fix(drivers): detect mid-run comms loss and recover from it (#527)

DriverInstanceActor.DisconnectObserved had no production sender. The only paths
into Reconnecting were a failed *initial* connect and an operator's Force
Reconnect, so a driver that connected and then lost its device stayed Connected
indefinitely: publishing Bad for every tag, never re-initialising, and NOT
recovering when the device returned. PublishHealthSnapshot read GetHealth() for
reporting only and never acted on a driver reporting itself unhealthy.

Both comms-loss quality paths -- #477's native-condition annotation and #481's
scripted-alarm input fan-out -- hang off ConnectivityChanged, so both were
correctly wired to a signal that never fired.

The Connected health tick now evaluates a watchdog and self-sends
DisconnectObserved when the driver reports a non-Healthy state AND its
LastSuccessfulRead has been frozen for DefaultCommsLossTimeout (90s).

The conjunction is the design, and the issue's own proposal -- "non-Healthy for
N consecutive polls" -- is wrong. Degraded means *connected but some data is
bad*; several drivers write health per tag inside the read loop
(ModbusDriver.ReadAsync), so one unreadable address latches Degraded forever
against a perfectly reachable device, and a state-only watchdog would reconnect
that driver every 90s indefinitely -- worse than the bug. LastSuccessfulRead is
the honest evidence: preserved across Degraded/Faulted writes, advanced by any
success. The state check remains the second conjunct so an idle Healthy driver
with nothing subscribed is not declared dead for not reading.

Verified across all 12 drivers that a sustained failure does reach a non-Healthy
state -- nine poll drivers via Degraded, MQTT via live connection state, Galaxy
via its reconnect supervisor. CalculationDriver reports Healthy while running
and so can never trip, which is correct: it has no transport.

Also: the Reconnecting retry now calls ShutdownAsync before InitializeAsync.
ModbusDriver (_transport) and MqttDriver (_connection) overwrite an
IAsyncDisposable field inside InitializeAsync without disposing the previous
one, so re-initialising without a teardown leaks a socket per attempt -- latent
while only a manual Force Reconnect reached this path, but the watchdog makes it
automatic and unbounded (~360 leaks for an hour-long outage at the 10s retry).

Tests: 8 new in DriverInstanceActorCommsLossWatchdogTests, each absence
assertion carrying a positive control (a proven count of processed health-poll
ticks). Falsified five ways -- dropping either conjunct reds exactly the test
written for it, and removing the teardown, the null baseline, or the watchdog
call each reds its own guard.

Live gate PASSED on docker-dev (Modbus + otopcua-pymodbus-standard), run twice:
  - fixture stopped -> watchdog fires at ~108s, "declaring comms lost"
  - fan-out observed at Debug: "pushed BadNoCommunication for 2 mux ref(s)"
    (#481 Layer 4) and the #477 native-condition annotation on a driver
    owning conditions
  - fixture restarted -> reconnected in ~8s with NO node restart; both the raw
    (ns=2) and UNS (ns=3) NodeIds read Good with fresh timestamps

Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
This commit is contained in:
Joseph Doherty
2026-07-31 10:58:38 -04:00
parent 9fa701b14b
commit 5a7a08deca
6 changed files with 587 additions and 21 deletions
+51
View File
@@ -219,6 +219,57 @@ So a driver whose `InitializeAsync` disposes anything on its failure path must b
`MTConnectDriver` does today, because it is the only one that tears down inside a `catch`. The
shutdown paths deliberately keep the single trailing write.
### The comms-loss watchdog (Gitea #527) — `GetHealth()` is now load-bearing
`GetHealth()` used to be **reporting-only**: `DriverInstanceActor.PublishHealthSnapshot` read it every 30 s
and forwarded it to the AdminUI, and nothing ever acted on a driver that reported itself unhealthy. That
left `DisconnectObserved` with **no production sender at all** — the only paths into `Reconnecting` were a
failed *initial* connect and an operator's Force Reconnect. A driver that connected and then lost its
device stayed `Connected` forever: publishing Bad for every tag, never re-initialising, and **not
recovering when the device came back** (live-confirmed against a stopped Modbus fixture, which needed a
node restart). Both comms-loss quality paths — #477's native-condition annotation and #481's
scripted-alarm input fan-out — hang off `ConnectivityChanged`, so both were wired to a signal that never
fired.
The `Connected`-state health tick now also evaluates a watchdog, and self-sends `DisconnectObserved` when
**both** of these hold:
1. the driver reports a state other than `Healthy`, **and**
2. `DriverHealth.LastSuccessfulRead` has not advanced for `DefaultCommsLossTimeout` (90 s = three ticks),
measured from the Connected entry when the driver has never reported a successful read.
**The conjunction is the whole design, and "non-Healthy for N polls" is the wrong rule.** `Degraded` means
*connected but some data is bad* — the enum says so. Several drivers publish health **per tag inside their
read loop** (`ModbusDriver.ReadAsync` writes `Healthy` or `Degraded` once per reference), so a single
unreadable address leaves the driver latched `Degraded` whenever it happens to be read last, indefinitely,
against a device that is perfectly reachable. A state-only watchdog would tear that driver down every 90 s
forever — strictly worse than the bug it fixes. `LastSuccessfulRead` is the honest liveness evidence: every
driver advances it on any successful read and *preserves* it across `Degraded`/`Faulted` writes, so one bad
tag among good ones keeps it moving while a device that is genuinely gone freezes it. The state check is
still needed as the second conjunct, because a `Healthy` driver with nothing subscribed legitimately never
reads and must not be declared dead for being idle. Both halves are pinned by their own test in
`DriverInstanceActorCommsLossWatchdogTests`, each of which goes red when the *other* conjunct is deleted.
Two consequences worth knowing:
- **`CalculationDriver` can never trip it, correctly.** It reports `Healthy` whenever it is running and has
no transport to be degraded about. Every other driver reaches a non-Healthy state on sustained failure:
the nine poll drivers via `Degraded`, MQTT via its live connection state, Galaxy via its reconnect
supervisor. This was surveyed across all 12 before relying on it — it is the assumption the whole
mechanism rests on.
- **A device that accepts a connection but serves no data will cycle**, reconnecting once per threshold.
That is the correct reading of a broken device, it is rate-limited, and it is visible in the health
snapshot's error count — but do not mistake it for a bug when reading logs.
**The reconnect retry now tears down before re-initialising.** `Reconnecting`'s `RetryConnect` calls
`ShutdownAsync` before `InitializeAsync` — the sequence every driver's own `ReinitializeAsync` already
uses — because several drivers **overwrite** an `IAsyncDisposable` transport field inside `InitializeAsync`
without disposing the previous one (`ModbusDriver._transport`, `MqttDriver._connection`). Re-initialising
without a teardown leaks one socket per attempt. That was latent while only a manual Force Reconnect
re-entered this path; the watchdog makes it automatic and unbounded, so a device down for an hour would
have leaked ~360 transports at the 10 s retry interval. The shutdown is best-effort: a driver that throws
on it still gets its initialise attempt.
---