fix(s7): refuse unservable tag shapes per tag at every gate (R07:H3, R07:U4)

The init-time tag guards THREW: one mis-authored tag (DB1.DBZ0, DB1.DBW0 typed
Float64, T5 typed Int32, a writable Bool array) faulted the whole driver and the
actor retried the same init every 10 s forever, darkening every tag on the PLC.
Neither the editor nor the deploy gate checked any of it.

- S7AddressParser moves to S7.Contracts (same namespace) and a new
  S7TagShapeRules there is the single authority on servable shapes.
- S7TagDefinitionFactory.FromTagConfig applies it, so the AdminUI editor, the
  deploy gate (Inspect, with the specific reason) and the driver init refuse
  the same tags. Init now skips a refused tag (ISkippedTagReporter) instead of
  throwing; the throwing RejectUnsupportedTagConfigs is gone.
- New rules on top of the old guards: a narrow type at the wrong access width
  (every read failed) and a Bool array not starting at bit 0 (U4: DB1.DBX0.3
  silently read bit 0 of bytes 0..n).
- AdminUI test fixtures that used addresses the driver could never serve
  (DB1.DBS0, a browse "SomeAddress", Int32/Float32 on DBW) now use real ones.

Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
This commit is contained in:
Joseph Doherty
2026-10-22 15:04:19 -04:00
parent 7bcb6331ed
commit 87a7414df7
19 changed files with 598 additions and 368 deletions
@@ -1,222 +0,0 @@
namespace ZB.MOM.WW.OtOpcUa.Driver.S7;
/// <summary>
/// Siemens S7 memory area. The driver's tag-address parser maps every S7 tag string into
/// exactly one of these + an offset. Values match the on-wire S7 area codes only
/// incidentally — S7.Net uses its own <c>DataType</c> enum (<c>DataBlock</c>, <c>Memory</c>,
/// <c>Input</c>, <c>Output</c>, <c>Timer</c>, <c>Counter</c>) so the adapter layer translates.
/// </summary>
public enum S7Area
{
DataBlock,
Memory, // M (Merker / marker byte)
Input, // I (process-image input)
Output, // Q (process-image output)
Timer,
Counter,
}
/// <summary>
/// Access width for a DB / M / I / Q address. Timers and counters are always 16-bit
/// opaque (not user-addressable via size suffixes).
/// </summary>
public enum S7Size
{
Bit, // X
Byte, // B
Word, // W — 16-bit
DWord, // D — 32-bit
}
/// <summary>
/// Parsed form of an S7 tag-address string. Produced by <see cref="S7AddressParser.Parse"/>.
/// </summary>
/// <param name="Area">Memory area (DB, M, I, Q, T, C).</param>
/// <param name="DbNumber">Data block number; only meaningful when <paramref name="Area"/> is <see cref="S7Area.DataBlock"/>.</param>
/// <param name="Size">Access width. Always <see cref="S7Size.Word"/> for Timer and Counter.</param>
/// <param name="ByteOffset">Byte offset into the area (for DB/M/I/Q) or the timer/counter number.</param>
/// <param name="BitOffset">Bit position 0-7 when <paramref name="Size"/> is <see cref="S7Size.Bit"/>; 0 otherwise.</param>
public readonly record struct S7ParsedAddress(
S7Area Area,
int DbNumber,
S7Size Size,
int ByteOffset,
int BitOffset);
/// <summary>
/// Parses Siemens S7 address strings into <see cref="S7ParsedAddress"/>. Accepts the
/// Siemens TIA-Portal / STEP 7 Classic syntax documented in <c>docs/v2/driver-specs.md</c> §5:
/// <list type="bullet">
/// <item><c>DB{n}.DB{X|B|W|D}{offset}[.bit]</c> — e.g. <c>DB1.DBX0.0</c>, <c>DB1.DBW0</c>, <c>DB1.DBD4</c></item>
/// <item><c>M{B|W|D}{offset}</c> or <c>M{offset}.{bit}</c> — e.g. <c>MB0</c>, <c>MW0</c>, <c>MD4</c>, <c>M0.0</c></item>
/// <item><c>I{B|W|D}{offset}</c> or <c>I{offset}.{bit}</c> — e.g. <c>IB0</c>, <c>IW0</c>, <c>ID0</c>, <c>I0.0</c></item>
/// <item><c>Q{B|W|D}{offset}</c> or <c>Q{offset}.{bit}</c> — e.g. <c>QB0</c>, <c>QW0</c>, <c>QD0</c>, <c>Q0.0</c></item>
/// <item><c>T{n}</c> — e.g. <c>T0</c>, <c>T15</c></item>
/// <item><c>C{n}</c> — e.g. <c>C0</c>, <c>C10</c></item>
/// </list>
/// Grammar is case-insensitive. Leading/trailing whitespace tolerated. Bit specifiers
/// must be 0-7; byte offsets must be non-negative; DB numbers must be &gt;= 1.
