Task #141 — Modbus subscribe-side knobs (deadband + write-on-change)
Two driver-side filters that ≥5 of 6 surveyed vendors expose: 1. Per-tag Deadband (double?, on ModbusTagDefinition) — when set, the PollGroupEngine onChange callback suppresses publishes whose distance from the last-published value is below the threshold. Reduces wire traffic to OPC UA clients on noisy analog signals (flow meters, temperatures). Numeric scalar types only — Bool / BitInRegister / String / array tags publish unconditionally. 2. WriteOnChangeOnly (bool, on ModbusDriverOptions) — when true, the driver short-circuits writes whose value matches the most recent successful write to that tag. Saves PLC bandwidth on clients that re-publish the same setpoint every scan. Cache invalidates on any read that returns a different value, so HMI-side changes don't get masked. Both default off so existing deployments see no behaviour change. Implementation: - ShouldPublish guard wraps the existing OnDataChange invocation. First sample always passes through (no baseline); subsequent samples compare via Convert.ToDouble for the cross-numeric-type math. - IsRedundantWrite check at the top of WriteAsync; on success the cache is populated. Object.Equals handles boxed-numeric equality; arrays are excluded (reference-equality would never match anyway). - ReadAsync invalidates the WriteOnChangeOnly cache when the new value differs from the cached last-written value. Tests (5 new ModbusSubscribeOptionsTests): - Deadband suppresses sub-threshold changes (100 → 102 → 106 → 107 with deadband=5 publishes 100 and 106 only). - Deadband=null still publishes every change. - WriteOnChangeOnly suppresses 3 identical 42 writes (only first hits wire). - WriteOnChangeOnly default false hits the wire every time. - Read-divergence cache invalidation: external panel write to 99, our client's re-write of 42 must NOT be suppressed. 220/220 unit tests green; existing ProtocolOptions tests hardened against probe-loop noise by disabling the probe in their fixtures.
This commit is contained in:
@@ -55,7 +55,47 @@ public sealed class ModbusDriver
|
||||
_poll = new PollGroupEngine(
|
||||
reader: ReadAsync,
|
||||
onChange: (handle, tagRef, snapshot) =>
|
||||
OnDataChange?.Invoke(this, new DataChangeEventArgs(handle, tagRef, snapshot)));
|
||||
{
|
||||
// #141 deadband filter: when configured on a tag, suppress publishes whose
|
||||
// numeric distance from the last-published value is below the threshold.
|
||||
if (!ShouldPublish(tagRef, snapshot)) return;
|
||||
OnDataChange?.Invoke(this, new DataChangeEventArgs(handle, tagRef, snapshot));
|
||||
});
|
||||
}
|
||||
|
||||
// Last-published value per tag, keyed by FullReference. Used by ShouldPublish to apply
|
||||
// the deadband filter. Stored as object so all numeric types share one map; the comparison
|
||||
// does a typed cast inside.
|
||||
private readonly Dictionary<string, object> _lastPublishedByRef = new(StringComparer.OrdinalIgnoreCase);
|
||||
|
||||
// Last-written value per tag for the WriteOnChangeOnly suppression. Invalidated by reads
|
||||
// that return a different value (so an HMI-side change doesn't get masked).
|
||||
private readonly Dictionary<string, object?> _lastWrittenByRef = new(StringComparer.OrdinalIgnoreCase);
|
||||
private readonly object _lastWrittenLock = new();
|
||||
|
||||
private bool ShouldPublish(string tagRef, DataValueSnapshot snapshot)
|
||||
{
|
||||
if (!_tagsByName.TryGetValue(tagRef, out var tag) || tag.Deadband is null) return true;
|
||||
if (snapshot.Value is null) return true;
|
||||
// Deadband only applies to numeric scalar types — array / Bool / String publishes
|
||||
// unconditionally. Easier to special-case skip than to enumerate the supported types.
|
||||
if (tag.ArrayCount.HasValue || tag.DataType is ModbusDataType.Bool or ModbusDataType.BitInRegister or ModbusDataType.String)
|
||||
return true;
|
||||
|
||||
if (!_lastPublishedByRef.TryGetValue(tagRef, out var prev))
|
||||
{
|
||||
// First sample passes through unconditionally — the threshold can't be evaluated
|
||||
// without a baseline. The publish lands and seeds the comparison.
