fix(s7): refuse unservable tag shapes per tag at every gate (R07:H3, R07:U4)

The init-time tag guards THREW: one mis-authored tag (DB1.DBZ0, DB1.DBW0 typed
Float64, T5 typed Int32, a writable Bool array) faulted the whole driver and the
actor retried the same init every 10 s forever, darkening every tag on the PLC.
Neither the editor nor the deploy gate checked any of it.

- S7AddressParser moves to S7.Contracts (same namespace) and a new
  S7TagShapeRules there is the single authority on servable shapes.
- S7TagDefinitionFactory.FromTagConfig applies it, so the AdminUI editor, the
  deploy gate (Inspect, with the specific reason) and the driver init refuse
  the same tags. Init now skips a refused tag (ISkippedTagReporter) instead of
  throwing; the throwing RejectUnsupportedTagConfigs is gone.
- New rules on top of the old guards: a narrow type at the wrong access width
  (every read failed) and a Bool array not starting at bit 0 (U4: DB1.DBX0.3
  silently read bit 0 of bytes 0..n).
- AdminUI test fixtures that used addresses the driver could never serve
  (DB1.DBS0, a browse "SomeAddress", Int32/Float32 on DBW) now use real ones.

Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
This commit is contained in:
Joseph Doherty
2026-10-22 15:04:19 -04:00
parent 7bcb6331ed
commit 87a7414df7
19 changed files with 598 additions and 368 deletions
@@ -0,0 +1,222 @@
namespace ZB.MOM.WW.OtOpcUa.Driver.S7;
/// <summary>
/// Siemens S7 memory area. The driver's tag-address parser maps every S7 tag string into
/// exactly one of these + an offset. Values match the on-wire S7 area codes only
/// incidentally — S7.Net uses its own <c>DataType</c> enum (<c>DataBlock</c>, <c>Memory</c>,
/// <c>Input</c>, <c>Output</c>, <c>Timer</c>, <c>Counter</c>) so the adapter layer translates.
/// </summary>
public enum S7Area
{
DataBlock,
Memory, // M (Merker / marker byte)
Input, // I (process-image input)
Output, // Q (process-image output)
Timer,
Counter,
}
/// <summary>
/// Access width for a DB / M / I / Q address. Timers and counters are always 16-bit
/// opaque (not user-addressable via size suffixes).
/// </summary>
public enum S7Size
{
Bit, // X
Byte, // B
Word, // W — 16-bit
DWord, // D — 32-bit
}
/// <summary>
/// Parsed form of an S7 tag-address string. Produced by <see cref="S7AddressParser.Parse"/>.
/// </summary>
/// <param name="Area">Memory area (DB, M, I, Q, T, C).</param>
/// <param name="DbNumber">Data block number; only meaningful when <paramref name="Area"/> is <see cref="S7Area.DataBlock"/>.</param>
/// <param name="Size">Access width. Always <see cref="S7Size.Word"/> for Timer and Counter.</param>
/// <param name="ByteOffset">Byte offset into the area (for DB/M/I/Q) or the timer/counter number.</param>
/// <param name="BitOffset">Bit position 0-7 when <paramref name="Size"/> is <see cref="S7Size.Bit"/>; 0 otherwise.</param>
public readonly record struct S7ParsedAddress(
S7Area Area,
int DbNumber,
S7Size Size,
int ByteOffset,
int BitOffset);
/// <summary>
/// Parses Siemens S7 address strings into <see cref="S7ParsedAddress"/>. Accepts the
/// Siemens TIA-Portal / STEP 7 Classic syntax documented in <c>docs/v2/driver-specs.md</c> §5:
/// <list type="bullet">
/// <item><c>DB{n}.DB{X|B|W|D}{offset}[.bit]</c> — e.g. <c>DB1.DBX0.0</c>, <c>DB1.DBW0</c>, <c>DB1.DBD4</c></item>
/// <item><c>M{B|W|D}{offset}</c> or <c>M{offset}.{bit}</c> — e.g. <c>MB0</c>, <c>MW0</c>, <c>MD4</c>, <c>M0.0</c></item>
/// <item><c>I{B|W|D}{offset}</c> or <c>I{offset}.{bit}</c> — e.g. <c>IB0</c>, <c>IW0</c>, <c>ID0</c>, <c>I0.0</c></item>
/// <item><c>Q{B|W|D}{offset}</c> or <c>Q{offset}.{bit}</c> — e.g. <c>QB0</c>, <c>QW0</c>, <c>QD0</c>, <c>Q0.0</c></item>
/// <item><c>T{n}</c> — e.g. <c>T0</c>, <c>T15</c></item>
/// <item><c>C{n}</c> — e.g. <c>C0</c>, <c>C10</c></item>
/// </list>
/// Grammar is case-insensitive. Leading/trailing whitespace tolerated. Bit specifiers
/// must be 0-7; byte offsets must be non-negative; DB numbers must be &gt;= 1.
