feat(focas): CNC alarms reach Part 9 conditions via ALARM: tags (#647)

An ALARM: address (*, <Type>, <Type>/<n>, <Type>/<lo>-<hi>, T<code>, OTHER) on a raw tag that
also carries the cross-driver alarm object is ONE condition with ConditionId == RawPath and a
Kind (Raise / Retrigger / Clear), so DriverHostActor.ForwardNativeAlarm routes it and
NativeAlarmProjector activates it. Fixes all seven triage defects:

1. SubscribeAlarmsAsync treated the host's RawPaths as device hosts -> nothing polled.
2. Decorated "{host}#{Type}:{Number}" ConditionId -> every event dropped.
3. No Kind -> projector kept prior state.
4. WireFocasClient.ReadAlarmsAsync answered [] on failure -> mass clear + un-acked re-raise.
   It now throws; a failed device read keeps every condition's state.
5. Acks lost on reconnect -> told-record dedup (MTConnect #626 pattern) held for the driver's
   lifetime; same-set re-subscribe / re-init re-raise nothing; changed set prunes leavers only.
6. Subscribe threw while AlarmProjection.Enabled=false -> the tag is the opt-in; flag is a no-op.
7. Alarm tags could not be authored -> ALARM: grammar (FocasAlarmSelector, Contracts) backs the
   editor, the address picker, the deploy-time inspector and driver init.

Severity: authored alarm.severity -> exact OpcUaSeverity; else the 16i-era type bucket. The type
table stays the only one (moved to Contracts, documented 16i-era; 30i codes not invented; raw
T<code> selector + raw code in every message). Read-only: ack is server-side. Also clears the
value table on a re-initialise (#630 gap that let a removed/moved tag keep reading).

E2E: Runtime.Tests FocasNativeAlarmEndToEndTests drives the real driver through the real
DriverHostActor and asserts the condition goes Active then inactive.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
This commit is contained in:
Joseph Doherty
2026-10-08 19:46:48 -04:00
parent 8801631739
commit 482bafdfac
27 changed files with 2110 additions and 515 deletions
@@ -39,6 +39,9 @@ public static class FocasCapabilityMatrix
// What a given CNC actually exposes there is discovered at runtime and capability-gated
// per subtree; a path this machine does not have resolves to BadNodeIdUnknown at read.
FocasAreaKind.Fixed => null,
// An ALARM: selector reads the device's whole active-alarm list (cnc_rdalmmsg2), which every
// series exposes; the selector filters it driver-side, so there is no range to check (#647).
FocasAreaKind.Alarm => null,
_ => null,
};
}