|
||||
_lastPublishedByRef[tagRef] = snapshot.Value;
|
||||
return true;
|
||||
}
|
||||
|
||||
var newD = Convert.ToDouble(snapshot.Value);
|
||||
var oldD = Convert.ToDouble(prev);
|
||||
if (Math.Abs(newD - oldD) < tag.Deadband.Value) return false;
|
||||
|
||||
_lastPublishedByRef[tagRef] = snapshot.Value;
|
||||
return true;
|
||||
}
|
||||
|
||||
public string DriverInstanceId => _driverInstanceId;
|
||||
@@ -151,6 +191,19 @@ public sealed class ModbusDriver
|
||||
var value = await ReadOneAsync(transport, tag, cancellationToken).ConfigureAwait(false);
|
||||
results[i] = new DataValueSnapshot(value, 0u, now, now);
|
||||
_health = new DriverHealth(DriverState.Healthy, now, null);
|
||||
|
||||
// Invalidate the WriteOnChangeOnly cache when the read returns a different value
|
||||
// — typically an HMI-side or PLC-internal change. Without this, a setpoint
|
||||
// tweaked at the panel could be silently re-suppressed when our client tried
|
||||
// to restore it.
|
||||
if (_options.WriteOnChangeOnly)
|
||||
{
|
||||
lock (_lastWrittenLock)
|
||||
{
|
||||
if (_lastWrittenByRef.TryGetValue(fullReferences[i], out var prev) && !Equals(prev, value))
|
||||
_lastWrittenByRef.Remove(fullReferences[i]);
|
||||
}
|
||||
}
|
||||
}
|
||||
catch (ModbusException mex)
|
||||
{
|
||||
@@ -387,10 +440,20 @@ public sealed class ModbusDriver
|
||||
results[i] = new WriteResult(StatusBadNotWritable);
|
||||
continue;
|
||||
}
|
||||
// #141 WriteOnChangeOnly suppression: skip the wire round-trip when the same value
|
||||
// was already successfully written and no read since has invalidated the cache.
|
||||
if (_options.WriteOnChangeOnly && IsRedundantWrite(w.FullReference, w.Value))
|
||||
{
|
||||
results[i] = new WriteResult(0u);
|
||||
continue;
|
||||
}
|
||||
|
||||
try
|
||||
{
|
||||
await WriteOneAsync(transport, tag, w.Value, cancellationToken).ConfigureAwait(false);
|
||||
results[i] = new WriteResult(0u);
|
||||
if (_options.WriteOnChangeOnly)
|
||||
lock (_lastWrittenLock) _lastWrittenByRef[w.FullReference] = w.Value;
|
||||
}
|
||||
catch (ModbusException mex)
|
||||
{
|
||||
@@ -404,6 +467,20 @@ public sealed class ModbusDriver
|
||||
return results;
|
||||
}
|
||||
|
||||
private bool IsRedundantWrite(string tagRef, object? value)
|
||||
{
|
||||
lock (_lastWrittenLock)
|
||||
{
|
||||
if (!_lastWrittenByRef.TryGetValue(tagRef, out var prev)) return false;
|
||||
// Object.Equals handles boxed-numeric equality (5 == 5 even if one was short and
|
||||
// one int through boxing). For arrays we deliberately don't suppress — equality
|
||||
// semantics on arrays are reference-only so the cache miss is the safer answer.