/// </summary>
/// <remarks>
/// Parse is deliberately strict — the parser rejects syntactic garbage up-front so a bad
/// tag config fails at driver init time instead of surfacing as a misleading
/// <c>BadInternalError</c> on every Read against that tag.
/// </remarks>
public static class S7AddressParser
{
/// <summary>
/// Parse an S7 address. Throws <see cref="FormatException"/> on any syntax error with
/// the offending input echoed in the message so operators can correlate to the tag
/// config that produced the fault.
/// </summary>
/// <param name="address">The S7 address string to parse.</param>
/// <returns>The parsed address structure.</returns>
/// <exception cref="FormatException">Thrown if the address syntax is invalid.</exception>
public static S7ParsedAddress Parse(string address)
{
if (string.IsNullOrWhiteSpace(address))
throw new FormatException("S7 address must not be empty");
var s = address.Trim().ToUpperInvariant();
// --- DB{n}.DB{X|B|W|D}{offset}[.bit] ---
if (s.StartsWith("DB") && TryParseDataBlock(s, out var dbResult))
return dbResult;
if (s.Length < 2)
throw new FormatException($"S7 address '{address}' is too short to parse");
var areaChar = s[0];
var rest = s.Substring(1);
switch (areaChar)
{
case 'M': return ParseMIQ(S7Area.Memory, rest, address);
case 'I': return ParseMIQ(S7Area.Input, rest, address);
case 'Q': return ParseMIQ(S7Area.Output, rest, address);
case 'T': return ParseTimerOrCounter(S7Area.Timer, rest, address);
case 'C': return ParseTimerOrCounter(S7Area.Counter, rest, address);
default:
throw new FormatException($"S7 address '{address}' starts with unknown area '{areaChar}' (expected DB/M/I/Q/T/C)");
}
}
/// <summary>
/// Try-parse variant for callers that can't afford an exception on bad input (e.g.
/// config validation pages in the Admin UI). Returns <c>false</c> for any input that
/// would throw from <see cref="Parse"/>.
/// </summary>
/// <param name="address">The S7 address string to parse.</param>
/// <param name="result">The parsed address structure (valid only if method returns true).</param>
/// <returns>True if parsing succeeded; false otherwise.</returns>
public static bool TryParse(string address, out S7ParsedAddress result)
{
try
{
result = Parse(address);
return true;
}
catch (FormatException)
{
result = default;
return false;
}
}
private static bool TryParseDataBlock(string s, out S7ParsedAddress result)
{
result = default;
// Split on first '.': left side must be DB{n}, right side DB{X|B|W|D}{offset}[.bit]
var dot = s.IndexOf('.');
if (dot < 0) return false;
var head = s.Substring(0, dot); // DB{n}
var tail = s.Substring(dot + 1); // DB{X|B|W|D}{offset}[.bit]
if (head.Length < 3) return false;
if (!int.TryParse(head.AsSpan(2), out var dbNumber) || dbNumber < 1)
throw new FormatException($"S7 DB number in '{s}' must be a positive integer");
if (!tail.StartsWith("DB") || tail.Length < 4)
throw new FormatException($"S7 DB address tail '{tail}' must start with DB{{X|B|W|D}}");
var sizeChar = tail[2];
var offsetStart = 3;
var size = sizeChar switch
{
'X' => S7Size.Bit,
'B' => S7Size.Byte,
'W' => S7Size.Word,
'D' => S7Size.DWord,
_ => throw new FormatException($"S7 DB size '{sizeChar}' in '{s}' must be X/B/W/D"),
};
var (byteOffset, bitOffset) = ParseOffsetAndOptionalBit(tail, offsetStart, size, s);
result = new S7ParsedAddress(S7Area.DataBlock, dbNumber, size, byteOffset, bitOffset);
return true;
}
private static S7ParsedAddress ParseMIQ(S7Area area, string rest, string original)
{
if (rest.Length == 0)
throw new FormatException($"S7 address '{original}' has no offset");
var first = rest[0];
S7Size size;
int offsetStart;
switch (first)
{
case 'B': size = S7Size.Byte; offsetStart = 1; break;
case 'W': size = S7Size.Word; offsetStart = 1; break;
case 'D': size = S7Size.DWord; offsetStart = 1; break;
default:
// No size prefix => bit-level address requires explicit .bit. Size stays Bit;
// ParseOffsetAndOptionalBit will demand the dot.
