Phase 3 PR 46 -- DL205 BCD decoder (binary-coded-decimal numeric encoding). Adds ModbusDataType.Bcd16 and Bcd32 to the driver. Bcd16 is 1 register wide, Bcd32 is 2 registers wide; Bcd32 respects ModbusByteOrder (BigEndian/WordSwap) the same way Int32 does so the CDAB-style families (including DL205/DL260 themselves) can be configured. DecodeRegister uses the new internal DecodeBcd helper: walks each nibble from MSB to LSB, multiplies the running result by 10, adds the nibble as a decimal digit. Explicitly rejects nibbles > 9 with InvalidDataException -- hardware sometimes produces garbage during write-in-progress transitions and silently returning wrong numeric values would quietly corrupt the caller's data. EncodeRegister's new EncodeBcd inverts the operation (mod/div by 10 nibble-by-nibble) with an up-front overflow check against 10^nibbles-1. Why this matters for DL205/DL260: AutomationDirect DirectLOGIC uses BCD as the default numeric encoding for timers, counters, and operator-display numerics (not binary). A plain Int16 read of register 0x1234 returns 4660; the BCD path returns 1234. The two differ enough that silently defaulting to Int16 would give wildly wrong HMI values -- the caller must opt in to Bcd16/Bcd32 per tag. Unit tests: DecodeBcd (theory: 0,1,9,10,1234,9999), DecodeBcd_rejects_nibbles_above_nine, EncodeBcd (theory), Bcd16_decodes_DL205_register_1234_as_decimal_1234 (control: same bytes as Int16 decode to 4660), Bcd16_encode_round_trips_with_decode, Bcd16_encode_rejects_out_of_range_values, Bcd32_decodes_8_digits_big_endian, Bcd32_word_swap_handles_CDAB_layout, Bcd32_encode_round_trips_with_decode, Bcd_RegisterCount_matches_underlying_width. 66/66 Modbus.Tests pass. Integration test: DL205BcdQuirkTests.DL205_BCD16_decodes_HR1072_as_decimal_1234 against dl205.json pymodbus profile (HR[1072]=0x1234). Asserts Bcd16 decode=1234 AND Int16 decode=0x1234 on the same wire bytes to prove the paths are distinct. 3/3 DL205 integration tests pass with MODBUS_SIM_PROFILE=dl205.
This commit is contained in:
@@ -0,0 +1,56 @@
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.DL205;
|
||||
|
||||
/// <summary>
|
||||
/// Verifies DL205/DL260 binary-coded-decimal register handling against the
|
||||
/// <c>dl205.json</c> pymodbus profile. HR[1072] = 0x1234 on the profile represents
|
||||
/// decimal 1234 (BCD nibbles). Reading it as <see cref="ModbusDataType.Int16"/> would
|
||||
/// return 0x1234 = 4660; the <see cref="ModbusDataType.Bcd16"/> path decodes 1234.
|
||||
/// </summary>
|
||||
[Collection(ModbusSimulatorCollection.Name)]
|
||||
[Trait("Category", "Integration")]
|
||||
[Trait("Device", "DL205")]
|
||||
public sealed class DL205BcdQuirkTests(ModbusSimulatorFixture sim)
|
||||
{
|
||||
[Fact]
|
||||
public async Task DL205_BCD16_decodes_HR1072_as_decimal_1234()
|
||||
{
|
||||
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
||||
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "dl205",
|
||||
StringComparison.OrdinalIgnoreCase))
|
||||
{
|
||||
Assert.Skip("MODBUS_SIM_PROFILE != dl205 — skipping (standard profile does not seed HR[1072]).");
|
||||
}
|
||||
|
||||
var options = new ModbusDriverOptions
|
||||
{
|
||||
Host = sim.Host,
|
||||
Port = sim.Port,
|
||||
UnitId = 1,
|
||||
Timeout = TimeSpan.FromSeconds(2),
|
||||
Tags =
|
||||
[
|
||||
new ModbusTagDefinition("DL205_Count_Bcd",
|
||||
ModbusRegion.HoldingRegisters, Address: 1072,
|
||||
DataType: ModbusDataType.Bcd16, Writable: false),
|
||||
new ModbusTagDefinition("DL205_Count_Int16",
|
||||
ModbusRegion.HoldingRegisters, Address: 1072,
|
||||
DataType: ModbusDataType.Int16, Writable: false),
|
||||
],
|
||||
Probe = new ModbusProbeOptions { Enabled = false },
|
||||
};
|
||||
await using var driver = new ModbusDriver(options, driverInstanceId: "dl205-bcd");
|
||||
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
|
||||
var results = await driver.ReadAsync(["DL205_Count_Bcd", "DL205_Count_Int16"],
|
||||
TestContext.Current.CancellationToken);
|
||||
|
||||
results[0].StatusCode.ShouldBe(0u);
|
||||
results[0].Value.ShouldBe(1234, "DL205 BCD register 0x1234 represents decimal 1234 per the DirectLOGIC convention");
|
||||
|
||||
results[1].StatusCode.ShouldBe(0u);
|
||||
results[1].Value.ShouldBe((short)0x1234, "same register read as Int16 returns the raw 0x1234 = 4660 value — proves BCD path is distinct");
|
||||
}
|
||||
}
|
||||