fix(historian): stamp a positive StorageRateMs on provisioned tags
GatewayTagProvisioner built HistorianTagDefinition without a StorageRateMs, so
the proto uint32 defaulted to 0. The gateway's EnsureTags maps StorageRateMs
straight to the AVEVA SDK's storageRateMs, which requires a positive value —
0 makes the SDK throw ArgumentOutOfRangeException ('Storage rate must be > 0 ms'),
so EVERY historized-tag auto-provision (the deploy-time IHistorianProvisioning
hook) silently failed at the gateway with failed=N.
Stamp DefaultStorageRateMs=1000 (matches the gateway's own live provisioner
convention; quantized 1000/5000/10000). Add a regression unit test asserting the
definition carries a positive rate, and set StorageRateMs on the live-suite's
inline definitions so the retype probe reaches a real EnsureTags.
Found via the R2-06 live gate against a real 0.2.0 gateway + AVEVA historian:
with this fixed, Float/Int2/UInt2/Int4/UInt4/Double all provision and the live
suite goes 3/6 -> 5/6. (Int1/Boolean remains blocked by the gateway histsdk's
ProtocolEvidenceMissingException for Int1 — a gateway-side type-support gap, not
this bug.)
Gateway driver unit 103/103.
This commit is contained in:
+3
@@ -103,6 +103,7 @@ public sealed class GatewayLiveIntegrationTests(GatewayLiveFixture fixture) : IC
|
||||
DataType = HistorianDataType.Float,
|
||||
EngineeringUnit = string.Empty,
|
||||
Description = "OtOpcUa live validation sandbox",
|
||||
StorageRateMs = 1000, // 0 makes the gateway's EnsureTags throw (storageRateMs must be > 0).
|
||||
},
|
||||
},
|
||||
ct);
|
||||
@@ -345,6 +346,7 @@ public sealed class GatewayLiveIntegrationTests(GatewayLiveFixture fixture) : IC
|
||||
DataType = HistorianDataType.Float,
|
||||
EngineeringUnit = string.Empty,
|
||||
Description = "OtOpcUa live validation retype probe (stage 1: Float)",
|
||||
StorageRateMs = 1000, // 0 makes the gateway's EnsureTags throw (storageRateMs must be > 0).
|
||||
},
|
||||
},
|
||||
ct);
|
||||
@@ -358,6 +360,7 @@ public sealed class GatewayLiveIntegrationTests(GatewayLiveFixture fixture) : IC
|
||||
DataType = HistorianDataType.Int1,
|
||||
EngineeringUnit = string.Empty,
|
||||
Description = "OtOpcUa live validation retype probe (stage 2: Int1)",
|
||||
StorageRateMs = 1000, // 0 makes the gateway's EnsureTags throw (storageRateMs must be > 0).
|
||||
},
|
||||
},
|
||||
ct);
|
||||
|
||||