Task #222 partial — unblock AB Legacy PCCC via cip-path workaround (5/5 stages)

Replaced the "ab_server PCCC upstream-broken" skip gate with the actual
root cause: libplctag's ab_server rejects empty CIP routing paths at the
unconnected-send layer before the PCCC dispatcher runs. Real SLC/
MicroLogix/PLC-5 hardware accepts empty paths (no backplane); ab_server
does not. With `/1,0` in place, N (Int16), F (Float32), and L (Int32)
file reads + writes round-trip cleanly across all three compose profiles.

## Fixture changes

- `AbLegacyServerFixture.cs`:
  - Drop `AB_LEGACY_TRUST_WIRE` env var + the reachable-but-untrusted
    skip branch. Fixture now only skips on TCP unreachability.
  - Add `AB_LEGACY_CIP_PATH` env var (default `1,0`) + expose `CipPath`
    property. Set `AB_LEGACY_CIP_PATH=` (empty) against real hardware.
  - Shorter skip messages on the `[AbLegacyFact]` / `[AbLegacyTheory]`
    attributes — one reason: endpoint not reachable.

- `AbLegacyReadSmokeTests.cs`:
  - Device URI built from `sim.CipPath` instead of hardcoded empty path.
  - New `AB_LEGACY_COMPOSE_PROFILE` env var filters the parametric
    theory to the running container's family. Only one container binds
    `:44818` at a time, so cross-family params would otherwise fail.
  - `Slc500_write_then_read_round_trip` skips cleanly when the running
    profile isn't `slc500`.

## E2E + seed + docs

- `scripts/e2e/test-ablegacy.ps1` — drop the `AB_LEGACY_TRUST_WIRE`
  skip gate; synopsis calls out the `/1,0` vs empty cip-path split
  between the Docker fixture and real hardware.
- `scripts/e2e/e2e-config.sample.json` — sample gateway flipped from
  the hardware placeholder (`192.168.1.10`) to the Docker fixture
  (`127.0.0.1/1,0`); comment rewritten.
- `scripts/e2e/README.md` — AB Legacy expected-matrix row goes from
  SKIP to PASS.
- `scripts/smoke/seed-ablegacy-smoke.sql` — default HostAddress points
  at the Docker fixture + header / footer text reflect the new state.
- `tests/.../Docker/README.md` — "Known limitations" section rewritten
  to describe the cip-path gate (not a dispatcher gap); env-var table
  picks up `AB_LEGACY_CIP_PATH` + `AB_LEGACY_COMPOSE_PROFILE`.
- `docs/drivers/AbLegacy-Test-Fixture.md` + `docs/drivers/README.md`
  + `docs/DriverClis.md` — flip status from blocked to functional;
  residual bit-file-write gap (B3:0/5 → 0x803D0000) documented.

## Residual gap

Bit-file writes (`B3:0/5` style) surface `0x803D0000` against
`ab_server --plc=SLC500`; bit reads work. Non-blocking for smoke
coverage — N/F/L round-trip is enough. Real hardware / RSEmulate 500
for bit-write fidelity. Documented in `Docker/README.md` §"Known
limitations" + the `AbLegacy-Test-Fixture.md` follow-ups list.

## Verified

- Full-solution build: 0 errors, 334 pre-existing warnings.
- Integration suite passes per-profile with
  `AB_LEGACY_COMPOSE_PROFILE=<slc500|micrologix|plc5>` + matching
  compose container up.
- All four non-hardware e2e scripts (Modbus / AB CIP / AB Legacy / S7)
  now 5/5 against the respective docker-compose fixtures.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
Joseph Doherty
2026-04-21 12:38:43 -04:00
parent e1f172c053
commit 95c7e0b490
10 changed files with 151 additions and 126 deletions

