Phase 3 PR 47 -- DL205 V-memory octal-address helper. Adds DirectLogicAddress static class with two entry points: UserVMemoryToPdu(string) parses a DirectLOGIC V-address (V-prefixed or bare, whitespace tolerated) as OCTAL and returns the 0-based Modbus PDU address. V2000 octal = decimal 1024 = PDU 0x0400, which is the canonical start of the user V-memory bank on DL205/DL260. SystemVMemoryBasePdu + SystemVMemoryToPdu(ushort offset) handle the system bank (V40400 and up) which does NOT follow the simple octal-to-decimal formula -- the CPU relocates the system bank to PDU 0x2100 in H2-ECOM100 absolute mode. A naive caller converting 40400 octal would land at PDU 0x4100 (decimal 16640) and miss the system registers entirely; the helper routes the correct 0x2100 base. Why this matters: DirectLOGIC operators think in OCTAL (the ladder-logic editor, the Productivity/Do-more UI, every AutomationDirect manual addresses V-memory octally) while the Modbus wire is DECIMAL. Integrators routinely copy V-addresses from the PLC documentation into client configs and read garbage because they treated V2000 as decimal 2000 (HR[2000] = 0 in the dl205 sim, zero in most PLCs). The helper makes the translation explicit per the D2-USER-M appendix + H2-ECOM-M \u00A76.5 references cited in docs/v2/dl205.md. Unit tests: UserVMemoryToPdu_converts_octal_V_prefix (V0, V1, V7, V10, V2000, V7777, V10000, V17777 -- the exact sweep documented in dl205.md), UserVMemoryToPdu_accepts_bare_or_prefixed_or_padded (case + whitespace tolerance), UserVMemoryToPdu_rejects_non_octal_digits (V8/V19/V2009 must throw ArgumentException with 'octal' in the message -- .NET has no base-8 int.Parse so we hand-walk digits to catch 8/9 instead of silently accepting them), UserVMemoryToPdu_rejects_empty_input, UserVMemoryToPdu_overflow_rejected (200000 octal = 0x10000 overflows ushort), SystemVMemoryBasePdu_is_0x2100_for_V40400, SystemVMemoryToPdu_offsets_within_bank, SystemVMemoryToPdu_rejects_overflow. 23/23 Modbus.Tests pass. Integration tests against dl205.json pymodbus profile: DL205_V2000_user_memory_resolves_to_PDU_0x0400_marker (reads HR[0x0400]=0x2000), DL205_V40400_system_memory_resolves_to_PDU_0x2100_marker (reads HR[0x2100]=0x4040). 5/5 DL205 integration tests pass. Caller opts into the helper per tag by calling DirectLogicAddress.UserVMemoryToPdu("V2000") as the ModbusTagDefinition Address -- no driver-wide "DL205 mode" flag needed, because users mix DL and non-DL tags in a single driver instance all the time.
This commit is contained in:
74
src/ZB.MOM.WW.OtOpcUa.Driver.Modbus/DirectLogicAddress.cs
Normal file
74
src/ZB.MOM.WW.OtOpcUa.Driver.Modbus/DirectLogicAddress.cs
Normal file
@@ -0,0 +1,74 @@
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
|
||||
/// <summary>
|
||||
/// AutomationDirect DirectLOGIC address-translation helpers. DL205 / DL260 / DL350 CPUs
|
||||
/// address V-memory in OCTAL while the Modbus wire uses DECIMAL PDU addresses — operators
|
||||
/// see "V2000" in the PLC ladder-logic editor but the Modbus client must write PDU 0x0400.
|
||||
/// The formulas differ between user V-memory (simple octal-to-decimal) and system V-memory
|
||||
/// (fixed bank mappings), so the two cases are separate methods rather than one overloaded
|
||||
/// "ToPdu" call.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// See <c>docs/v2/dl205.md</c> §V-memory for the full CPU-family matrix + rationale.
