fix(historian): read-only historian bindings + ProvisionTags policy; provision OPC UA type names (#899, #898)
v2-ci / unit-tests (push) Has been cancelled
v2-ci / unit-tests (push) Has been cancelled
#899 — EnsureTags is an upsert, so binding a node to an existing AVEVA tag via historianTagname re-typed/re-described it on every add and host start. - TagConfig `historianReadOnly: true` (TagConfigIntent -> RawTagPlan.HistorianReadOnly): HistoryRead from an existing historian tag that OtOpcUa never provisions and never records into (AddressSpaceApplier.IsOwnedHistorizedValue gates both the EnsureTags hook and the recorder feed). Node-inert: surgical, not mirrored on UNS refs, in the RawTagPlan equality/hash. A non-bool value is the deploy error HistorianReadOnlyInvalid. AdminUI: CSV column HistorianReadOnly (strict), TagHistorizeConfig reads via the runtime parse. - ServerHistorian:ProvisionTags = CreateOrUpdate (default, unchanged) | CreateOnly (Gateway only: TagExistsAsync first, existing tags left alone, failed lookup not sent) | Off. Unknown value / CreateOnly on a SQL backend fail host start. - Default for an explicit historianTagname stays OWNED: overrides pin owned history across renames, a read-only default would silently stop provisioning + recording. #898 — the hook parsed Tag.DataType (an OPC UA name) as DriverDataType, so historized Float/Double/Byte/SByte tags were never provisioned. New shared HistorianDataTypeNames.TryResolve: Float->Float32, Double->Float64, Byte/SByte->Int16 (lossless, provisioned as Int2); unmapped names logged at Information. Gateway now skips Int64/UInt64 (HistorianGateway cannot create Int8/UInt8: lossless-cast-or-reject). UPGRADE: the first host start after this provisions (upserts) every existing historized Float/Double/Byte/SByte tag. Mark foreign-tag bindings historianReadOnly, or set ServerHistorian:ProvisionTags=CreateOnly/Off, before upgrading (docs/Historian.md). Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
+36
@@ -219,6 +219,42 @@ public sealed class AddressSpacePlannerDualNamespaceTests
|
||||
_ = prev;
|
||||
}
|
||||
|
||||
/// <summary>lmxopcua#899: a redeploy whose ONLY change is <c>historianReadOnly</c> must reach the applier as a
|
||||
/// ChangedRawTags delta — otherwise (the field missing from RawTagPlan's hand-written equality) the flip would diff
|
||||
/// empty and a tag marked read-only would keep being provisioned and recorded until something else about it changed.</summary>
|
||||
[Theory]
|
||||
[InlineData(false, true)]
|
||||
[InlineData(true, false)]
|
||||
public void Historian_read_only_flip_alone_routes_to_ChangedRawTags(bool before, bool after)
|
||||
{
|
||||
var folder = new RawFolder { RawFolderId = "raw-plant", ClusterId = "c1", Name = RawFolderName };
|
||||
var driver = new DriverInstance
|
||||
{
|
||||
DriverInstanceId = "drv-modbus", ClusterId = "c1", RawFolderId = "raw-plant",
|
||||
Name = DriverName, DriverType = "Modbus", DriverConfig = "{}",
|
||||
};
|
||||
var device = new Device { DeviceId = "dev-1", DriverInstanceId = "drv-modbus", Name = DeviceName, DeviceConfig = "{}" };
|
||||
AddressSpaceComposition ComposeWith(bool readOnly) => AddressSpaceComposer.Compose(
|
||||
Array.Empty<UnsArea>(), Array.Empty<UnsLine>(), Array.Empty<Equipment>(),
|
||||
new[] { driver }, Array.Empty<ScriptedAlarm>(),
|
||||
tags: new[]
|
||||
{
|
||||
new Tag
|
||||
{
|
||||
TagId = "t-speed", DeviceId = "dev-1", Name = "Speed", DataType = "Int32", AccessLevel = TagAccessLevel.Read,
|
||||
TagConfig = $"{{\"isHistorized\":true,\"historianTagname\":\"SysTimeSec\",\"historianReadOnly\":{(readOnly ? "true" : "false")}}}",
|
||||
},
|
||||
},
|
||||
rawFolders: new[] { folder }, devices: new[] { device });
|
||||
|
||||
var plan = AddressSpacePlanner.Compute(ComposeWith(before), ComposeWith(after));
|
||||
|
||||
var changed = plan.ChangedRawTags.ShouldHaveSingleItem();
|
||||
changed.Previous.HistorianReadOnly.ShouldBe(before);
|
||||
changed.Current.HistorianReadOnly.ShouldBe(after);
|
||||
AddressSpaceChangeClassifier.Classify(plan).ShouldBe(AddressSpaceChangeKind.AttributeOnly); // in place, no rebuild
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// <b>THE PIN (2026-08-15 surgical-deploys review):</b> a RAW-side edit to the backing tag's historian
|
||||
/// intent or array shape must produce a <c>ChangedRawTags</c> delta AND a <b>coincident</b>
|
||||
|
||||
Reference in New Issue
Block a user