|
||||
if (prev is null || value is null) return Equals(prev, value);
|
||||
if (prev is Array || value is Array) return false;
|
||||
return prev.Equals(value);
|
||||
}
|
||||
}
|
||||
|
||||
// BitInRegister writes need a read-modify-write against the full holding register. A
|
||||
// per-register lock keeps concurrent bit-write callers from stomping on each other —
|
||||
// Write bit 0 and Write bit 5 targeting the same register can arrive on separate
|
||||
|
||||
@@ -45,6 +45,7 @@ public static class ModbusDriverFactoryExtensions
|
||||
UseFC15ForSingleCoilWrites = dto.UseFC15ForSingleCoilWrites ?? false,
|
||||
UseFC16ForSingleRegisterWrites = dto.UseFC16ForSingleRegisterWrites ?? false,
|
||||
DisableFC23 = dto.DisableFC23 ?? false,
|
||||
WriteOnChangeOnly = dto.WriteOnChangeOnly ?? false,
|
||||
AutoReconnect = dto.AutoReconnect ?? true,
|
||||
Tags = dto.Tags is { Count: > 0 }
|
||||
? [.. dto.Tags.Select(t => BuildTag(t, driverInstanceId))]
|
||||
@@ -102,7 +103,8 @@ public static class ModbusDriverFactoryExtensions
|
||||
? ModbusStringByteOrder.HighByteFirst
|
||||
: ParseEnum<ModbusStringByteOrder>(t.StringByteOrder, name, driverInstanceId, "StringByteOrder"),
|
||||
WriteIdempotent: t.WriteIdempotent ?? false,
|
||||
ArrayCount: parsed.ArrayCount);
|
||||
ArrayCount: parsed.ArrayCount,
|
||||
Deadband: t.Deadband);
|
||||
}
|
||||
|
||||
return new ModbusTagDefinition(
|
||||
@@ -121,7 +123,8 @@ public static class ModbusDriverFactoryExtensions
|
||||
? ModbusStringByteOrder.HighByteFirst
|
||||
: ParseEnum<ModbusStringByteOrder>(t.StringByteOrder, t.Name, driverInstanceId, "StringByteOrder"),
|
||||
WriteIdempotent: t.WriteIdempotent ?? false,
|
||||
ArrayCount: t.ArrayCount);
|
||||
ArrayCount: t.ArrayCount,
|
||||
Deadband: t.Deadband);
|
||||
}
|
||||
|
||||
private static T ParseEnum<T>(string? raw, string? tagName, string driverInstanceId, string field) where T : struct, Enum
|
||||
@@ -155,6 +158,7 @@ public static class ModbusDriverFactoryExtensions
|
||||
public bool? UseFC15ForSingleCoilWrites { get; init; }
|
||||
public bool? UseFC16ForSingleRegisterWrites { get; init; }
|
||||
public bool? DisableFC23 { get; init; }
|
||||
public bool? WriteOnChangeOnly { get; init; }
|
||||
public bool? AutoReconnect { get; init; }
|
||||
public List<ModbusTagDto>? Tags { get; init; }
|
||||
public ModbusProbeDto? Probe { get; init; }
|
||||
@@ -202,6 +206,7 @@ public static class ModbusDriverFactoryExtensions
|
||||
public string? StringByteOrder { get; init; }
|
||||
public bool? WriteIdempotent { get; init; }
|
||||
public int? ArrayCount { get; init; }
|
||||
public double? Deadband { get; init; }
|
||||
}
|
||||
|
||||
internal sealed class ModbusProbeDto
|
||||
|
||||
@@ -79,6 +79,17 @@ public sealed class ModbusDriverOptions
|
||||
/// </summary>
|
||||
public bool DisableFC23 { get; init; } = false;
|
||||
|
||||
/// <summary>
|
||||
/// When <c>true</c>, the driver suppresses redundant writes: if the most recent
|
||||
/// successful write to a tag carried value V and a new write of V arrives, the second
|
||||
/// write returns Good without touching the wire. Saves PLC bandwidth on clients that
|
||||
/// re-publish the same setpoint every scan. The cached "last written" is invalidated
|
||||
/// on the next read that returns a different value, so HMI-side changes don't get
|
||||
/// masked. Default <c>false</c> preserves the historical "every write goes to the wire"
|
||||
/// behaviour. Per-tag deadband lives on <c>ModbusTagDefinition.Deadband</c>.
|
||||
/// </summary>
|
||||
public bool WriteOnChangeOnly { get; init; } = false;
|
||||
|
||||
/// <summary>
|
||||
/// When <c>true</c> (default) the built-in <see cref="ModbusTcpTransport"/> detects
|
||||
/// mid-transaction socket failures (<see cref="System.IO.EndOfStreamException"/>,
|
||||
@@ -186,6 +197,13 @@ public sealed class ModbusProbeOptions
|
||||
/// registers consumed = ArrayCount * registers-per-element. Bit + array is rejected at
|
||||
/// bind time (no use case). Default null = scalar (existing behavior).
