fix(s7): a CPU refusal is per-tag Bad and counts as answered (R07:H4)
A deterministic PLC refusal (object does not exist, address out of range,
type inconsistent...) degraded driver health, and an all-refused driver (a
wrong DB number) sat Degraded with LastSuccessfulRead frozen, so the 90 s
comms-loss watchdog reconnected it forever against a reachable PLC.
- IsRefusal / IsAccessDenied classify over the whole exception chain. Live
probe on the snap7 fixture: S7.Net's READ paths raise the item error as a
BARE Exception ("Received error from PLC: ..."), its write paths as
PlcException(WriteData). The old PlcException-only match missed the read
shape entirely, so a real read access-denied was BadCommunicationError +
Degraded instead of the Faulted PUT/GET alert; the Test Connect probe had
the same blind spot.
- A refusal (read or write) is BadDeviceFailure with a once-per-tag Warning,
no health write and no reopen; it counts as answered, so it advances
LastSuccessfulRead and restores Healthy after a comms fault. An undecodable
buffer (S7ValueRangeException) also counts as answered.
- A write batch the CPU answered without a failure advances
LastSuccessfulRead and retires a Degraded the write side itself published.
- Tests that used ReadData as their generic "device fault" now use SendData
so their Degraded leg is still exercised.
Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
This commit is contained in:
+13
-2
@@ -312,7 +312,8 @@ Portal under *Protection & Security* for the CPU.
|
||||
| Read-only tag written | `BadNotWritable` | unchanged |
|
||||
| Unimplemented data type | `BadNotSupported` | unchanged |
|
||||
| PUT/GET denied | `BadNotSupported` | `Faulted` (config alert) |
|
||||
| CPU / hardware fault | `BadDeviceFailure` | `Degraded` |
|
||||
| CPU refusal of the item (object does not exist, address out of range, type inconsistent, hardware fault) | `BadDeviceFailure` | unchanged — counts as *answered*, advances `LastSuccessfulRead`; one Warning per tag |
|
||||
| Other device-layer fault (`PlcException` that is neither a refusal nor connection-fatal) | `BadDeviceFailure` | `Degraded` |
|
||||
| Socket / timeout | `BadCommunicationError` | `Degraded` |
|
||||
| Reconnect suppressed (backoff window) | `BadCommunicationError` | `Degraded` |
|
||||
| Array write of the wrong shape / length / element type | `BadTypeMismatch` | unchanged |
|
||||
@@ -323,7 +324,17 @@ accumulate their outcomes and write health once (`Healthy < Degraded < Faulted`)
|
||||
`Faulted` item is not erased by a later `Degraded` or successful sibling. The write-side `Faulted` is
|
||||
**sticky against reads**: a clean read pass (reads often work against a write-protected CPU) leaves
|
||||
`Faulted` in place and only advances `LastSuccessfulRead`; the next write that succeeds clears it. A
|
||||
transient `Degraded` write failure is still cleared by a clean read, as before.
|
||||
transient `Degraded` write failure is cleared by a clean read, or by the next write batch the CPU
|
||||
answers without a failure.
|
||||
|
||||
**A refusal is an answer (R07:H4).** S7.Net's read paths raise the CPU's item error as a bare
|
||||
`Exception` ("Received error from PLC: Object does not exist." — live-probed on the snap7 fixture), its
|
||||
write paths as a `PlcException(WriteData)`; both are classified over the whole exception chain, and the
|
||||
access-denied text inside either is the `Faulted` alert. A refusal is deterministic, so it neither
|
||||
degrades health nor reopens the connection, and because it proves the CPU is reachable it advances
|
||||
`LastSuccessfulRead` and restores `Healthy` after an earlier comms fault. Before this, a driver whose
|
||||
every tag was refused (a wrong DB number) sat `Degraded` with a frozen timestamp and the comms-loss
|
||||
watchdog reconnected it every 90 s against a perfectly reachable PLC.
|
||||
|
||||
**Connect backoff.** A dead PLC costs one connect attempt per backoff window (1 s doubling to a 30 s
|
||||
cap), not one per read / poll tick / probe tick: inside the window `EnsureConnectedAsync` fails fast
|
||||
|
||||