|
||||
/// References: D2-USER-M appendix (DL205/D2-260), H2-ECOM-M §6.5 (absolute vs relative
|
||||
/// addressing), AutomationDirect forum guidance on V40400 system-base.
|
||||
/// </remarks>
|
||||
public static class DirectLogicAddress
|
||||
{
|
||||
/// <summary>
|
||||
/// Convert a DirectLOGIC user V-memory address (octal) to a 0-based Modbus PDU address.
|
||||
/// Accepts bare octal (<c>"2000"</c>) or <c>V</c>-prefixed (<c>"V2000"</c>). Range
|
||||
/// depends on CPU model — DL205 D2-260 user memory is V1400-V7377 + V10000-V17777
|
||||
/// octal, DL260 extends to V77777 octal.
|
||||
/// </summary>
|
||||
/// <exception cref="ArgumentException">Input is null / empty / contains non-octal digits (8,9).</exception>
|
||||
/// <exception cref="OverflowException">Parsed value exceeds ushort.MaxValue (0xFFFF).</exception>
|
||||
public static ushort UserVMemoryToPdu(string vAddress)
|
||||
{
|
||||
if (string.IsNullOrWhiteSpace(vAddress))
|
||||
throw new ArgumentException("V-memory address must not be empty", nameof(vAddress));
|
||||
var s = vAddress.Trim();
|
||||
if (s[0] == 'V' || s[0] == 'v') s = s.Substring(1);
|
||||
if (s.Length == 0)
|
||||
throw new ArgumentException($"V-memory address '{vAddress}' has no digits", nameof(vAddress));
|
||||
|
||||
// Octal conversion. Reject 8/9 digits up-front — int.Parse in the obvious base would
|
||||
// accept them silently because .NET has no built-in base-8 parser.
|
||||
uint result = 0;
|
||||
foreach (var ch in s)
|
||||
{
|
||||
if (ch < '0' || ch > '7')
|
||||
throw new ArgumentException(
|
||||
$"V-memory address '{vAddress}' contains non-octal digit '{ch}' — DirectLOGIC V-addresses are octal (0-7)",
|
||||
nameof(vAddress));
|
||||
result = result * 8 + (uint)(ch - '0');
|
||||
if (result > ushort.MaxValue)
|
||||
throw new OverflowException(
|
||||
$"V-memory address '{vAddress}' exceeds the 16-bit Modbus PDU address range");
|
||||
}
|
||||
return (ushort)result;
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// DirectLOGIC system V-memory starts at octal V40400 on DL260 / H2-ECOM100 in factory
|
||||
/// "absolute" addressing mode. Unlike user V-memory, the mapping is NOT a simple
|
||||
/// octal-to-decimal conversion — the CPU relocates the system bank to Modbus PDU 0x2100
|
||||
/// (decimal 8448). This helper returns the CPU-family base plus a user-supplied offset
|
||||
/// within the system bank.
|
||||
/// </summary>
|
||||
public const ushort SystemVMemoryBasePdu = 0x2100;
|
||||
|
||||
/// <param name="offsetWithinSystemBank">
|
||||
/// 0-based register offset within the system bank. Pass 0 for V40400 itself; pass 1 for
|
||||
/// V40401 (octal), and so on. NOT an octal-decoded value — the system bank lives at
|
||||
/// consecutive PDU addresses, so the offset is plain decimal.
|
||||
/// </param>
|
||||
public static ushort SystemVMemoryToPdu(ushort offsetWithinSystemBank)
|
||||
{
|
||||
var pdu = SystemVMemoryBasePdu + offsetWithinSystemBank;
|
||||
if (pdu > ushort.MaxValue)
|
||||
throw new OverflowException(
|
||||
$"System V-memory offset {offsetWithinSystemBank} maps past 0xFFFF");
|
||||
return (ushort)pdu;
|
||||
}
|
||||
}
|
||||
Reference in New Issue
Block a user