#519 — a driver's OPC UA status code now reaches a client with its sub-code intact. DriverInstanceActor projected the driver's uint onto a 3-state Good/Uncertain/Bad enum and OtOpcUaNodeManager re-expanded Bad to a bare 0x80000000, so BadNoCommunication, BadTypeMismatch and BadNotSupported were indistinguishable on the wire and every driver's status constants (incl. the 16 #497 had just corrected) were diagnostic in logs only. Resolved by option (b): the raw uint rides AttributeValuePublished -> AttributeValueUpdate -> IOpcUaAddressSpaceSink.WriteValue, OpcUaQuality is deleted, and severity classification is a helper (OpcUaStatus.IsGood/IsUncertain/IsBad). The surface was wider than the issue costed (41 files, not "the sink and 3 implementations"): OpcUaQuality had non-driver producers with no uint to carry. Each got its natural code — BadInternalError for a failed virtual-tag script, BadNoCommunication for driver comms loss — and ScriptedAlarmHostActor's pair of mutually-inverse uint<->enum mappers is deleted, having round-tripped a code the engine already held. AddressSpaceApplier's removal writes deliberately keep the generic Bad: not losing a code the driver had is this issue; inventing one for the deploy path is a separate call. Behaviour change: WriteAlarmQuality fires its Part 9 event on a status-code change rather than a severity-bucket change. While the annotation was 3-state those were the same predicate; now a move between two Bad reasons changes what a subscriber reads. New SDK-free named constants live on Commons.OpcUa.OpcUaStatus, and StatusCodeParityTests is widened to cover them — that guard is reflection-driven, so it can only see a named constant, never an inline literal. #517 — the symptom is real but the issue named the wrong path and its fix was unsafe. ShutdownAsync cannot race: DriverInstanceActor calls it from PostStop, after the mailbox drains. (Core/Hosting/DriverHost, the one class with a concurrent GetHealth, has no production call site.) InitializeAsync can: it runs on a fire-and-forget Task.Run, and MTConnectDriver writes Healthy then starts loops that can throw into a catch which disposes the client before writing Faulted. Moving the write earlier, as suggested, inverts the terminal state — teardown drains in-flight loops that write health as they unwind, so a late loop could leave Healthy at rest with every connection closed. The fix is a bracket (conservative before, terminal after), applied to MTConnect's init-failure path only; shutdown keeps its single trailing write, and the rule plus the reachability table are documented on IDriver.ShutdownAsync. CalculationDriver.GetHealth returned a hard-coded Healthy that consulted nothing — Healthy before initialize, after shutdown and after dispose. Now derived from _running. Its test, named Health_is_always_Connected, asserted the defect and is replaced. Every new guard was falsified by breaking the production code and watching it go red. The two sub-code tests each assert two different Bad codes, since a single-code assertion could pass against a hard-coded constant under the old projection. Pre-existing failures, verified unchanged on a stashed tree and not chased: 4 in Driver.AbLegacy.IntegrationTests (slc500/micrologix/plc5 fixtures not up) and 3 in Host.IntegrationTests. Closes #517 Closes #519 Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
This commit is contained in:
@@ -158,12 +158,10 @@ public sealed class CalculationDriverTests
|
||||
after[0].Value.ShouldBe(6.0);
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void Health_is_always_Connected()
|
||||
{
|
||||
var (driver, _, _) = Build(CalcTag("calc/e/x", "return 1.0;"));
|
||||
driver.GetHealth().State.ShouldBe(DriverState.Healthy);
|
||||
}
|
||||
// REMOVED (Gitea #517): `Health_is_always_Connected` asserted that a driver which had never been
|
||||
// initialized still reported Healthy — a characterization test of the defect, not of a requirement.
|
||||
// Its valid half (a running Calculation driver has no transport to be Degraded about, so it is simply
|
||||
// Healthy) is covered by GetHealth_tracks_the_lifecycle_rather_than_reporting_a_constant below.
|
||||
|
||||
private static async Task<bool> WaitUntil(Func<bool> predicate, TimeSpan timeout)
|
||||
{
|
||||
@@ -176,6 +174,41 @@ public sealed class CalculationDriverTests
|
||||
return predicate();
|
||||
}
|
||||
|
||||
// ── health lifecycle (Gitea #517) ─────────────────────────────────────────────────────────
|
||||
|
||||
/// <summary>
|
||||
/// Gitea #517 — <c>GetHealth()</c> must not report Healthy for a driver that is not running.
|
||||
/// <para>This driver returned a hard-coded <see cref="DriverState.Healthy"/> that consulted
|
||||
/// nothing, which made it the fleet's only driver reporting Healthy with its timers stopped —
|
||||
/// deterministically, not as a race window. Every other driver reads a <c>_health</c> field that
|
||||
/// shutdown lands on <see cref="DriverState.Unknown"/>.</para>
|
||||
/// <para>The pre-initialize leg is what makes this falsifiable against the old code: a test that
|
||||
/// only checked post-shutdown could be satisfied by a driver that happened to write Unknown once,
|
||||
/// whereas asserting BOTH ends pins the value to the lifecycle flag.</para>
|
||||
/// </summary>
|
||||
[Fact]
|
||||
public async Task GetHealth_tracks_the_lifecycle_rather_than_reporting_a_constant()
|
||||
{
|
||||
var (driver, _, _) = Build(CalcTag("calc/e/x", "return 1.0;"));
|
||||
|
||||
// Constructed but never initialized — nothing is computing, so Healthy would be a lie.
|
||||
driver.GetHealth().State.ShouldBe(DriverState.Unknown);
|
||||
|
||||
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
driver.GetHealth().State.ShouldBe(DriverState.Healthy);
|
||||
|
||||
await driver.ShutdownAsync(TestContext.Current.CancellationToken);
|
||||
driver.GetHealth().State.ShouldBe(DriverState.Unknown,
|
||||
"timers are stopped and _running is false — the driver computes nothing");
|
||||
|
||||
// Re-initialize brings it back, so the flag is genuinely read each call rather than latched once.
|
||||
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
driver.GetHealth().State.ShouldBe(DriverState.Healthy);
|
||||
|
||||
driver.Dispose();
|
||||
driver.GetHealth().State.ShouldBe(DriverState.Unknown);
|
||||
}
|
||||
|
||||
private sealed class CapturingPublisher(List<ScriptLogEntry> sink) : IScriptLogPublisher
|
||||
{
|
||||
private readonly object _lock = new();
|
||||
|
||||
Reference in New Issue
Block a user