docs(r2-01): mark EnsureConnectedAsync as the R2-09 connect-throttle seam (STAB-8 note, task 10)
This commit is contained in:
@@ -1211,6 +1211,15 @@ public sealed class S7Driver
|
||||
/// MUST be called while holding <see cref="_gate"/> — it mutates <see cref="Plc"/> /
|
||||
/// <see cref="_plcDead"/> and reuses the single-connection-per-PLC invariant the gate
|
||||
/// enforces. The read / write / probe paths all take the gate before calling it.
|
||||
/// <para>
|
||||
/// While the PLC is down every data call and probe tick pays a full connect attempt
|
||||
/// bounded only by <c>_options.Timeout</c> (STAB-8). This method is the single
|
||||
/// choke-point all S7 reconnects flow through (already gate-serialized), so the
|
||||
/// fleet-wide connect-attempt throttle planned in R2-09 plugs in here: a
|
||||
/// last-failed-attempt timestamp checked at the top of the slow path. Deliberately NOT
|
||||
/// implemented driver-locally — see
|
||||
/// <c>archreview/plans/R2-01-s7-fault-hardening-plan.md</c> Finding 3.
|
||||
/// </para>
|
||||
/// </remarks>
|
||||
/// <param name="ct">Cancellation token for the (re)connect attempt.</param>
|
||||
/// <returns>A live <see cref="IS7Plc"/>.</returns>
|
||||
|
||||
Reference in New Issue