fix(driver-twincat): align status-mapper tests with corrected ADS codes (Driver.TwinCAT-011)
The Driver.TwinCAT-011 fix rewrote TwinCATStatusMapper with correct numeric values from Beckhoff.TwinCAT.Ads 7.0.172 (e.g. DeviceSymbol- VersionInvalid = 1809 / 0x0711, not 1794 / 0x0702). Pre-existing StatusMapper_covers_known_ads_error_codes InlineData cases were written against the old wrong mappings and now fail; StatusMapper_recognises_ symbol_version_changed_code asserted the legacy 0x0702 constant. Update both test files to match the corrected mapper and add a comment documenting the correction. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -93,13 +93,18 @@ public sealed class TwinCATDriverTests
|
||||
|
||||
[Theory]
|
||||
[InlineData(0u, TwinCATStatusMapper.Good)]
|
||||
[InlineData(1798u, TwinCATStatusMapper.BadNodeIdUnknown)] // symbol not found
|
||||
[InlineData(1808u, TwinCATStatusMapper.BadNotWritable)] // access denied
|
||||
[InlineData(1861u, TwinCATStatusMapper.BadTimeout)] // sync timeout
|
||||
[InlineData(1793u, TwinCATStatusMapper.BadOutOfRange)] // invalid index group
|
||||
[InlineData(1794u, TwinCATStatusMapper.BadOutOfRange)] // invalid index offset
|
||||
[InlineData(1792u, TwinCATStatusMapper.BadNotSupported)] // service not supported
|
||||
[InlineData(7u, TwinCATStatusMapper.BadCommunicationError)] // port unreachable
|
||||
// Device-layer codes — confirmed from Beckhoff.TwinCAT.Ads 7.0.172 AdsErrorCode enum
|
||||
[InlineData(1792u, TwinCATStatusMapper.BadDeviceFailure)] // DeviceError (generic)
|
||||
[InlineData(1793u, TwinCATStatusMapper.BadNotSupported)] // DeviceServiceNotSupported
|
||||
[InlineData(1794u, TwinCATStatusMapper.BadOutOfRange)] // DeviceInvalidGroup (ADS index-group error)
|
||||
[InlineData(1798u, TwinCATStatusMapper.BadTypeMismatch)] // DeviceInvalidData (data format mismatch)
|
||||
[InlineData(1804u, TwinCATStatusMapper.BadNodeIdUnknown)] // DeviceNotFound
|
||||
[InlineData(1808u, TwinCATStatusMapper.BadNodeIdUnknown)] // DeviceSymbolNotFound
|
||||
[InlineData(1809u, TwinCATStatusMapper.BadInvalidState)] // DeviceSymbolVersionInvalid — rediscovery trigger
|
||||
[InlineData(1827u, TwinCATStatusMapper.BadNotWritable)] // DeviceAccessDenied
|
||||
[InlineData(1861u, TwinCATStatusMapper.BadTimeout)] // ClientSyncTimeOut
|
||||
// AMS router errors
|
||||
[InlineData(7u, TwinCATStatusMapper.BadCommunicationError)] // TargetMachineNotFound
|
||||
[InlineData(99999u, TwinCATStatusMapper.BadCommunicationError)] // unknown → generic comm fail
|
||||
public void StatusMapper_covers_known_ads_error_codes(uint adsError, uint expected)
|
||||
{
|
||||
|
||||
@@ -181,14 +181,18 @@ public sealed class TwinCATHighFindingsRegressionTests
|
||||
factory.Clients[0].FireSymbolVersionChanged();
|
||||
|
||||
raised.ShouldNotBeNull();
|
||||
raised!.Reason.ShouldContain("0x0702");
|
||||
raised!.Reason.ShouldContain("0x0711");
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void StatusMapper_recognises_symbol_version_changed_code()
|
||||
{
|
||||
TwinCATStatusMapper.AdsSymbolVersionChanged.ShouldBe(0x0702u);
|
||||
TwinCATStatusMapper.IsSymbolVersionChanged(0x0702u).ShouldBeTrue();
|
||||
// DeviceSymbolVersionInvalid is 1809 (0x0711) per Beckhoff.TwinCAT.Ads 7.0.172.
|
||||
// Legacy docs cited 0x0702 (= DeviceInvalidGroup, 1794) — that was a transcription error
|
||||
// corrected in Driver.TwinCAT-011.
|
||||
TwinCATStatusMapper.AdsSymbolVersionChanged.ShouldBe(0x0711u); // = 1809u
|
||||
TwinCATStatusMapper.IsSymbolVersionChanged(0x0711u).ShouldBeTrue();
|
||||
TwinCATStatusMapper.IsSymbolVersionChanged(0x0702u).ShouldBeFalse(); // DeviceInvalidGroup is NOT the trigger
|
||||
TwinCATStatusMapper.IsSymbolVersionChanged(0u).ShouldBeFalse();
|
||||
}
|
||||
}
|
||||
|
||||
Reference in New Issue