/// </summary>
/// <remarks>
/// Parse is deliberately strict — the parser rejects syntactic garbage up-front so a bad
/// tag config fails at driver init time instead of surfacing as a misleading
/// <c>BadInternalError</c> on every Read against that tag.
/// </remarks>
public static class S7AddressParser
{
/// <summary>
/// Parse an S7 address. Throws <see cref="FormatException"/> on any syntax error with
/// the offending input echoed in the message so operators can correlate to the tag
/// config that produced the fault.
/// </summary>
/// <param name="address">The S7 address string to parse.</param>
/// <returns>The parsed address structure.</returns>
/// <exception cref="FormatException">Thrown if the address syntax is invalid.</exception>
public static S7ParsedAddress Parse(string address)
{
if (string.IsNullOrWhiteSpace(address))
throw new FormatException("S7 address must not be empty");
var s = address.Trim().ToUpperInvariant();
// --- DB{n}.DB{X|B|W|D}{offset}[.bit] ---
if (s.StartsWith("DB") && TryParseDataBlock(s, out var dbResult))
return dbResult;
if (s.Length < 2)
throw new FormatException($"S7 address '{address}' is too short to parse");
var areaChar = s[0];
var rest = s.Substring(1);
switch (areaChar)
{
case 'M': return ParseMIQ(S7Area.Memory, rest, address);
case 'I': return ParseMIQ(S7Area.Input, rest, address);
case 'Q': return ParseMIQ(S7Area.Output, rest, address);
case 'T': return ParseTimerOrCounter(S7Area.Timer, rest, address);
case 'C': return ParseTimerOrCounter(S7Area.Counter, rest, address);
default:
throw new FormatException($"S7 address '{address}' starts with unknown area '{areaChar}' (expected DB/M/I/Q/T/C)");
}
}
/// <summary>
/// Try-parse variant for callers that can't afford an exception on bad input (e.g.
/// config validation pages in the Admin UI). Returns <c>false</c> for any input that
/// would throw from <see cref="Parse"/>.