|
||||
/// </param>
|
||||
/// <param name="Deadband">
|
||||
/// When non-null, the subscribe path suppresses a publish whenever
|
||||
/// <c>|new - last_published| < Deadband</c>. Reduces wire traffic on noisy analog
|
||||
/// signals (flow meters, temperatures). Only meaningful for numeric scalar types
|
||||
/// (Int*, UInt*, Float32, Float64, Bcd*); ignored for Bool / BitInRegister / String /
|
||||
/// array tags. Default null = no deadband (every change publishes).
|
||||
/// </param>
|
||||
public sealed record ModbusTagDefinition(
|
||||
string Name,
|
||||
ModbusRegion Region,
|
||||
@@ -197,4 +215,5 @@ public sealed record ModbusTagDefinition(
|
||||
ushort StringLength = 0,
|
||||
ModbusStringByteOrder StringByteOrder = ModbusStringByteOrder.HighByteFirst,
|
||||
bool WriteIdempotent = false,
|
||||
int? ArrayCount = null);
|
||||
int? ArrayCount = null,
|
||||
double? Deadband = null);
|
||||
|
||||
@@ -63,7 +63,7 @@ public sealed class ModbusProtocolOptionsTests
|
||||
{
|
||||
var fake = new CapturingTransport();
|
||||
var tag = new ModbusTagDefinition("Run", ModbusRegion.Coils, 0, ModbusDataType.Bool);
|
||||
var drv = new ModbusDriver(new ModbusDriverOptions { Host = "f", Tags = [tag] }, "m1", _ => fake);
|
||||
var drv = new ModbusDriver(new ModbusDriverOptions { Host = "f", Tags = [tag], Probe = new ModbusProbeOptions { Enabled = false } }, "m1", _ => fake);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
await drv.WriteAsync([new WriteRequest("Run", true)], CancellationToken.None);
|
||||
@@ -76,7 +76,7 @@ public sealed class ModbusProtocolOptionsTests
|
||||
{
|
||||
var fake = new CapturingTransport();
|
||||
var tag = new ModbusTagDefinition("Run", ModbusRegion.Coils, 0, ModbusDataType.Bool);
|
||||
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], UseFC15ForSingleCoilWrites = true };
|
||||
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], UseFC15ForSingleCoilWrites = true, Probe = new ModbusProbeOptions { Enabled = false } };
|
||||
var drv = new ModbusDriver(opts, "m1", _ => fake);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
@@ -90,7 +90,7 @@ public sealed class ModbusProtocolOptionsTests
|
||||
{
|
||||
var fake = new CapturingTransport();
|
||||
var tag = new ModbusTagDefinition("Sp", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16);
|
||||
var drv = new ModbusDriver(new ModbusDriverOptions { Host = "f", Tags = [tag] }, "m1", _ => fake);
|
||||
var drv = new ModbusDriver(new ModbusDriverOptions { Host = "f", Tags = [tag], Probe = new ModbusProbeOptions { Enabled = false } }, "m1", _ => fake);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
await drv.WriteAsync([new WriteRequest("Sp", (short)42)], CancellationToken.None);
|
||||
@@ -103,7 +103,7 @@ public sealed class ModbusProtocolOptionsTests
|
||||
{
|
||||
var fake = new CapturingTransport();
|
||||
var tag = new ModbusTagDefinition("Sp", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16);
|
||||
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], UseFC16ForSingleRegisterWrites = true };
|
||||
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], UseFC16ForSingleRegisterWrites = true, Probe = new ModbusProbeOptions { Enabled = false } };
|
||||
var drv = new ModbusDriver(opts, "m1", _ => fake);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
@@ -118,7 +118,7 @@ public sealed class ModbusProtocolOptionsTests
|
||||
var fake = new CapturingTransport();
|
||||
// 2500 coils with cap 2000 → 2 reads (2000 + 500).
|
||||
var tag = new ModbusTagDefinition("Big", ModbusRegion.Coils, 0, ModbusDataType.Bool, ArrayCount: 2500);
|
||||
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], MaxCoilsPerRead = 2000 };
|
||||
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], MaxCoilsPerRead = 2000, Probe = new ModbusProbeOptions { Enabled = false } };
|
||||
var drv = new ModbusDriver(opts, "m1", _ => fake);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
|
||||
@@ -0,0 +1,172 @@
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.Tests;
|
||||
|
||||
/// <summary>
|
||||
/// #141 subscribe-side knobs: per-tag Deadband, driver-wide WriteOnChangeOnly.