size = S7Size.Bit;
offsetStart = 0;
break;
}
var (byteOffset, bitOffset) = ParseOffsetAndOptionalBit(rest, offsetStart, size, original);
return new S7ParsedAddress(area, DbNumber: 0, size, byteOffset, bitOffset);
}
private static S7ParsedAddress ParseTimerOrCounter(S7Area area, string rest, string original)
{
if (rest.Length == 0)
throw new FormatException($"S7 address '{original}' has no {area} number");
if (!int.TryParse(rest, out var number) || number < 0)
throw new FormatException($"S7 {area} number in '{original}' must be a non-negative integer");
return new S7ParsedAddress(area, DbNumber: 0, S7Size.Word, number, BitOffset: 0);
}
private static (int byteOffset, int bitOffset) ParseOffsetAndOptionalBit(
string s, int start, S7Size size, string original)
{
var offsetEnd = start;
while (offsetEnd < s.Length && s[offsetEnd] >= '0' && s[offsetEnd] <= '9')
offsetEnd++;
if (offsetEnd == start)
throw new FormatException($"S7 address '{original}' has no byte-offset digits");
if (!int.TryParse(s.AsSpan(start, offsetEnd - start), out var byteOffset) || byteOffset < 0)
throw new FormatException($"S7 byte offset in '{original}' must be non-negative");
// No bit-suffix: done unless size is Bit with no prefix, which requires one.
if (offsetEnd == s.Length)
{
if (size == S7Size.Bit)
throw new FormatException($"S7 address '{original}' needs a .{{bit}} suffix for bit access");
return (byteOffset, 0);
}
if (s[offsetEnd] != '.')
throw new FormatException($"S7 address '{original}' has unexpected character after offset");
if (size != S7Size.Bit)
throw new FormatException($"S7 address '{original}' has a bit suffix but the size is {size} — bit access needs X (DB) or no size prefix (M/I/Q)");
if (!int.TryParse(s.AsSpan(offsetEnd + 1), out var bitOffset) || bitOffset is < 0 or > 7)
throw new FormatException($"S7 bit offset in '{original}' must be 0-7");
return (byteOffset, bitOffset);
}
}
@@ -48,8 +48,23 @@ public static class S7TagDefinitionFactory
/// <param name="def">The mapped definition when this returns <see langword="true"/>.</param>
/// <returns><see langword="true"/> when <paramref name="tagConfig"/> is a valid S7 address object.</returns>
public static bool FromTagConfig(string tagConfig, string rawPath, out S7TagDefinition def)
=> FromTagConfig(tagConfig, rawPath, out def, out _);
/// <summary>
/// <see cref="FromTagConfig(string, string, out S7TagDefinition)"/>, also reporting WHY a structurally
/// valid blob was refused by <see cref="S7TagShapeRules"/> (an unparseable address, or a shape the
/// driver cannot serve). <paramref name="shapeRejection"/> stays <see langword="null"/> for a JSON-level
/// refusal (missing keys, bad enum), which <see cref="Inspect"/> explains on its own.
/// </summary>
/// <param name="tagConfig">The authored equipment-tag TagConfig JSON.</param>
/// <param name="rawPath">The tag's RawPath — becomes the definition's identity (<c>Name</c>).</param>
/// <param name="def">The mapped definition when this returns <see langword="true"/>.</param>
/// <param name="shapeRejection">The shape/address rejection reason, when that is why it refused.</param>
/// <returns><see langword="true"/> when the driver can serve the tag.</returns>
public static bool FromTagConfig(string tagConfig, string rawPath, out S7TagDefinition def, out string? shapeRejection)
{
def = null!;
shapeRejection = null;
if (string.IsNullOrWhiteSpace(tagConfig)) return false;
try
{
@@ -78,7 +93,7 @@ public static class S7TagDefinitionFactory
// "writable" defaults to true when absent (today's value); node-level authz still governs
// writes. Honouring the key makes read-only equipment tags authorable.