/// </summary>
/// <param name="address">The S7 address string to parse.</param>
/// <param name="result">The parsed address structure (valid only if method returns true).</param>
/// <returns>True if parsing succeeded; false otherwise.</returns>
public static bool TryParse(string address, out S7ParsedAddress result)
{
try
{
result = Parse(address);
return true;
}
catch (FormatException)
{
result = default;
return false;
}
}
private static bool TryParseDataBlock(string s, out S7ParsedAddress result)
{
result = default;
// Split on first '.': left side must be DB{n}, right side DB{X|B|W|D}{offset}[.bit]
var dot = s.IndexOf('.');
if (dot < 0) return false;
var head = s.Substring(0, dot); // DB{n}
var tail = s.Substring(dot + 1); // DB{X|B|W|D}{offset}[.bit]
if (head.Length < 3) return false;
if (!int.TryParse(head.AsSpan(2), out var dbNumber) || dbNumber < 1)
throw new FormatException($"S7 DB number in '{s}' must be a positive integer");
if (!tail.StartsWith("DB") || tail.Length < 4)
throw new FormatException($"S7 DB address tail '{tail}' must start with DB{{X|B|W|D}}");
var sizeChar = tail[2];
var offsetStart = 3;
var size = sizeChar switch
{
'X' => S7Size.Bit,
'B' => S7Size.Byte,
'W' => S7Size.Word,
'D' => S7Size.DWord,
_ => throw new FormatException($"S7 DB size '{sizeChar}' in '{s}' must be X/B/W/D"),
};
var (byteOffset, bitOffset) = ParseOffsetAndOptionalBit(tail, offsetStart, size, s);
result = new S7ParsedAddress(S7Area.DataBlock, dbNumber, size, byteOffset, bitOffset);
return true;
}
private static S7ParsedAddress ParseMIQ(S7Area area, string rest, string original)
{
if (rest.Length == 0)
throw new FormatException($"S7 address '{original}' has no offset");
var first = rest[0];
S7Size size;
int offsetStart;
switch (first)
{
case 'B': size = S7Size.Byte; offsetStart = 1; break;
case 'W': size = S7Size.Word; offsetStart = 1; break;
case 'D': size = S7Size.DWord; offsetStart = 1; break;
default:
// No size prefix => bit-level address requires explicit .bit. Size stays Bit;
// ParseOffsetAndOptionalBit will demand the dot.
size = S7Size.Bit;
offsetStart = 0;
break;
}
var (byteOffset, bitOffset) = ParseOffsetAndOptionalBit(rest, offsetStart, size, original);
return new S7ParsedAddress(area, DbNumber: 0, size, byteOffset, bitOffset);
}
private static S7ParsedAddress ParseTimerOrCounter(S7Area area, string rest, string original)
{
if (rest.Length == 0)
throw new FormatException($"S7 address '{original}' has no {area} number");
if (!int.TryParse(rest, out var number) || number < 0)
throw new FormatException($"S7 {area} number in '{original}' must be a non-negative integer");
return new S7ParsedAddress(area, DbNumber: 0, S7Size.Word, number, BitOffset: 0);
}
private static (int byteOffset, int bitOffset) ParseOffsetAndOptionalBit(
string s, int start, S7Size size, string original)
{
var offsetEnd = start;
while (offsetEnd < s.Length && s[offsetEnd] >= '0' && s[offsetEnd] <= '9')
offsetEnd++;
if (offsetEnd == start)
throw new FormatException($"S7 address '{original}' has no byte-offset digits");
if (!int.TryParse(s.AsSpan(start, offsetEnd - start), out var byteOffset) || byteOffset < 0)
throw new FormatException($"S7 byte offset in '{original}' must be non-negative");
// No bit-suffix: done unless size is Bit with no prefix, which requires one.
if (offsetEnd == s.Length)
{
if (size == S7Size.Bit)
throw new FormatException($"S7 address '{original}' needs a .{{bit}} suffix for bit access");
return (byteOffset, 0);
}
if (s[offsetEnd] != '.')
throw new FormatException($"S7 address '{original}' has unexpected character after offset");
if (size != S7Size.Bit)
throw new FormatException($"S7 address '{original}' has a bit suffix but the size is {size} — bit access needs X (DB) or no size prefix (M/I/Q)");
if (!int.TryParse(s.AsSpan(offsetEnd + 1), out var bitOffset) || bitOffset is < 0 or > 7)
throw new FormatException($"S7 bit offset in '{original}' must be 0-7");
return (byteOffset, bitOffset);
}
}
@@ -239,41 +239,36 @@ public sealed class S7Driver
if (HasConfigBody(driverConfigJson))
_options = S7DriverFactoryExtensions.ParseOptions(_driverInstanceId, driverConfigJson);
// v3: build the RawPath → definition table from the authored raw tags BEFORE the config
// guards run (they now iterate the mapped table). Each entry's TagConfig blob is mapped by
// the pure factory; the entry's WriteIdempotent flag is threaded onto the def (it lives on
// the RawTagEntry, not inside the blob). A mapper miss is skipped (logged), never thrown —
// one bad tag must not fail the whole driver init.
