fix(opcuaserver): chunked, per-item-isolated WriteValues with typed partial-failure outcome
This commit is contained in:
@@ -339,7 +339,12 @@ public sealed class OpcUaPublishActor : ReceiveActor, IWithTimers
|
||||
/// <summary>Mirrors <see cref="HandleAttributeUpdate"/> for a whole burst: ONE
|
||||
/// <see cref="IOpcUaAddressSpaceSink.WriteValues"/> call, but the write tally and the
|
||||
/// <c>otopcua.opcua.sink.write</c> meter still advance PER ITEM — batching is a transport change, so
|
||||
/// dashboards must not drop by the batch factor.</summary>
|
||||
/// dashboards must not drop by the batch factor.
|
||||
/// <para>A <see cref="ValueWriteBatchException"/> is a PARTIAL failure: the sink applied every item it
|
||||
/// could and is telling us which one it couldn't. So it is caught ahead of the general catch to (a) name
|
||||
/// the offending node in the log — a bare "the batch threw" cannot be acted on — and (b) still count the
|
||||
/// items that DID land, keeping the per-item counting invariant honest instead of silently under-reporting
|
||||
/// a whole batch because one item was bad.</para></summary>
|
||||
private void HandleAttributeBatchUpdate(AttributeValueBatchUpdate msg)
|
||||
{
|
||||
try
|
||||
@@ -348,6 +353,15 @@ public sealed class OpcUaPublishActor : ReceiveActor, IWithTimers
|
||||
Interlocked.Add(ref _writes, msg.Items.Count);
|
||||
OtOpcUaTelemetry.OpcUaSinkWrite.Add(msg.Items.Count, new KeyValuePair<string, object?>("kind", "value"));
|
||||
}
|
||||
catch (ValueWriteBatchException ex)
|
||||
{
|
||||
_log.Warning(ex,
|
||||
"OpcUaPublish: sink.WriteValues partially failed for a {Count}-item batch — {Failed} failed " +
|
||||
"(first: {Node}), {Succeeded} applied",
|
||||
msg.Items.Count, ex.FailedCount, ex.FirstFailedNodeId, ex.SucceededCount);
|
||||
Interlocked.Add(ref _writes, ex.SucceededCount);
|
||||
OtOpcUaTelemetry.OpcUaSinkWrite.Add(ex.SucceededCount, new KeyValuePair<string, object?>("kind", "value"));
|
||||
}
|
||||
catch (Exception ex)
|
||||
{
|
||||
_log.Warning(ex, "OpcUaPublish: sink.WriteValues threw for a {Count}-item batch", msg.Items.Count);
|
||||
|
||||
Reference in New Issue