Task #222 partial — unblock AB Legacy PCCC via cip-path workaround (5/5 stages)
Replaced the "ab_server PCCC upstream-broken" skip gate with the actual
root cause: libplctag's ab_server rejects empty CIP routing paths at the
unconnected-send layer before the PCCC dispatcher runs. Real SLC/
MicroLogix/PLC-5 hardware accepts empty paths (no backplane); ab_server
does not. With `/1,0` in place, N (Int16), F (Float32), and L (Int32)
file reads + writes round-trip cleanly across all three compose profiles.
## Fixture changes
- `AbLegacyServerFixture.cs`:
- Drop `AB_LEGACY_TRUST_WIRE` env var + the reachable-but-untrusted
skip branch. Fixture now only skips on TCP unreachability.
- Add `AB_LEGACY_CIP_PATH` env var (default `1,0`) + expose `CipPath`
property. Set `AB_LEGACY_CIP_PATH=` (empty) against real hardware.
- Shorter skip messages on the `[AbLegacyFact]` / `[AbLegacyTheory]`
attributes — one reason: endpoint not reachable.
- `AbLegacyReadSmokeTests.cs`:
- Device URI built from `sim.CipPath` instead of hardcoded empty path.
- New `AB_LEGACY_COMPOSE_PROFILE` env var filters the parametric
theory to the running container's family. Only one container binds
`:44818` at a time, so cross-family params would otherwise fail.
- `Slc500_write_then_read_round_trip` skips cleanly when the running
profile isn't `slc500`.
## E2E + seed + docs
- `scripts/e2e/test-ablegacy.ps1` — drop the `AB_LEGACY_TRUST_WIRE`
skip gate; synopsis calls out the `/1,0` vs empty cip-path split
between the Docker fixture and real hardware.
- `scripts/e2e/e2e-config.sample.json` — sample gateway flipped from
the hardware placeholder (`192.168.1.10`) to the Docker fixture
(`127.0.0.1/1,0`); comment rewritten.
- `scripts/e2e/README.md` — AB Legacy expected-matrix row goes from
SKIP to PASS.
- `scripts/smoke/seed-ablegacy-smoke.sql` — default HostAddress points
at the Docker fixture + header / footer text reflect the new state.
- `tests/.../Docker/README.md` — "Known limitations" section rewritten
to describe the cip-path gate (not a dispatcher gap); env-var table
picks up `AB_LEGACY_CIP_PATH` + `AB_LEGACY_COMPOSE_PROFILE`.
- `docs/drivers/AbLegacy-Test-Fixture.md` + `docs/drivers/README.md`
+ `docs/DriverClis.md` — flip status from blocked to functional;
residual bit-file-write gap (B3:0/5 → 0x803D0000) documented.
## Residual gap
Bit-file writes (`B3:0/5` style) surface `0x803D0000` against
`ab_server --plc=SLC500`; bit reads work. Non-blocking for smoke
coverage — N/F/L round-trip is enough. Real hardware / RSEmulate 500
for bit-write fidelity. Documented in `Docker/README.md` §"Known
limitations" + the `AbLegacy-Test-Fixture.md` follow-ups list.
## Verified
- Full-solution build: 0 errors, 334 pre-existing warnings.
- Integration suite passes per-profile with
`AB_LEGACY_COMPOSE_PROFILE=<slc500|micrologix|plc5>` + matching
compose container up.
- All four non-hardware e2e scripts (Modbus / AB CIP / AB Legacy / S7)
now 5/5 against the respective docker-compose fixtures.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -1,15 +1,17 @@
|
||||
-- AB Legacy e2e smoke seed — closes #213 (umbrella #209).
|
||||
--
|
||||
-- Hardware-gated. The ab_server PCCC dispatcher is upstream-broken (task #222
|
||||
-- tracks the lab rig + alternative fixtures), so verifying this seed end-to-end
|
||||
-- requires real SLC 500 / MicroLogix / PLC-5 hardware or an RSEmulate 500
|
||||
-- golden-box. The factory + seed ship here so the wiring is in place the
|
||||
-- moment real hardware becomes available — no server code changes needed.
|
||||
-- Works against the ab_server PCCC Docker fixture (one of the slc500 /
|
||||
-- micrologix / plc5 compose profiles) or real SLC 500 / MicroLogix / PLC-5
|
||||
-- hardware. Default HostAddress below points at the Docker fixture with a
|
||||
-- `/1,0` cip-path; libplctag's ab_server rejects empty paths before routing
|
||||
-- to the PCCC dispatcher. Real hardware uses an empty path — change the
|
||||
-- HostAddress to `ab://<plc-ip>:44818/` (note the trailing slash with nothing
|
||||
-- after) before running the seed for that setup.
|
||||
--
|
||||
-- Usage (once hardware is reachable):
|
||||
-- Usage:
|
||||
-- docker compose -f tests/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.IntegrationTests/Docker/docker-compose.yml --profile slc500 up -d
|
||||
-- sqlcmd -S "localhost,14330" -d OtOpcUaConfig -U sa -P "OtOpcUaDev_2026!" \
|
||||
-- -i scripts/smoke/seed-ablegacy-smoke.sql
|
||||
-- (Update the `HostAddress` below to point at the real gateway first.)
|
||||
|
||||
SET NOCOUNT ON;
|
||||
SET XACT_ABORT ON;
|
||||
@@ -83,7 +85,7 @@ VALUES (@Gen, @DrvId, @ClusterId, @NsId, 'ablegacy-smoke', 'AbLegacy', N'{
|
||||
"TimeoutMs": 2000,
|
||||
"Devices": [
|
||||
{
|
||||
"HostAddress": "ab://192.168.1.10/1,0",
|
||||
"HostAddress": "ab://127.0.0.1:44818/1,0",
|
||||
"PlcFamily": "Slc500",
|
||||
"DeviceName": "slc-500"
|
||||
}
|
||||
@@ -92,7 +94,7 @@ VALUES (@Gen, @DrvId, @ClusterId, @NsId, 'ablegacy-smoke', 'AbLegacy', N'{
|
||||
"Tags": [
|
||||
{
|
||||
"Name": "N7_5",
|
||||
"DeviceHostAddress": "ab://192.168.1.10/1,0",
|
||||
"DeviceHostAddress": "ab://127.0.0.1:44818/1,0",
|
||||
"Address": "N7:5",
|
||||
"DataType": "Int",
|
||||
"Writable": true,
|
||||
@@ -117,6 +119,7 @@ PRINT ' Cluster: ' + @ClusterId;
|
||||
PRINT ' Node: ' + @NodeId;
|
||||
PRINT ' Generation: ' + CONVERT(nvarchar(20), @Gen);
|
||||
PRINT '';
|
||||
PRINT 'NOTE: hardware-gated. ab_server PCCC is upstream-broken (#222). Point the';
|
||||
PRINT ' DriverConfig HostAddress at real SLC / MicroLogix / PLC-5 / RSEmulate';
|
||||
PRINT ' and run the e2e script with AB_LEGACY_TRUST_WIRE=1.';
|
||||
PRINT 'NOTE: default points at the ab_server slc500 Docker fixture with a /1,0';
|
||||
PRINT ' cip-path (required by ab_server). For real SLC/MicroLogix/PLC-5';
|
||||
PRINT ' hardware, edit the DriverConfig HostAddress to end with /<empty>';
|
||||
PRINT ' e.g. "ab://<plc-ip>:44818/" and re-run this seed.';
|
||||
|
||||