// v3: build the RawPath → definition table from the authored raw tags. Each entry's TagConfig
// blob is mapped by the pure factory, which also applies S7TagShapeRules (the address must
// parse; wide arrays, mis-typed Timer/Counter, wrong access widths, writable Timer/Counter or
// Bool arrays and offset Bool arrays are refused). A refused tag is SKIPPED (logged, reported
// through ISkippedTagReporter, reads BadNodeIdUnknown), never thrown: these used to be init
// guards that faulted every tag on the PLC and made the actor retry the same init forever.
// The entry's WriteIdempotent flag is threaded onto the def (it lives on the RawTagEntry).
_tagsByRawPath.Clear();
_parsedByRawPath.Clear();
_resolver.Clear(); // no-op in v3 (the resolver reads the live table by closure); kept for symmetry
_skippedTags.BeginRebuild(_options.RawTags.Count);
foreach (var entry in _options.RawTags)
{
if (S7TagDefinitionFactory.FromTagConfig(entry.TagConfig, entry.RawPath, out var def))
if (S7TagDefinitionFactory.FromTagConfig(entry.TagConfig, entry.RawPath, out var def, out var shapeRejection)
&& S7AddressParser.TryParse(def.Address, out var parsedAddress))
{
_tagsByRawPath[entry.RawPath] = def with { WriteIdempotent = entry.WriteIdempotent };
_parsedByRawPath[entry.RawPath] = parsedAddress;
}
else
{
_skippedTags.Skip(entry.RawPath, "TagConfig did not map to a definition");
var reason = shapeRejection ?? "TagConfig did not map to a definition";
_skippedTags.Skip(entry.RawPath, reason);
_logger.LogWarning(
"S7 tag config did not map to a definition; skipping. Driver={DriverInstanceId} RawPath={RawPath}",
_driverInstanceId, entry.RawPath);
"S7 tag skipped: {Reason} Driver={DriverInstanceId} RawPath={RawPath}",
reason, _driverInstanceId, entry.RawPath);
}
}
_skippedTags.Commit();
// Phase 4d combined config guard. Timer/Counter addresses and the wide/structured
// types (Int64/UInt64/Float64/String/DateTime) are now SUPPORTED, but only in
// specific shapes — this rejects the genuinely-unsupported configurations
// (wide-type arrays, non-byte-addressed wide scalars, wrong Timer/Counter DataType)
// so a config typo fails fast at init instead of as a misleading per-read fault.
RejectUnsupportedTagConfigs();
// Legacy data-type seam. The UnimplementedDataTypes set is now
// empty (Phase 4d unblocked all five wide types), so this rejects nothing — kept as
// the single grep target / future seam should a type ever need re-gating at init.
RejectUnsupportedTagDataTypes();
// Build the connection through the factory (the same seam EnsureConnectedAsync's reopen
// uses) so the read/write timeouts are baked in identically on connect and reconnect.
var plc = _plcFactory.Create(_options);
@@ -306,15 +301,6 @@ public sealed class S7Driver
_connectBackoff.RecordSuccess();
Volatile.Write(ref _negotiatedPduSize, plc.MaxPduSize);
// Parse every tag's address once at init so config typos fail fast here instead
// of surfacing as BadInternalError on every Read against the bad tag. The parser
// also rejects bit-offset > 7, DB 0, unknown area letters, etc. Keyed by RawPath
// (== def.Name) so Read/Write can pick up the pre-parsed address.
foreach (var t in _tagsByRawPath.Values)
{
_parsedByRawPath[t.Name] = S7AddressParser.Parse(t.Address); // throws FormatException
}
_initialized = true;
Health = new DriverHealth(DriverState.Healthy, DateTime.UtcNow, null);
_logger.LogInformation("S7Driver connected. Driver={DriverInstanceId} Host={Host} CPU={CpuType} PduSize={PduSize} Tags={TagCount}",
@@ -437,13 +423,6 @@ public sealed class S7Driver
return trimmed is not "{}" and not "[]";
}
/// <summary>
/// S7 data types addressed by START BYTE (the <c>B</c> suffix) rather than by an
/// access-width suffix. Phase 4d decodes these from a contiguous byte buffer
/// (<c>DB{n}.DBB{offset}</c> / <c>MB</c> / <c>IB</c> / <c>QB{offset}</c>), so a wide tag
/// authored against a non-byte suffix (DBW/DBD/…) is a config error — see
/// <see cref="RejectUnsupportedTagConfigs"/>.
