feat(v3-batch4-wp4): multi-notifier native alarms (single ReportEvent → raw + equipment notifiers) + teardown symmetry

Materialize each native alarm ONCE at the raw tag (ConditionId = RawPath, Raw
realm); wire the single condition as an SDK event notifier of each referencing
equipment's UNS folder so one ReportEvent fans to every root without
re-reporting per root (which would break Server-object dedup + Part 9 ack
correlation).

- New sink method WireAlarmNotifiers(alarmNodeId, alarmRealm,
  notifierFolderNodeIds, notifierFolderRealm) on IOpcUaAddressSpaceSink,
  forwarded through DeferredAddressSpaceSink + SdkAddressSpaceSink +
  NullOpcUaAddressSpaceSink (the forwarding-trap guard); auto-covered by the
  DeferredSinkForwardingReflectionTests realm + forwarding guards + a
  hand-written forward test.
- OtOpcUaNodeManager: the normative AddNotifier(isInverse) pair + idempotent
  EnsureFolderIsEventNotifier per equipment folder; tracked per condition in
  _alarmNotifierWiring. Teardown symmetry: RemoveNotifier(bidirectional:true) on
  RebuildAddressSpace, RemoveAlarmConditionNode, and RemoveEquipmentSubtree so no
  inverse-notifier entry leaks across redeploys.
- AddressSpaceApplier.MaterialiseRawSubtree wires notifiers for each native alarm
  tag, resolving its ReferencingEquipmentPaths (Area/Line/Equipment) to the
  EquipmentId folder NodeIds via BuildEquipmentIdByFolderPath.
- AlarmTransitionEvent gains ReferencingEquipmentPaths (empty default); /alerts
  renders the referencing-equipment list as display metadata.
- Un-skipped + rewrote the native-alarm dark tests
  (DriverHostActorNativeAlarmTests x6, DriverHostActorNativeAlarmAckRoutingTests
  x1) for the v3 raw-condition model; new NodeManagerMultiNotifierAlarmTests
  proves multi-notifier wiring + teardown symmetry (no leaked duplicates after a
  re-trip) + applier wiring test.

Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
This commit is contained in:
Joseph Doherty
2026-07-16 12:07:11 -04:00
parent 9d09523675
commit 8ebc712eff
21 changed files with 744 additions and 182 deletions
@@ -17,6 +17,7 @@ namespace ZB.MOM.WW.OtOpcUa.Commons.Messages.Alerts;
/// <param name="AlarmTypeName">OPC UA Part 9 condition subtype name — one of <c>LimitAlarm</c> / <c>DiscreteAlarm</c> / <c>OffNormalAlarm</c> / <c>AlarmCondition</c> (the base type, used as the default). The historian feed maps this onto the durable alarm-type column.</param>
/// <param name="Comment">Operator-supplied comment on ack / confirm / comment transitions; <c>null</c> for engine-driven transitions (Activated / Cleared / Shelved / …) that carry no comment.</param>
/// <param name="HistorizeToAveva">When <c>false</c>, the durable historian sink suppresses this transition (the live <c>alerts</c> fan-out is unaffected); <c>null</c> or <c>true</c> historize. <c>null</c> is the cross-version/rolling-restart case: an old-format message missing the field deserializes to <c>null</c> (CLR default for <c>bool?</c>) and is historized (safe default-on), matching the <c>AlarmTypeName</c> null-coalesce in <c>HistorianAdapterActor.Translate</c>. The producer (<c>ScriptedAlarmHostActor</c>) always sets a concrete <c>true</c>/<c>false</c>.</param>
/// <param name="ReferencingEquipmentPaths">v3 Batch 4 (multi-notifier native alarms) — the (possibly empty) list of UNS equipment-folder paths (<c>Area/Line/Equipment</c>) that reference the alarm's backing raw tag. A native alarm is a SINGLE Part 9 condition materialised once at the raw tag (its <see cref="AlarmId"/> is the RawPath); the same condition fans events to every referencing equipment's UNS folder via SDK notifiers, and this list is carried so <c>/alerts</c> shows the one condition row with all its referencing equipment as display metadata. Empty for scripted alarms (they are per-equipment) and for a native alarm whose raw tag no equipment references. Defaults empty so every existing producer + rolling-restart deserialization keeps compiling / working.</param>
public sealed record AlarmTransitionEvent(
string AlarmId,
string EquipmentPath,
@@ -28,4 +29,5 @@ public sealed record AlarmTransitionEvent(
DateTime TimestampUtc,
string AlarmTypeName = "AlarmCondition",
string? Comment = null,
bool? HistorizeToAveva = null);
bool? HistorizeToAveva = null,
IReadOnlyList<string>? ReferencingEquipmentPaths = null);