fix(historian): read-only historian bindings + ProvisionTags policy; provision OPC UA type names (#899, #898)
v2-ci / unit-tests (push) Has been cancelled
v2-ci / unit-tests (push) Has been cancelled
#899 — EnsureTags is an upsert, so binding a node to an existing AVEVA tag via historianTagname re-typed/re-described it on every add and host start. - TagConfig `historianReadOnly: true` (TagConfigIntent -> RawTagPlan.HistorianReadOnly): HistoryRead from an existing historian tag that OtOpcUa never provisions and never records into (AddressSpaceApplier.IsOwnedHistorizedValue gates both the EnsureTags hook and the recorder feed). Node-inert: surgical, not mirrored on UNS refs, in the RawTagPlan equality/hash. A non-bool value is the deploy error HistorianReadOnlyInvalid. AdminUI: CSV column HistorianReadOnly (strict), TagHistorizeConfig reads via the runtime parse. - ServerHistorian:ProvisionTags = CreateOrUpdate (default, unchanged) | CreateOnly (Gateway only: TagExistsAsync first, existing tags left alone, failed lookup not sent) | Off. Unknown value / CreateOnly on a SQL backend fail host start. - Default for an explicit historianTagname stays OWNED: overrides pin owned history across renames, a read-only default would silently stop provisioning + recording. #898 — the hook parsed Tag.DataType (an OPC UA name) as DriverDataType, so historized Float/Double/Byte/SByte tags were never provisioned. New shared HistorianDataTypeNames.TryResolve: Float->Float32, Double->Float64, Byte/SByte->Int16 (lossless, provisioned as Int2); unmapped names logged at Information. Gateway now skips Int64/UInt64 (HistorianGateway cannot create Int8/UInt8: lossless-cast-or-reject). UPGRADE: the first host start after this provisions (upserts) every existing historized Float/Double/Byte/SByte tag. Mark foreign-tag bindings historianReadOnly, or set ServerHistorian:ProvisionTags=CreateOnly/Off, before upgrading (docs/Historian.md). Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
+9
-2
@@ -20,6 +20,8 @@ namespace ZB.MOM.WW.OtOpcUa.Runtime.Tests.Drivers;
|
||||
/// </summary>
|
||||
public sealed class DeploymentArtifactRawUnsParityTests
|
||||
{
|
||||
private const string RunTagConfig = "{\"isHistorized\":true,\"historianTagname\":\"SysPulse\",\"historianReadOnly\":true}";
|
||||
|
||||
[Fact]
|
||||
public void Raw_and_uns_node_sets_are_byte_parity_between_compose_and_artifact_decode()
|
||||
{
|
||||
@@ -44,7 +46,8 @@ public sealed class DeploymentArtifactRawUnsParityTests
|
||||
var run = new Tag
|
||||
{
|
||||
TagId = "tag-run", DeviceId = "dev-1", TagGroupId = null, Name = "Run", DataType = "Boolean",
|
||||
AccessLevel = TagAccessLevel.Read, TagConfig = "{}",
|
||||
// lmxopcua#899: a read-only historian binding — the flag must survive the artifact round-trip.
|
||||
AccessLevel = TagAccessLevel.Read, TagConfig = RunTagConfig,
|
||||
};
|
||||
var profile = new Tag
|
||||
{
|
||||
@@ -81,7 +84,7 @@ public sealed class DeploymentArtifactRawUnsParityTests
|
||||
Tags = new object[]
|
||||
{
|
||||
new { TagId = "tag-speed", DeviceId = "dev-1", TagGroupId = "grp-1", Name = "Speed", DataType = "Float", AccessLevel = 1, TagConfig = "{\"isHistorized\":true,\"historianTagname\":\"WW.Speed\"}" },
|
||||
new { TagId = "tag-run", DeviceId = "dev-1", TagGroupId = (string?)null, Name = "Run", DataType = "Boolean", AccessLevel = 0, TagConfig = "{}" },
|
||||
new { TagId = "tag-run", DeviceId = "dev-1", TagGroupId = (string?)null, Name = "Run", DataType = "Boolean", AccessLevel = 0, TagConfig = RunTagConfig },
|
||||
new { TagId = "tag-profile", DeviceId = "dev-1", TagGroupId = "grp-1", Name = "Profile", DataType = "Float", AccessLevel = 0, TagConfig = "{\"region\":\"HoldingRegisters\",\"address\":100,\"dataType\":\"Float32\",\"isArray\":true,\"arrayLength\":16}" },
|
||||
new { TagId = "tag-temphi", DeviceId = "dev-1", TagGroupId = (string?)null, Name = "TempHi", DataType = "Boolean", AccessLevel = 1, TagConfig = "{\"alarm\":{\"alarmType\":\"OffNormalAlarm\",\"severity\":700}}" },
|
||||
},
|
||||
@@ -111,6 +114,10 @@ public sealed class DeploymentArtifactRawUnsParityTests
|
||||
composedAlarm.Alarm.ShouldNotBeNull();
|
||||
composedAlarm.Alarm!.AlarmType.ShouldBe("OffNormalAlarm");
|
||||
composedAlarm.Writable.ShouldBeTrue();
|
||||
var composedRun = composed.RawTags.Single(t => t.Name == "Run");
|
||||
composedRun.IsHistorized.ShouldBeTrue();
|
||||
composedRun.HistorianReadOnly.ShouldBeTrue();
|
||||
composed.RawTags.Single(t => t.Name == "Speed").HistorianReadOnly.ShouldBeFalse();
|
||||
composed.UnsReferenceVariables.Count.ShouldBe(2);
|
||||
var composedSpeedRef = composed.UnsReferenceVariables.Single(v => v.UnsTagReferenceId == "ref-1");
|
||||
composedSpeedRef.NodeId.ShouldBe("filling/line1/station1/MotorSpeed");
|
||||
|
||||
@@ -81,5 +81,9 @@ public static class TagConfigGoldenCorpus
|
||||
"{\"address\":5,\"region\":\"Coils\",\"dataType\":\"Int16\",\"isHistorized\":true,\"alarm\":{\"severity\":250},\"foo\":\"bar\"}",
|
||||
// 29 all intents combined
|
||||
"{\"address\":\"C.D\",\"isArray\":true,\"arrayLength\":4,\"isHistorized\":true,\"historianTagname\":\"H\",\"alarm\":{\"alarmType\":\"DiscreteAlarm\",\"severity\":900,\"historizeToAveva\":false}}",
|
||||
// 30 lmxopcua#899 read-only historian binding
|
||||
"{\"address\":\"A\",\"isHistorized\":true,\"historianTagname\":\"SysTimeSec\",\"historianReadOnly\":true}",
|
||||
// 31 historianReadOnly non-bool → false (the deploy gate refuses it: HistorianReadOnlyInvalid)
|
||||
"{\"address\":\"A\",\"isHistorized\":true,\"historianReadOnly\":\"true\"}",
|
||||
};
|
||||
}
|
||||
|
||||
Reference in New Issue
Block a user