/// </summary>
/// <summary>
/// PDU size the CPU negotiated on the most recent successful connect, in bytes; 0 before the first
/// connect and after shutdown. Snapshotted at connect so it stays readable while the handle is
@@ -474,143 +453,6 @@ public sealed class S7Driver
: new Dictionary<string, string>();
}
private static readonly HashSet<S7DataType> ByteAnchoredDataTypes = new()
{
S7DataType.Int64,
S7DataType.UInt64,
S7DataType.Float64,
S7DataType.String,
S7DataType.DateTime,
S7DataType.WString,
S7DataType.Char,
S7DataType.WChar,
S7DataType.Dtl,
S7DataType.Date,
S7DataType.Tod,
S7DataType.Time,
S7DataType.S5Time,
};
/// <summary>
/// Combined init-time config guard (Phase 4d, supersedes the old Timer/Counter-only
/// <c>RejectUnsupportedTagAddresses</c>). Timer/Counter tags and the wide/structured
/// types (Int64/UInt64/Float64/String/DateTime) are now <i>supported</i> — but only in
/// specific shapes. This guard fails fast on the genuinely-unsupported configurations so
/// a config typo throws here at init rather than as a misleading per-read fault:
/// <list type="bullet">
/// <item>(a) a wide/structured type declared as an array — wide-type arrays are out of scope this phase.</item>
/// <item>(b) a wide/structured type on a DB/M/I/Q area whose address isn't byte-anchored (<c>DBB</c>/<c>MB</c>/<c>IB</c>/<c>QB</c>).</item>
/// <item>(c) a Timer tag not typed <c>Float64</c>, or a Counter tag not typed <c>Int32</c>.</item>
/// </list>
/// Addresses that don't parse are left to the existing <see cref="S7AddressParser.Parse"/>
/// pass in <see cref="InitializeAsync"/> so the parse error isn't double-handled.
/// </summary>
private void RejectUnsupportedTagConfigs()
{
foreach (var t in _tagsByRawPath.Values)
{
var isWide = ByteAnchoredDataTypes.Contains(t.DataType);
// (a) wide-type arrays — out of scope this phase.
if (isWide && t.ArrayCount is >= 1)
{
throw new NotSupportedException(
$"S7 tag '{t.Name}' is a {t.DataType} array, which the S7 driver does not yet " +
"support. Use a scalar wide tag, or an Int16/UInt16/Int32/UInt32/Float32/Byte/Bool " +
"element type for arrays.");
}
// Parse the address; if it doesn't parse, leave it for the InitializeAsync
// S7AddressParser.Parse pass to throw the FormatException (no double-handling).
if (!S7AddressParser.TryParse(t.Address, out var parsed))
continue;
// (b) wide/structured scalar on DB/M/I/Q must be byte-anchored (Size == Byte). The
// codec decodes from a byte buffer at the start byte; a non-byte suffix (DBW/DBD/…)
// would mis-frame the value.
if (isWide
&& parsed.Area is S7Area.DataBlock or S7Area.Memory or S7Area.Input or S7Area.Output
&& parsed.Size != S7Size.Byte)
{
throw new NotSupportedException(
$"S7 tag '{t.Name}' is a {t.DataType} at '{t.Address}', which is not byte-addressed. " +
"Wide/structured types must be byte-addressed (DBB/MB/IB/QB) — e.g. 'DB1.DBB0', 'MB4'.");
}
// (c) Timer/Counter type constraints — Timer decodes to a Float64 (seconds), Counter
// to an Int32 (count); both are read-only.