var writable = TagConfigJson.ReadWritable(root);
def = new S7TagDefinition(
var mapped = new S7TagDefinition(
Name: rawPath,
Address: address,
DataType: dataType,
@@ -86,6 +101,15 @@ public static class S7TagDefinitionFactory
StringLength: stringLength == 0 ? MaxStringLength : stringLength,
WriteIdempotent: false,
ArrayCount: arrayCount);
// The address must parse and the shape must be one the driver can serve. These used to be
// init-time guards that THREW and faulted every tag on the PLC; refusing here skips only
// this tag, and the editor + deploy gate (which ask this method) refuse it too.
if (S7TagShapeRules.Validate(mapped, out _) is { } reason)
{
shapeRejection = reason;
return false;
}
def = mapped;
return true;
}
catch (JsonException) { return false; }
@@ -162,7 +186,9 @@ public static class S7TagDefinitionFactory
/// <b>reject</b> — a structurally unparseable or non-object document, an absent / non-string /
/// blank <c>address</c>, an <b>absent</b> <c>dataType</c> (see <see cref="DeclaresDataType"/>), a
/// present-but-invalid <c>dataType</c> (the runtime enum read is STRICT, so a
/// typo rejects the tag), or an out-of-range <c>stringLength</c> on a <c>String</c> tag. Such a tag
/// typo rejects the tag), an out-of-range <c>stringLength</c> on a <c>String</c> tag, or a shape
/// <see cref="S7TagShapeRules"/> refuses (an unparseable address, a wrong access width, a mis-typed
/// Timer/Counter, an unsupported array). Such a tag
/// is skipped by the driver and reads <c>BadNodeIdUnknown</c> forever. Empty when the mapper accepts
/// the blob, when it is blank, or when it is not an equipment-tag object. Never throws.
/// </summary>
@@ -184,7 +210,13 @@ public static class S7TagDefinitionFactory
// The accept gate: whatever the driver reads draws nothing. The RAW reference is handed to the
// mapper — the driver reads the stored blob, not a trimmed copy of it.
if (FromTagConfig(reference, InspectionRawPath, out _)) return warnings;
if (FromTagConfig(reference, InspectionRawPath, out _, out var shapeRejection)) return warnings;
if (shapeRejection is not null)
{
warnings.Add(shapeRejection + " The driver will skip this tag and it will read BadNodeIdUnknown.");
return warnings;
}
try
{
@@ -0,0 +1,149 @@
namespace ZB.MOM.WW.OtOpcUa.Driver.S7;
/// <summary>
/// <b>The single authority on which S7 tag shapes the driver can serve.</b> Consulted by
/// <see cref="S7TagDefinitionFactory.FromTagConfig"/>, so the AdminUI editor, the deploy gate
/// (<see cref="S7TagDefinitionFactory.Inspect"/>) and the driver's own init all refuse the same
/// tags with the same words.
/// </summary>
/// <remarks>
/// <para>
/// These rules used to be init-time guards in <c>S7Driver</c> that THREW. One mis-authored tag
/// (<c>DB1.DBZ0</c>, <c>DB1.DBW0</c> typed <c>Float64</c>, <c>T5</c> typed <c>Int32</c>) faulted the
/// whole driver, and the actor retried that same init every 10 s forever, darkening every tag on
/// the PLC. The editor and the deploy gate checked none of it, and a CSV import or API blob
/// bypasses the editor entirely. A rejected tag is now skipped on its own (it reads
/// <c>BadNodeIdUnknown</c>) and the deploy gate warns about it.
/// </para>
/// <para>
/// Every rule rejects a tag that could never be served correctly. None of them can newly break
/// a tag that used to work: each one either faulted init, or failed (or silently mis-decoded)
/// every read of that tag.
/// </para>
/// </remarks>
public static class S7TagShapeRules
{
/// <summary>
/// S7 data types addressed by START BYTE (the <c>B</c> suffix) rather than by an access-width
/// suffix. The driver decodes them from a contiguous byte buffer, so a wide tag authored against a
/// non-byte suffix (DBW/DBD/...) would mis-frame its value.
/// </summary>
private static readonly HashSet<S7DataType> ByteAnchoredDataTypes =
[
S7DataType.Int64,
S7DataType.UInt64,
S7DataType.Float64,
S7DataType.String,
S7DataType.DateTime,
S7DataType.WString,
S7DataType.Char,
S7DataType.WChar,
S7DataType.Dtl,
S7DataType.Date,
S7DataType.Tod,
S7DataType.Time,
S7DataType.S5Time,
];
/// <summary>True when <paramref name="dataType"/> is a wide/structured type read from a byte-anchored block.</summary>
/// <param name="dataType">The declared data type.</param>
/// <returns><see langword="true"/> for the byte-anchored types.</returns>
public static bool IsByteAnchored(S7DataType dataType) => ByteAnchoredDataTypes.Contains(dataType);
/// <summary>
/// Judges one tag definition. Returns <see langword="null"/> when the driver can serve it, or
/// the operator-facing reason it cannot.
