fix(opcua): credential lockout review fixes (#833)
- Reserve an in-flight slot per client before authenticating (TryBegin / Complete / Abandon under one lock); refuse once recorded failures + in-flight attempts reach MaxFailedAttempts, so a parallel burst cannot pass the check before its first failure is recorded. - An expired lockout resets the count (LockoutSeconds < FailureWindowSeconds relocked on every single failure after the first lockout). - Validate OpcUa:CredentialLockout at host start: disabled, or both durations > 0. - Log the first refusal of a lockout episode at Information, the rest at Debug. - Document that on None endpoints the key is effectively IP-only (NAT neighbours share a UserName count) and a null peer shares one key.
This commit is contained in:
+9
@@ -29,5 +29,14 @@ public sealed class OpcUaApplicationHostOptionsValidator : OptionsValidatorBase<
|
||||
// IReadOnlyCollection<T>, so it can't bind to MinCount's IReadOnlyCollection<T> parameter
|
||||
// directly. ToList() bridges to the shared primitive while preserving the count (and message).
|
||||
builder.MinCount(o.EnabledSecurityProfiles?.ToList(), 1, "OpcUa:EnabledSecurityProfiles");
|
||||
|
||||
// #833 review: an enabled credential lockout needs positive durations — a zero LockoutSeconds would lock
|
||||
// nothing, a zero FailureWindowSeconds would never accumulate. MaxFailedAttempts <= 0 disables it.
|
||||
var lockout = o.CredentialLockout;
|
||||
builder.RequireThat(lockout is null || lockout.MaxFailedAttempts <= 0
|
||||
|| (lockout.LockoutSeconds > 0 && lockout.FailureWindowSeconds > 0),
|
||||
"OpcUa:CredentialLockout:LockoutSeconds and OpcUa:CredentialLockout:FailureWindowSeconds must both be "
|
||||
+ "greater than 0 while OpcUa:CredentialLockout:MaxFailedAttempts is greater than 0 (set "
|
||||
+ "MaxFailedAttempts to 0 to disable the lockout)");
|
||||
}
|
||||
}
|
||||
|
||||
Reference in New Issue