Phase 3 PR 51 -- DL260 X-input FC02 discrete-input mapping end-to-end test. Integration test DL205XInputTests reads FC02 at the DirectLogicAddress.XInputToDiscrete-resolved address and asserts two behaviors against the dl205.json pymodbus profile: (1) X20 octal (=decimal 16 = Modbus DI 16) reads ON, proving the helper correctly octal-parses the trailing number and adds it to the 0 base; (2) X21 octal reads OFF (not exception) -- per docs/v2/dl205.md §I/O-mapping, 'reading a non-populated X input returns zero, not an exception' on DL260, because the CPU sizes the discrete-input table to the configured I/O not the installed hardware. Pymodbus models this by returning the default 0 value for any DI bit in the configured 'di size' range that wasn't explicitly seeded, matching real DL260 behaviour. Test uses X20 rather than X0 to sidestep a shared-blocks conflict: pymodbus places FC01/FC02 bit-address 0..15 into cell 0, but cell 0 is already uint16-typed (V0 marker = 0xCAFE) per the register-zero quirk test, and shared-blocks semantics allow only one type per cell. X20 octal = DI 16 lands in cell 1 which is free, so both the V0 quirk AND the X-input quirk can coexist in one profile. dl205.json: bits cell 1 seeded value=9 (bits 0 and 3 set -> X20, X23 octal = ON), write-range extended to include cell 1 (though X-inputs are read-only; the write-range entry is required by pymodbus for ANY cell referenced in a bits section even if only reads are expected -- pymodbus validates write-access uniformly). 10/10 DL205 integration tests pass with MODBUS_SIM_PROFILE=dl205. No driver code changes -- the XInputToDiscrete helper + FC02 read path already landed in PRs 50 and 21 respectively. This PR closes the integration-test gap that docs/v2/dl205.md called out under test name DL205_Xinput_unpopulated_reads_as_zero.
This commit is contained in:
@@ -0,0 +1,71 @@
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.DL205;
|
||||
|
||||
/// <summary>
|
||||
/// Verifies the DL260 X-input discrete-input mapping against the <c>dl205.json</c>
|
||||
/// pymodbus profile. X-inputs are FC02 discrete-input-only (Modbus doesn't allow writes
|
||||
/// to discrete inputs), and the DirectLOGIC convention is X0 → DI 0 with octal offsets
|
||||
/// for subsequent addresses. The sim seeds X20 octal (= DI 16) = ON so the test can
|
||||
/// prove the helper routes through to the right cell.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// X0 / X1 / …X17 octal all share cell 0 (DI 0-15 → cell 0 bits 0-15) which conflicts
|
||||
/// with the V0 uint16 marker; we can't seed both types at cell 0 under shared-blocks
|
||||
/// semantics. So the test uses X20 octal (first address beyond the cell-0 boundary) which
|
||||
/// lands cleanly at cell 1 bit 0 and leaves the V0 register-zero quirk intact.
|
||||
/// </remarks>
|
||||
[Collection(ModbusSimulatorCollection.Name)]
|
||||
[Trait("Category", "Integration")]
|
||||
[Trait("Device", "DL205")]
|
||||
public sealed class DL205XInputTests(ModbusSimulatorFixture sim)
|
||||
{
|
||||
[Fact]
|
||||
public async Task DL260_X20_octal_maps_to_DiscreteInput_16_and_reads_ON()
|
||||
{
|
||||
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
||||
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "dl205",
|
||||
StringComparison.OrdinalIgnoreCase))
|
||||
{
|
||||
Assert.Skip("MODBUS_SIM_PROFILE != dl205 — skipping.");
|
||||
}
|
||||
|
||||
// X20 octal = decimal 16 = DI 16 per the DL260 convention (X-inputs start at DI 0).
|
||||
var di = DirectLogicAddress.XInputToDiscrete("X20");
|
||||
di.ShouldBe((ushort)16);
|
||||
|
||||
var options = BuildOptions(sim, [
|
||||
new ModbusTagDefinition("DL260_X20",
|
||||
ModbusRegion.DiscreteInputs, Address: di,
|
||||
DataType: ModbusDataType.Bool, Writable: false),
|
||||
// Unpopulated-X control: pymodbus returns 0 (not exception) for any bit in the
|
||||
// configured DI range that wasn't explicitly seeded — per docs/v2/dl205.md
|
||||
// "Reading a non-populated X input ... returns zero, not an exception".
|
||||
new ModbusTagDefinition("DL260_X21_off",
|
||||
ModbusRegion.DiscreteInputs, Address: DirectLogicAddress.XInputToDiscrete("X21"),
|
||||
DataType: ModbusDataType.Bool, Writable: false),
|
||||
]);
|
||||
await using var driver = new ModbusDriver(options, driverInstanceId: "dl205-xinput");
|
||||
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
|
||||
var results = await driver.ReadAsync(["DL260_X20", "DL260_X21_off"], TestContext.Current.CancellationToken);
|
||||
|
||||
results[0].StatusCode.ShouldBe(0u);
|
||||
results[0].Value.ShouldBe(true, "dl205.json seeds cell 1 bit 0 (X20 octal = DI 16) = ON");
|
||||
|
||||
results[1].StatusCode.ShouldBe(0u, "unpopulated X inputs must read cleanly — DL260 does NOT raise an exception");
|
||||
results[1].Value.ShouldBe(false);
|
||||
}
|
||||
|
||||
private static ModbusDriverOptions BuildOptions(ModbusSimulatorFixture sim, IReadOnlyList<ModbusTagDefinition> tags)
|
||||
=> new()
|
||||
{
|
||||
Host = sim.Host,
|
||||
Port = sim.Port,
|
||||
UnitId = 1,
|
||||
Timeout = TimeSpan.FromSeconds(2),
|
||||
Tags = tags,
|
||||
Probe = new ModbusProbeOptions { Enabled = false },
|
||||
};
|
||||
}
|
||||
Reference in New Issue