/// </summary>
/// <param name="def">The mapped tag definition.</param>
/// <param name="parsed">The parsed address when this returns <see langword="null"/>.</param>
/// <returns>The rejection reason, or <see langword="null"/> when the tag is servable.</returns>
public static string? Validate(S7TagDefinition def, out S7ParsedAddress parsed)
{
ArgumentNullException.ThrowIfNull(def);
parsed = default;
S7ParsedAddress addr;
try
{
addr = S7AddressParser.Parse(def.Address);
}
catch (FormatException ex)
{
return $"S7 address '{def.Address}' does not parse: {ex.Message}";
}
var isWide = IsByteAnchored(def.DataType);
var isArray = def.ArrayCount is >= 1;
// Wide-type arrays have no decoder.
if (isWide && isArray)
return $"S7 {def.DataType} arrays are not supported. Use a scalar {def.DataType} tag, or an " +
"Int16/UInt16/Int32/UInt32/Float32/Byte/Bool element type for an array.";
// Timer / Counter type constraints: a timer decodes to Float64 seconds, a counter to an Int32 count.
if (addr.Area is S7Area.Timer && def.DataType != S7DataType.Float64)
return $"S7 Timer address '{def.Address}' is typed {def.DataType}. Timer tags must be " +
"DataType=Float64 (decoded to seconds, read-only).";
if (addr.Area is S7Area.Counter && def.DataType != S7DataType.Int32)
return $"S7 Counter address '{def.Address}' is typed {def.DataType}. Counter tags must be " +
"DataType=Int32 (decoded to a count, read-only).";
if (addr.Area is S7Area.Timer or S7Area.Counter)
{
if (isArray)
return $"S7 Timer/Counter address '{def.Address}' cannot be an array.";
if (def.Writable)
return $"S7 Timer/Counter address '{def.Address}' is declared writable. Timer/Counter tags " +
"are read-only; set Writable=false.";
parsed = addr;
return null;
}
// Wide/structured scalars on DB/M/I/Q must be byte-anchored (DBB/MB/IB/QB).
if (isWide)
{
if (addr.Size != S7Size.Byte)
return $"S7 {def.DataType} at '{def.Address}' is not byte-addressed. Wide/structured types " +
"must be byte-addressed (DBB/MB/IB/QB), e.g. 'DB1.DBB0', 'MB4'.";
parsed = addr;
return null;
}
// Narrow types: the declared type must match the address's access width, or every read fails
// (or decodes garbage) with a type mismatch.
var required = def.DataType switch
{
S7DataType.Bool => S7Size.Bit,
S7DataType.Byte => S7Size.Byte,
S7DataType.Int16 or S7DataType.UInt16 => S7Size.Word,
_ => S7Size.DWord, // Int32 / UInt32 / Float32
};
if (addr.Size != required)
return $"S7 {def.DataType} at '{def.Address}' has the wrong access width ({addr.Size}). " +
$"A {def.DataType} tag needs a {SuffixHint(required)} address.";
if (isArray && def.DataType == S7DataType.Bool)
{
// Element i of a Bool array is bit 0 of byte (start + i): the array is byte-granular. A
// non-zero bit offset used to be silently ignored (DB1.DBX0.3 returned bit 0 of bytes 0..n).
if (addr.BitOffset != 0)
return $"S7 Bool array at '{def.Address}' starts at bit {addr.BitOffset}. A Bool array reads " +
"one byte per element (bit 0 of each byte), so it must start at bit 0 (e.g. 'DB1.DBX0.0').";
// A byte-granular write would overwrite the 7 neighbouring bits of every byte it touches.
if (def.Writable)
return $"S7 Bool array at '{def.Address}' is declared writable. Bool array writes are not " +
"supported (a byte-granular write would clobber neighbouring bits); set Writable=false " +
"or write the bits as individual scalar Bool tags.";
}
parsed = addr;
return null;
}
private static string SuffixHint(S7Size size) => size switch
{
S7Size.Bit => "bit (DBX/M/I/Q n.b)",
S7Size.Byte => "byte (DBB/MB/IB/QB)",
S7Size.Word => "word (DBW/MW/IW/QW)",
_ => "double-word (DBD/MD/ID/QD)",
};
}