|
||||
/// </summary>
|
||||
[Trait("Category", "Unit")]
|
||||
public sealed class ModbusSubscribeOptionsTests
|
||||
{
|
||||
/// <summary>
|
||||
/// Programmable transport: caller seeds a bank-of-registers value, each FC03 returns
|
||||
/// the current value. Lets tests step the underlying register through a sequence and
|
||||
/// observe how the deadband filter responds.
|
||||
/// </summary>
|
||||
private sealed class ProgrammableTransport : IModbusTransport
|
||||
{
|
||||
public ushort CurrentValue;
|
||||
public int WritesSent;
|
||||
public int FC06Count;
|
||||
public Task ConnectAsync(CancellationToken ct) => Task.CompletedTask;
|
||||
public Task<byte[]> SendAsync(byte unitId, byte[] pdu, CancellationToken ct)
|
||||
{
|
||||
switch (pdu[0])
|
||||
{
|
||||
case 0x03:
|
||||
{
|
||||
var qty = (ushort)((pdu[3] << 8) | pdu[4]);
|
||||
var resp = new byte[2 + qty * 2];
|
||||
resp[0] = 0x03; resp[1] = (byte)(qty * 2);
|
||||
for (var i = 0; i < qty; i++)
|
||||
{
|
||||
resp[2 + i * 2] = (byte)(CurrentValue >> 8);
|
||||
resp[3 + i * 2] = (byte)(CurrentValue & 0xFF);
|
||||
}
|
||||
return Task.FromResult(resp);
|
||||
}
|
||||
case 0x06:
|
||||
WritesSent++; FC06Count++;
|
||||
CurrentValue = (ushort)((pdu[3] << 8) | pdu[4]);
|
||||
return Task.FromResult(pdu);
|
||||
default:
|
||||
return Task.FromResult(new byte[] { pdu[0], 0, 0 });
|
||||
}
|
||||
}
|
||||
public ValueTask DisposeAsync() => ValueTask.CompletedTask;
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task Deadband_Suppresses_SubThreshold_Changes()
|
||||
{
|
||||
var fake = new ProgrammableTransport();
|
||||
var tag = new ModbusTagDefinition("Temp", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16, Deadband: 5.0);
|
||||
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], Probe = new ModbusProbeOptions { Enabled = false } };
|
||||
var drv = new ModbusDriver(opts, "m1", _ => fake);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
var publishes = new List<short>();
|
||||
drv.OnDataChange += (_, e) => publishes.Add((short)e.Snapshot.Value!);
|
||||
|
||||
// First publish always passes (no baseline). Then step the value:
|
||||
// 100 → 102 (delta 2 < 5, suppressed) → 106 (delta 6 ≥ 5, published) → 107 (delta 1, suppressed).
|
||||
var sub = await drv.SubscribeAsync(["Temp"], TimeSpan.FromMilliseconds(50), CancellationToken.None);
|
||||
try
|
||||
{
|
||||
fake.CurrentValue = 100;
|
||||
await Task.Delay(150);
|
||||
fake.CurrentValue = 102;
|
||||
await Task.Delay(150);
|
||||
fake.CurrentValue = 106;
|
||||
await Task.Delay(150);
|
||||
fake.CurrentValue = 107;
|
||||
await Task.Delay(150);
|
||||
}
|
||||
finally
|
||||
{
|
||||
await drv.UnsubscribeAsync(sub, CancellationToken.None);
|
||||
}
|
||||
|
||||
// Expect at most 2 distinct values surfaced (100 baseline + 106). The 102 and 107 should
|
||||
// be suppressed by the deadband. Ordering can be flaky on slow CI so we assert the set,
|
||||
// not the exact sequence.
