plain <see cref="Exception"/> for the S7 <c>AccessingObjectNotAllowed</c> status —
|
||||
/// bare on the read paths, wrapped in a <see cref="PlcException"/> (<see cref="ErrorCode.WriteData"/>)
|
||||
/// on the write paths. There is no typed error code for it, so the message is the only
|
||||
/// discriminator S7.Net exposes. The top-level exception must be S7.Net-shaped (a
|
||||
/// <see cref="PlcException"/> or the validator's bare item error), so an unrelated exception that
|
||||
/// happens to say "not allowed" is not mistaken for it.
|
||||
/// </summary>
|
||||
/// <param name="ex">The exception raised by S7.Net.</param>
|
||||
/// <returns><see langword="true"/> when the PLC refused access to the object.</returns>
|
||||
internal static bool IsAccessDenied(Exception ex)
|
||||
{
|
||||
if (ex is not PlcException && !IsS7ItemError(ex)) return false;
|
||||
for (Exception? e = ex; e is not null; e = e.InnerException)
|
||||
{
|
||||
if (e.Message.Contains("Accessing object not allowed", StringComparison.OrdinalIgnoreCase)
|
||||
|| e.Message.Contains("not allowed", StringComparison.OrdinalIgnoreCase))
|
||||
|
||||
@@ -128,15 +128,17 @@ public sealed class S7DriverProbe : IDriverProbe
|
||||
return null;
|
||||
}
|
||||
catch (OperationCanceledException) { throw; }
|
||||
catch (PlcException pex) when (S7Driver.IsAccessDenied(pex))
|
||||
// S7.Net's read paths raise the CPU's item error as a BARE Exception ("Received error from
|
||||
// PLC: …"), not a PlcException, so both classifiers walk the whole chain (the driver's own).
|
||||
catch (Exception ex) when (S7Driver.IsAccessDenied(ex))
|
||||
{
|
||||
return new(false,
|
||||
"S7 connected but data access is denied — enable PUT/GET communication in TIA Portal " +
|
||||
$"(Protection & Security) for this CPU. PLC reported: {pex.Message}", null);
|
||||
$"(Protection & Security) for this CPU. PLC reported: {ex.Message}", null);
|
||||
}
|
||||
catch (PlcException pex) when (pex.ErrorCode == ErrorCode.ReadData)
|
||||
catch (Exception ex) when (S7Driver.IsRefusal(ex))
|
||||
{
|
||||
return null; // address not available on this CPU — not a connection problem
|
||||
return null; // address not available on this CPU — the CPU answered; not a connection problem
|
||||
}
|
||||