Phase 3 PR 47 -- DL205 V-memory octal-address helper. Adds DirectLogicAddress static class with two entry points: UserVMemoryToPdu(string) parses a DirectLOGIC V-address (V-prefixed or bare, whitespace tolerated) as OCTAL and returns the 0-based Modbus PDU address. V2000 octal = decimal 1024 = PDU 0x0400, which is the canonical start of the user V-memory bank on DL205/DL260. SystemVMemoryBasePdu + SystemVMemoryToPdu(ushort offset) handle the system bank (V40400 and up) which does NOT follow the simple octal-to-decimal formula -- the CPU relocates the system bank to PDU 0x2100 in H2-ECOM100 absolute mode. A naive caller converting 40400 octal would land at PDU 0x4100 (decimal 16640) and miss the system registers entirely; the helper routes the correct 0x2100 base. Why this matters: DirectLOGIC operators think in OCTAL (the ladder-logic editor, the Productivity/Do-more UI, every AutomationDirect manual addresses V-memory octally) while the Modbus wire is DECIMAL. Integrators routinely copy V-addresses from the PLC documentation into client configs and read garbage because they treated V2000 as decimal 2000 (HR[2000] = 0 in the dl205 sim, zero in most PLCs). The helper makes the translation explicit per the D2-USER-M appendix + H2-ECOM-M \u00A76.5 references cited in docs/v2/dl205.md. Unit tests: UserVMemoryToPdu_converts_octal_V_prefix (V0, V1, V7, V10, V2000, V7777, V10000, V17777 -- the exact sweep documented in dl205.md), UserVMemoryToPdu_accepts_bare_or_prefixed_or_padded (case + whitespace tolerance), UserVMemoryToPdu_rejects_non_octal_digits (V8/V19/V2009 must throw ArgumentException with 'octal' in the message -- .NET has no base-8 int.Parse so we hand-walk digits to catch 8/9 instead of silently accepting them), UserVMemoryToPdu_rejects_empty_input, UserVMemoryToPdu_overflow_rejected (200000 octal = 0x10000 overflows ushort), SystemVMemoryBasePdu_is_0x2100_for_V40400, SystemVMemoryToPdu_offsets_within_bank, SystemVMemoryToPdu_rejects_overflow. 23/23 Modbus.Tests pass. Integration tests against dl205.json pymodbus profile: DL205_V2000_user_memory_resolves_to_PDU_0x0400_marker (reads HR[0x0400]=0x2000), DL205_V40400_system_memory_resolves_to_PDU_0x2100_marker (reads HR[0x2100]=0x4040). 5/5 DL205 integration tests pass. Caller opts into the helper per tag by calling DirectLogicAddress.UserVMemoryToPdu("V2000") as the ModbusTagDefinition Address -- no driver-wide "DL205 mode" flag needed, because users mix DL and non-DL tags in a single driver instance all the time.
This commit is contained in:
@@ -0,0 +1,91 @@
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.DL205;
|
||||
|
||||
/// <summary>
|
||||
/// Verifies the DL205/DL260 V-memory octal addressing quirk end-to-end: use
|
||||
/// <see cref="DirectLogicAddress.UserVMemoryToPdu"/> to translate <c>V2000</c> octal into
|
||||
/// the Modbus PDU address actually dispatched, then read the marker the dl205.json profile
|
||||
/// placed at that address. HR[0x0400] = 0x2000 proves the translation was performed
|
||||
/// correctly — a naïve caller treating "V2000" as decimal 2000 would read HR[2000] (which
|
||||
/// the profile leaves at 0) and miss the marker entirely.
|
||||
/// </summary>
|
||||
[Collection(ModbusSimulatorCollection.Name)]
|
||||
[Trait("Category", "Integration")]
|
||||
[Trait("Device", "DL205")]
|
||||
public sealed class DL205VMemoryQuirkTests(ModbusSimulatorFixture sim)
|
||||
{
|
||||
[Fact]
|
||||
public async Task DL205_V2000_user_memory_resolves_to_PDU_0x0400_marker()
|
||||
{
|
||||
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
||||
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "dl205",
|
||||
StringComparison.OrdinalIgnoreCase))
|
||||
{
|
||||
Assert.Skip("MODBUS_SIM_PROFILE != dl205 — skipping (standard profile does not seed V-memory markers).");
|
||||
}
|
||||
|
||||
var pdu = DirectLogicAddress.UserVMemoryToPdu("V2000");
|
||||
pdu.ShouldBe((ushort)0x0400);
|
||||
|
||||
var options = new ModbusDriverOptions
|
||||
{
|
||||
Host = sim.Host,
|
||||
Port = sim.Port,
|
||||
UnitId = 1,
|
||||
Timeout = TimeSpan.FromSeconds(2),
|
||||
Tags =
|
||||
[
|
||||
new ModbusTagDefinition("DL205_V2000",
|
||||
ModbusRegion.HoldingRegisters, Address: pdu,
|
||||
DataType: ModbusDataType.UInt16, Writable: false),
|
||||
],
|
||||
Probe = new ModbusProbeOptions { Enabled = false },
|
||||
};
|
||||
await using var driver = new ModbusDriver(options, driverInstanceId: "dl205-vmem");
|
||||
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
|
||||
var results = await driver.ReadAsync(["DL205_V2000"], TestContext.Current.CancellationToken);
|
||||
results[0].StatusCode.ShouldBe(0u);
|
||||
results[0].Value.ShouldBe((ushort)0x2000, "dl205.json seeds HR[0x0400] with marker 0x2000 (= V2000 value)");
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task DL205_V40400_system_memory_resolves_to_PDU_0x2100_marker()
|
||||
{
|
||||
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
||||
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "dl205",
|
||||
StringComparison.OrdinalIgnoreCase))
|
||||
{
|
||||
Assert.Skip("MODBUS_SIM_PROFILE != dl205 — skipping.");
|
||||
}
|
||||
|
||||
// V40400 is system memory on DL260 / H2-ECOM100 absolute mode; it does NOT follow the
|
||||
// simple octal-to-decimal formula (40400 octal = 16640 decimal, which would read HR[0x4100]).
|
||||
// The CPU places the system bank at PDU 0x2100 instead. Proving the helper routes there.
|
||||
var pdu = DirectLogicAddress.SystemVMemoryToPdu(0);
|
||||
pdu.ShouldBe((ushort)0x2100);
|
||||
|
||||
var options = new ModbusDriverOptions
|
||||
{
|
||||
Host = sim.Host,
|
||||
Port = sim.Port,
|
||||
UnitId = 1,
|
||||
Timeout = TimeSpan.FromSeconds(2),
|
||||
Tags =
|
||||
[
|
||||
new ModbusTagDefinition("DL205_V40400",
|
||||
ModbusRegion.HoldingRegisters, Address: pdu,
|
||||
DataType: ModbusDataType.UInt16, Writable: false),
|
||||
],
|
||||
Probe = new ModbusProbeOptions { Enabled = false },
|
||||
};
|
||||
await using var driver = new ModbusDriver(options, driverInstanceId: "dl205-sysv");
|
||||
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
|
||||
var results = await driver.ReadAsync(["DL205_V40400"], TestContext.Current.CancellationToken);
|
||||
results[0].StatusCode.ShouldBe(0u);
|
||||
results[0].Value.ShouldBe((ushort)0x4040, "dl205.json seeds HR[0x2100] with marker 0x4040 (= V40400 value)");
|
||||
}
|
||||
}
|
||||