fix(opcuaclient): derive AlarmTransitionKind from upstream ActiveState/AckedState (#619 review)

NativeAlarmProjector derives Active/Acked ONLY from AlarmEventArgs.Kind, and this driver
never set it - every routed event projected Unspecified, leaving the condition inactive+acked
(only Message/Severity moved). The live-gate expectation 'toggling Active as opc-plc cycles'
could not have passed. Select ActiveState/Id + AckedState/Id (two-element browse paths) and
emit the Kind sequence that moves the projector from the state last told to the host to the
event's (Raise+Acknowledge when a notification carries both).

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
This commit is contained in:
Joseph Doherty
2026-10-08 17:04:48 -04:00
parent 3de2cc3ba8
commit 454775c67c
3 changed files with 135 additions and 5 deletions
@@ -98,6 +98,12 @@ public sealed class OpcUaClientDriver : IDriver, ITagDiscovery, IReadable, IWrit
/// node, which differs from the authored source node.</summary>
private readonly System.Collections.Concurrent.ConcurrentDictionary<string, AlarmAckTarget> _alarmConditionByRawPath =
new(StringComparer.Ordinal);
/// <summary>#619 review: the (Active, Acked) state last told to the host per reported condition id, from
/// which <see cref="AlarmTransitions"/> picks the Kind sequence that moves the host's projector to the
/// upstream event's state.</summary>
private readonly System.Collections.Concurrent.ConcurrentDictionary<string, (bool Active, bool Acked)> _alarmStateByRawPath =
new(StringComparer.Ordinal);
private long _nextAlarmSubscriptionId;
/// <summary>Occurs when an alarm event is received from the remote OPC UA server.</summary>
@@ -886,6 +892,7 @@ public sealed class OpcUaClientDriver : IDriver, ITagDiscovery, IReadable, IWrit
}
_alarmSubscriptions.Clear();
_alarmConditionByRawPath.Clear();
_alarmStateByRawPath.Clear();
await ReleaseSessionAsync(cancellationToken).ConfigureAwait(false);
_namespaceMap = null;
@@ -1628,6 +1635,8 @@ public sealed class OpcUaClientDriver : IDriver, ITagDiscovery, IReadable, IWrit
private const int AlarmFieldSeverity = 4;
private const int AlarmFieldTime = 5;
private const int AlarmFieldConditionId = 6;
private const int AlarmFieldActiveState = 7;
private const int AlarmFieldAckedState = 8;
/// <inheritdoc />
public async Task<IAlarmSubscriptionHandle> SubscribeAlarmsAsync(
@@ -1655,9 +1664,11 @@ public sealed class OpcUaClientDriver : IDriver, ITagDiscovery, IReadable, IWrit
&& !NamespaceMap.TryResolve(sessionForResolve, raw, out live)) return null;
return AlarmIndexKey(mapForResolve, live);
});
// Forget ack targets for alarm tags no longer subscribed (removed/renamed RawPaths).
// Forget ack targets + last-told states for alarm tags no longer subscribed (removed/renamed RawPaths).
foreach (var known in _alarmConditionByRawPath.Keys)
if (!sourceNodeIds.Contains(known, StringComparer.Ordinal)) _alarmConditionByRawPath.TryRemove(known, out _);
foreach (var known in _alarmStateByRawPath.Keys)
if (!sourceNodeIds.Contains(known, StringComparer.Ordinal)) _alarmStateByRawPath.TryRemove(known, out _);
var subscription = new Subscription(telemetry: null!, new SubscriptionOptions
{
@@ -1696,6 +1707,20 @@ public sealed class OpcUaClientDriver : IDriver, ITagDiscovery, IReadable, IWrit
BrowsePath = [], // empty path = the condition node itself
AttributeId = Attributes.NodeId,
});
// #619 review: the host derives Active/Acked solely from AlarmEventArgs.Kind, so the condition state
// must be selected. TWO-element browse paths — a single "ActiveState/Id" QualifiedName names nothing.
