feat(alarms): carry AlarmTypeName + operator Comment on AlarmTransitionEvent (historian feed prep)

This commit is contained in:
Joseph Doherty
2026-06-11 11:03:00 -04:00
parent cd72f79ef4
commit 8ac3ac5be9
5 changed files with 61 additions and 4 deletions
@@ -14,6 +14,8 @@ namespace ZB.MOM.WW.OtOpcUa.Commons.Messages.Alerts;
/// <param name="Message">Fully-rendered message text — template tokens already resolved.</param>
/// <param name="User">Operator who triggered the transition. "system" for engine-driven events.</param>
/// <param name="TimestampUtc">When the transition occurred.</param>
/// <param name="AlarmTypeName">OPC UA Part 9 condition subtype name — one of <c>LimitAlarm</c> / <c>DiscreteAlarm</c> / <c>OffNormalAlarm</c> / <c>AlarmCondition</c> (the base type, used as the default). The historian feed maps this onto the durable alarm-type column.</param>
/// <param name="Comment">Operator-supplied comment on ack / confirm / comment transitions; <c>null</c> for engine-driven transitions (Activated / Cleared / Shelved / …) that carry no comment.</param>
public sealed record AlarmTransitionEvent(
string AlarmId,
string EquipmentPath,
@@ -22,4 +24,6 @@ public sealed record AlarmTransitionEvent(
int Severity,
string Message,
string User,
DateTime TimestampUtc);
DateTime TimestampUtc,
string AlarmTypeName = "AlarmCondition",
string? Comment = null);