if (parsed.Area is S7Area.Timer && t.DataType != S7DataType.Float64)
{
throw new NotSupportedException(
$"S7 tag '{t.Name}' is a Timer address ('{t.Address}') but is typed {t.DataType}. " +
"Timer tags must be DataType=Float64 (decoded to seconds, read-only).");
}
if (parsed.Area is S7Area.Counter && t.DataType != S7DataType.Int32)
{
throw new NotSupportedException(
$"S7 tag '{t.Name}' is a Counter address ('{t.Address}') but is typed {t.DataType}. " +
"Counter tags must be DataType=Int32 (decoded to count, read-only).");
}
// (d) Timer/Counter declared Writable — writes are read-only this phase; without this
// a node is discovered as Operate-writable but every write returns BadNotSupported.
if (parsed.Area is S7Area.Timer or S7Area.Counter && t.Writable)
{
throw new NotSupportedException(
$"S7 tag '{t.Name}' is a Timer/Counter ('{t.Address}') declared Writable — " +
"Timer/Counter are read-only this phase; set Writable=false.");
}
// (e) Bool array declared Writable — element writes are byte-granular (one byte per
// element, mirroring the read), so a write would overwrite the 7 neighbouring bits of
// every byte it touches; a safe bit-packed write needs read-modify-write and is not
// implemented. Every other supported element type (Byte/Int16/UInt16/Int32/UInt32/
// Float32) writes as ONE contiguous block (EncodeArrayBlock). Wide-type arrays
// are already rejected above (guard-a).
if (t.ArrayCount is >= 1 && t.Writable && t.DataType == S7DataType.Bool)
{
throw new NotSupportedException(
$"S7 tag '{t.Name}' is a Bool array (ArrayCount={t.ArrayCount}) declared Writable — " +
"Bool array writes are not supported (a byte-granular write would clobber the neighbouring " +
"bits). Set Writable=false, or write the bits as individual scalar Bool tags.");
}
}
}
/// <summary>
/// Rejects tags configured with an <see cref="S7DataType"/> still on the
/// <see cref="UnimplementedDataTypes"/> list — types <see cref="ReinterpretRawValue"/> /
/// <see cref="BoxValueForWrite"/> throw <see cref="NotSupportedException"/> for, which
/// would otherwise create live OPC UA nodes via <see cref="DiscoverAsync"/> that return
/// <c>BadNotSupported</c> on every access.
/// <b>The set is now empty</b> (Phase 4d unblocked all five wide types), so this rejects
/// nothing — kept as the seam / grep target should a type ever need re-gating at init.
/// </summary>
private void RejectUnsupportedTagDataTypes()
{
foreach (var t in _tagsByRawPath.Values)
{
if (UnimplementedDataTypes.Contains(t.DataType))
{
throw new NotSupportedException(
$"S7 tag '{t.Name}' uses data type '{t.DataType}' which is not yet " +
"supported by the S7 driver — Read/Write would return BadNotSupported. " +
"Remove the tag or use Bool/Byte/Int16/UInt16/Int32/UInt32/Float32 until " +
$"{t.DataType} is wired through.");
}
}
}
/// <summary>
/// S7DataType members that the read/write helpers throw NotSupportedException for.
/// <b>Now empty</b> — Phase 4d (S7 wide types + Timer/Counter) wired Int64, UInt64,
/// Float64, String, and DateTime through the byte-buffer codec, and Timer/Counter read
/// through it on AREA. Kept here (rather than reflecting over
/// <see cref="ReinterpretRawValue"/>) as the single grep target / future seam should a
/// data type ever need re-gating at init.
/// </summary>
private static readonly HashSet<S7DataType> UnimplementedDataTypes = new();
// ---- IReadable ----
// The batch is served in two passes under ONE gate acquisition. First S7ReadSpanPlanner groups
@@ -1378,7 +1220,7 @@ public sealed class S7Driver
/// <returns><c>true</c> if the tag routes through the byte-buffer codec.</returns>
internal static bool IsBufferType(S7TagDefinition tag, S7ParsedAddress addr) =>
addr.Area is S7Area.Timer or S7Area.Counter
|| ByteAnchoredDataTypes.Contains(tag.DataType);
|| S7TagShapeRules.IsByteAnchored(tag.DataType);
/// <summary>