View File

@@ -20,6 +20,12 @@ namespace ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.IntegrationTests;
/// <item><c>AB_LEGACY_ENDPOINT</c> — <c>host:port</c> of the PCCC-mode simulator.
/// Defaults to <c>localhost:44818</c> (EtherNet/IP port; ab_server's PCCC
/// emulation exposes PCCC-over-CIP on the same port as CIP itself).</item>
/// <item><c>AB_LEGACY_CIP_PATH</c> — routing path appended to the <c>ab://host:port/</c>
/// URI. Defaults to <c>1,0</c> (port-1/slot-0 backplane), required by ab_server
/// which rejects unconnected Send_RR_Data with an empty path at the CIP layer
/// before the PCCC dispatcher runs. Real SLC 5/05 / MicroLogix / PLC-5 hardware
/// use an empty path — set <c>AB_LEGACY_CIP_PATH=</c> (empty) when pointing at
/// real hardware.</item>
/// </list>
/// Distinct from <c>AB_SERVER_ENDPOINT</c> used by the AB CIP fixture so both
/// can point at different containers simultaneously during a combined test run.
@@ -27,24 +33,30 @@ namespace ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.IntegrationTests;
public sealed class AbLegacyServerFixture : IAsyncLifetime
{
private const string EndpointEnvVar = "AB_LEGACY_ENDPOINT";
/// <summary>
/// Opt-in flag that promises the endpoint can actually round-trip PCCC reads/writes
/// (real SLC 5/05 / MicroLogix 1100/1400 / PLC-5 hardware, or a RSEmulate 500
/// golden-box per <c>docs/v2/lmx-followups.md</c>). Without this, the fixture assumes
/// the endpoint is libplctag's <c>ab_server --plc=SLC500</c> Docker container — whose
/// PCCC dispatcher is a known upstream gap — and skips cleanly rather than failing
/// every test with <c>BadCommunicationError</c>.
/// </summary>
private const string TrustWireEnvVar = "AB_LEGACY_TRUST_WIRE";
private const string CipPathEnvVar = "AB_LEGACY_CIP_PATH";
/// <summary>Standard EtherNet/IP port. PCCC-over-CIP rides on the same port as
/// native CIP; the differentiator is the <c>--plc</c> flag ab_server was started
/// with, not a different TCP listener.</summary>
public const int DefaultPort = 44818;
/// <summary>
/// ab_server rejects unconnected Send_RR_Data with an empty CIP routing path
/// at the CIP layer — the PCCC dispatcher never runs. <c>1,0</c> is the generic
/// port-1/slot-0 backplane path; any well-formed path passes the gate. Real
/// hardware (SLC 5/05 / MicroLogix / PLC-5) uses an empty path because there's
/// no backplane to cross, so point <c>AB_LEGACY_CIP_PATH=</c> (empty) at real
/// hardware to exercise the authentic wire semantics.
/// </summary>
public const string DefaultCipPath = "1,0";
public string Host { get; } = "127.0.0.1";
public int Port { get; } = DefaultPort;
/// <summary>CIP routing path portion of the device URI (after the <c>/</c> separator).
/// May be empty when targeting real hardware; non-empty against ab_server.</summary>
public string CipPath { get; } = DefaultCipPath;
public string? SkipReason { get; }
public AbLegacyServerFixture()
@@ -56,6 +68,11 @@ public sealed class AbLegacyServerFixture : IAsyncLifetime
if (parts.Length == 2 && int.TryParse(parts[1], out var p)) Port = p;
}
// Empty override is intentional (real hardware); treat `null` as "not set, use
// default" but preserve an explicit empty-string override.
var cipOverride = Environment.GetEnvironmentVariable(CipPathEnvVar);
if (cipOverride is not null) CipPath = cipOverride;
SkipReason = ResolveSkipReason(Host, Port);
}
@@ -82,22 +99,6 @@ public sealed class AbLegacyServerFixture : IAsyncLifetime
$"Start the Docker container (docker compose -f Docker/docker-compose.yml " +
$"--profile slc500 up -d), attach real hardware, or override {EndpointEnvVar}.";
}
// TCP reaches — but is the peer a real PLC (wire-trustworthy) or ab_server's PCCC
// mode (dispatcher is upstream-broken, every read surfaces BadCommunicationError)?
// We can't detect it at the wire without issuing a full libplctag session, so we
// require an explicit opt-in for wire-level runs. See
// `tests/.../Docker/README.md` §"Known limitations" for the upstream-tracking pointer.
if (Environment.GetEnvironmentVariable(TrustWireEnvVar) is not { Length: > 0 } trust
|| !(trust == "1" || string.Equals(trust, "true", StringComparison.OrdinalIgnoreCase)))
{
return $"AB Legacy endpoint at {host}:{port} is reachable but {TrustWireEnvVar} is not set. " +
"ab_server's PCCC dispatcher is a known upstream gap (libplctag/libplctag), so by " +
"default the integration suite assumes the simulator is in play and skips. Set " +
$"{TrustWireEnvVar}=1 when pointing at real SLC 5/05 / MicroLogix 1100/1400 / PLC-5 " +
"hardware or a RSEmulate 500 golden-box.";
}
return null;
}
@@ -166,7 +167,7 @@ public sealed class AbLegacyServerCollection : Xunit.ICollectionFixture<AbLegacy
}
/// <summary>
/// <c>[Fact]</c>-equivalent that skips when the PCCC endpoint isn't wire-trustworthy.
/// <c>[Fact]</c>-equivalent that skips when the PCCC endpoint isn't reachable.
/// See <see cref="AbLegacyServerFixture"/> for the exact skip semantics.
/// </summary>
public sealed class AbLegacyFactAttribute : FactAttribute
@@ -174,11 +175,9 @@ public sealed class AbLegacyFactAttribute : FactAttribute
public AbLegacyFactAttribute()
{
if (!AbLegacyServerFixture.IsServerAvailable())
Skip = "AB Legacy PCCC endpoint not wire-trustworthy. Either no simulator is " +
"running, or the Docker ab_server is up but AB_LEGACY_TRUST_WIRE is not " +
"set (ab_server's PCCC dispatcher is a known upstream gap). Set " +
"AB_LEGACY_TRUST_WIRE=1 when pointing AB_LEGACY_ENDPOINT at real hardware " +
"or a RSEmulate 500 golden-box.";
Skip = "AB Legacy PCCC endpoint not reachable. Start the Docker fixture " +
"(docker compose -f Docker/docker-compose.yml --profile slc500 up -d) " +
"or point AB_LEGACY_ENDPOINT at real hardware.";
}
}
@@ -190,10 +189,8 @@ public sealed class AbLegacyTheoryAttribute : TheoryAttribute
public AbLegacyTheoryAttribute()
{
if (!AbLegacyServerFixture.IsServerAvailable())
Skip = "AB Legacy PCCC endpoint not wire-trustworthy. Either no simulator is " +
"running, or the Docker ab_server is up but AB_LEGACY_TRUST_WIRE is not " +
"set (ab_server's PCCC dispatcher is a known upstream gap). Set " +
"AB_LEGACY_TRUST_WIRE=1 when pointing AB_LEGACY_ENDPOINT at real hardware " +
"or a RSEmulate 500 golden-box.";
Skip = "AB Legacy PCCC endpoint not reachable. Start the Docker fixture " +
"(docker compose -f Docker/docker-compose.yml --profile slc500 up -d) " +
"or point AB_LEGACY_ENDPOINT at real hardware.";
}
}