|
||||
publishes.ShouldContain((short)100);
|
||||
publishes.ShouldContain((short)106);
|
||||
publishes.ShouldNotContain((short)102);
|
||||
publishes.ShouldNotContain((short)107);
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task Deadband_Null_Publishes_Every_Change()
|
||||
{
|
||||
var fake = new ProgrammableTransport();
|
||||
var tag = new ModbusTagDefinition("Temp", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16); // no deadband
|
||||
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], Probe = new ModbusProbeOptions { Enabled = false } };
|
||||
var drv = new ModbusDriver(opts, "m1", _ => fake);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
var publishes = new List<short>();
|
||||
drv.OnDataChange += (_, e) => publishes.Add((short)e.Snapshot.Value!);
|
||||
|
||||
var sub = await drv.SubscribeAsync(["Temp"], TimeSpan.FromMilliseconds(50), CancellationToken.None);
|
||||
try
|
||||
{
|
||||
fake.CurrentValue = 100; await Task.Delay(150);
|
||||
fake.CurrentValue = 101; await Task.Delay(150); // tiny change still publishes
|
||||
}
|
||||
finally { await drv.UnsubscribeAsync(sub, CancellationToken.None); }
|
||||
|
||||
publishes.ShouldContain((short)100);
|
||||
publishes.ShouldContain((short)101);
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task WriteOnChangeOnly_Suppresses_Identical_Repeated_Writes()
|
||||
{
|
||||
var fake = new ProgrammableTransport();
|
||||
var tag = new ModbusTagDefinition("Sp", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16);
|
||||
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], WriteOnChangeOnly = true,
|
||||
Probe = new ModbusProbeOptions { Enabled = false } };
|
||||
var drv = new ModbusDriver(opts, "m1", _ => fake);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
await drv.WriteAsync([new WriteRequest("Sp", (short)42)], CancellationToken.None);
|
||||
await drv.WriteAsync([new WriteRequest("Sp", (short)42)], CancellationToken.None); // suppressed
|
||||
await drv.WriteAsync([new WriteRequest("Sp", (short)42)], CancellationToken.None); // suppressed
|
||||
await drv.WriteAsync([new WriteRequest("Sp", (short)43)], CancellationToken.None); // distinct
|
||||
|
||||
fake.WritesSent.ShouldBe(2, "two distinct values written; identical-value repeats suppressed");
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task WriteOnChangeOnly_Default_False_Always_Writes()
|
||||
{
|
||||
var fake = new ProgrammableTransport();
|
||||
var tag = new ModbusTagDefinition("Sp", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16);
|
||||
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag],
|
||||
Probe = new ModbusProbeOptions { Enabled = false } };
|
||||
var drv = new ModbusDriver(opts, "m1", _ => fake);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
await drv.WriteAsync([new WriteRequest("Sp", (short)42)], CancellationToken.None);
|
||||
await drv.WriteAsync([new WriteRequest("Sp", (short)42)], CancellationToken.None);
|
||||
await drv.WriteAsync([new WriteRequest("Sp", (short)42)], CancellationToken.None);
|
||||
|
||||
fake.WritesSent.ShouldBe(3, "default false → every write goes to the wire");
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task WriteOnChangeOnly_Cache_Invalidated_By_Read_Divergence()
|
||||
{
|
||||
var fake = new ProgrammableTransport();
|
||||
var tag = new ModbusTagDefinition("Sp", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16);
|
||||
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], WriteOnChangeOnly = true,
|
||||
Probe = new ModbusProbeOptions { Enabled = false } };
|
||||
var drv = new ModbusDriver(opts, "m1", _ => fake);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
await drv.WriteAsync([new WriteRequest("Sp", (short)42)], CancellationToken.None);
|
||||
fake.FC06Count.ShouldBe(1);
|
||||
|
||||
// External change at the PLC (panel writes 99). Read sees 99 → invalidates the cache.
|
||||
fake.CurrentValue = 99;
|
||||
var read = await drv.ReadAsync(["Sp"], CancellationToken.None);
|
||||
read[0].Value.ShouldBe((short)99);
|
||||
|
||||
// Now writing 42 again should NOT be suppressed because the cache was invalidated.
|
||||
await drv.WriteAsync([new WriteRequest("Sp", (short)42)], CancellationToken.None);
|
||||
fake.FC06Count.ShouldBe(2, "post-divergence write not suppressed");
|
||||
}
|
||||
}
|
||||
Reference in New Issue