fix(historian): read-only historian bindings + ProvisionTags policy; provision OPC UA type names (#899, #898)
v2-ci / unit-tests (push) Has been cancelled
v2-ci / unit-tests (push) Has been cancelled
#899 — EnsureTags is an upsert, so binding a node to an existing AVEVA tag via historianTagname re-typed/re-described it on every add and host start. - TagConfig `historianReadOnly: true` (TagConfigIntent -> RawTagPlan.HistorianReadOnly): HistoryRead from an existing historian tag that OtOpcUa never provisions and never records into (AddressSpaceApplier.IsOwnedHistorizedValue gates both the EnsureTags hook and the recorder feed). Node-inert: surgical, not mirrored on UNS refs, in the RawTagPlan equality/hash. A non-bool value is the deploy error HistorianReadOnlyInvalid. AdminUI: CSV column HistorianReadOnly (strict), TagHistorizeConfig reads via the runtime parse. - ServerHistorian:ProvisionTags = CreateOrUpdate (default, unchanged) | CreateOnly (Gateway only: TagExistsAsync first, existing tags left alone, failed lookup not sent) | Off. Unknown value / CreateOnly on a SQL backend fail host start. - Default for an explicit historianTagname stays OWNED: overrides pin owned history across renames, a read-only default would silently stop provisioning + recording. #898 — the hook parsed Tag.DataType (an OPC UA name) as DriverDataType, so historized Float/Double/Byte/SByte tags were never provisioned. New shared HistorianDataTypeNames.TryResolve: Float->Float32, Double->Float64, Byte/SByte->Int16 (lossless, provisioned as Int2); unmapped names logged at Information. Gateway now skips Int64/UInt64 (HistorianGateway cannot create Int8/UInt8: lossless-cast-or-reject). UPGRADE: the first host start after this provisions (upserts) every existing historized Float/Double/Byte/SByte tag. Mark foreign-tag bindings historianReadOnly, or set ServerHistorian:ProvisionTags=CreateOnly/Off, before upgrading (docs/Historian.md). Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
@@ -63,6 +63,18 @@ public sealed class ServerHistorianOptionsValidator : OptionsValidatorBase<Serve
|
||||
$"ServerHistorian:Backend '{options.Backend}' is not a known historian backend. "
|
||||
+ $"Allowed values: {string.Join(", ", HistorianBackendRegistry.KnownBackends)}.");
|
||||
|
||||
builder.RequireThat(
|
||||
ServerHistorianOptions.TryParseProvisionPolicy(options.ProvisionTags, out var provisionPolicy),
|
||||
$"ServerHistorian:ProvisionTags '{options.ProvisionTags}' is not a known provisioning policy. "
|
||||
+ $"Allowed values: {string.Join(", ", Enum.GetNames<HistorianProvisionPolicy>())}.");
|
||||
|
||||
// CreateOnly needs an existence lookup only the Gateway provisioner makes; the SQL backends' stores are
|
||||
// OtOpcUa's own tables (lmxopcua#899).
|
||||
builder.RequireThat(
|
||||
!options.Enabled || provisionPolicy != HistorianProvisionPolicy.CreateOnly || options.IsGatewayBackend,
|
||||
$"ServerHistorian:ProvisionTags=CreateOnly is supported only by the Gateway backend (Backend is '{options.Backend}'). "
|
||||
+ "Use CreateOrUpdate or Off, or opt individual tags out with historianReadOnly.");
|
||||
|
||||
var alarmHistorianEnabled = _configuration.GetValue<bool>("AlarmHistorian:Enabled");
|
||||
var consumed = options.Enabled || alarmHistorianEnabled;
|
||||
|
||||
|
||||
Reference in New Issue