filter.SelectClauses.Add(new SimpleAttributeOperand
{
TypeDefinitionId = ObjectTypeIds.AlarmConditionType,
BrowsePath = [new QualifiedName(BrowseNames.ActiveState), new QualifiedName(BrowseNames.Id)],
AttributeId = Attributes.Value,
});
filter.SelectClauses.Add(new SimpleAttributeOperand
{
TypeDefinitionId = ObjectTypeIds.AcknowledgeableConditionType,
BrowsePath = [new QualifiedName(BrowseNames.AckedState), new QualifiedName(BrowseNames.Id)],
AttributeId = Attributes.Value,
});
await _gate.WaitAsync(cancellationToken).ConfigureAwait(false);
try
@@ -1874,8 +1899,58 @@ public sealed class OpcUaClientDriver : IDriver, ITagDiscovery, IReadable, IWrit
{
if (args.NotificationValue is not EventFieldList efl) return;
var e = ProjectEvent(efl.EventFields, sourceFilter, handle,
n => AlarmIndexKey(_namespaceMap, n), (raw, target) => _alarmConditionByRawPath[raw] = target);
if (e is not null) OnAlarmEvent?.Invoke(this, e);
n => AlarmIndexKey(_namespaceMap, n), (raw, target) => _alarmConditionByRawPath[raw] = target,
out var state);
if (e is null) return;
if (state is not { } target)
{
// Not a condition (no ActiveState/AckedState) — a message/severity-only update, as before.
OnAlarmEvent?.Invoke(this, e);
return;
}
// Fresh prior = the host projector's own default (inactive, acked).
var prior = _alarmStateByRawPath.TryGetValue(e.ConditionId, out var p) ? p : (Active: false, Acked: true);
_alarmStateByRawPath[e.ConditionId] = target;
foreach (var kind in AlarmTransitions(prior, target))
OnAlarmEvent?.Invoke(this, e with { Kind = kind });
}
/// <summary>
/// #619 review — the <see cref="AlarmTransitionKind"/> sequence that moves the host's
/// <c>NativeAlarmProjector</c> (which knows only kinds: Raise ⇒ active+unacked, Acknowledge ⇒ acked,
/// Clear ⇒ inactive keeping acked) from <paramref name="prior"/> to <paramref name="target"/>. A single
/// upstream event can need two (an alarm that went active and was acknowledged between two notifications).
/// No state change ⇒ one <see cref="AlarmTransitionKind.Unspecified"/> (message/severity refresh).
/// </summary>
/// <param name="prior">The state last told to the host.</param>
/// <param name="target">The upstream event's ActiveState/Id + AckedState/Id.</param>
/// <returns>The kinds to emit, in order.</returns>
internal static IReadOnlyList<AlarmTransitionKind> AlarmTransitions(
(bool Active, bool Acked) prior, (bool Active, bool Acked) target)
{
var kinds = new List<AlarmTransitionKind>(2);
if (target.Active && !prior.Active)
{
kinds.Add(AlarmTransitionKind.Raise);
if (target.Acked) kinds.Add(AlarmTransitionKind.Acknowledge);
}
else if (!target.Active && prior.Active)
{
kinds.Add(AlarmTransitionKind.Clear);
if (target.Acked && !prior.Acked) kinds.Add(AlarmTransitionKind.Acknowledge);
}
else if (target.Acked && !prior.Acked)
{
kinds.Add(AlarmTransitionKind.Acknowledge);
}
else if (target.Active && !target.Acked && prior.Acked)
{
kinds.Add(AlarmTransitionKind.Retrigger);
}
if (kinds.Count == 0) kinds.Add(AlarmTransitionKind.Unspecified);
return kinds;
}
/// <summary>
@@ -1907,9 +1982,25 @@ public sealed class OpcUaClientDriver : IDriver, ITagDiscovery, IReadable, IWrit
IReadOnlyDictionary<string, string> sourceIndex,
IAlarmSubscriptionHandle handle,
Func<NodeId, string> keyOf,
Action<string, AlarmAckTarget> rememberCondition)
Action<string, AlarmAckTarget> rememberCondition) =>
ProjectEvent(fields, sourceIndex, handle, keyOf, rememberCondition, out _);
/// <summary>As the five-argument overload, also returning the event's (ActiveState/Id, AckedState/Id) through
/// <c>state</c> when it is an alarm condition (null otherwise).</summary>
internal static AlarmEventArgs? ProjectEvent(
IReadOnlyList<Variant> fields,
IReadOnlyDictionary<string, string> sourceIndex,
IAlarmSubscriptionHandle handle,
Func<NodeId, string> keyOf,
Action<string, AlarmAckTarget> rememberCondition,
out (bool Active, bool Acked)? state)
{
state = null;
if (fields.Count <= AlarmFieldConditionId) return null;
if (fields.Count > AlarmFieldAckedState
&& fields[AlarmFieldActiveState].Value is bool active
&& fields[AlarmFieldAckedState].Value is bool acked)
state = (active, acked);
// Pass-through (no authored refs) keeps the raw serialized ids; an authored index compares