feat(opcua): HistoryReadEvents projects EventType, ConditionName, SourceNode; honours the where-clause (lmxopcua#746)

HistoryReadEvents projected only EventId / SourceName / Time / ReceiveTime /
Message / Severity: a select clause asking for EventType, ConditionName or
SourceNode (what most generic alarm viewers ask for) got nulls, and the
event filter's where-clause (an OfType) was ignored.

- HistoricalEvent gains optional EventTypeName, ConditionName and AlarmId.
  SqlServer, QuestDB and Gateway event reads fill them from what their
  alarm writers already store (AlarmTypeName / AlarmName / AlarmId; the
  gateway event Type and its AlarmName / AlarmId properties).
- The node manager maps the type name to its Part 9 event type (unknown or
  non-event => AlarmConditionType), projects ConditionName, and resolves
  SourceNode to the materialised condition the alarm id names (the live
  events' SourceNode), else null.
- The where-clause is evaluated per event with the SDK content filter
  through an IFilterTarget (OfType via the type tree; other operators
  against the projected fields), after the page's cursor is taken, so
  paging is unchanged.

Tested in the node manager, over a real client session (the Client.CLI has
no `historyread --events` mode yet; filed as a follow-up), and by alarm
writer -> event read round trips on SqlServer and QuestDB.

Rebased from the unpushed remed/lane-H2 branch (originally authored 2026-10-22
in session_01Ub9hGmYLQvn9XETzw7CMsT) onto current master.

Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
This commit is contained in:
Joseph Doherty
2026-10-22 17:45:38 -04:00
parent 096a3d5b3c
commit 29665c1872
13 changed files with 503 additions and 31 deletions
@@ -63,6 +63,25 @@ public sealed class AlarmWriterTests(SqlHistorianFixture fx)
r.ShouldBe([HistorianWriteOutcome.Ack, HistorianWriteOutcome.PermanentFail, HistorianWriteOutcome.Ack]);
}
[Fact]
public async Task An_event_reads_back_with_its_type_name_condition_name_and_alarm_id()
{
fx.SkipIfUnavailable();
var s = SqlHistorianFixture.UniqueSchema();
var o = new SqlServerHistorianOptions { ConnectionString = fx.ConnectionString, Schema = s };
var c = new SqlHistorianConnection(o);
var boot = new SqlServerSchemaBootstrapper(c, o);
var w = new SqlServerAlarmHistorianWriter(c, boot);
(await w.WriteBatchAsync([Ev()], CancellationToken.None)).ShouldBe([HistorianWriteOutcome.Ack]);
using var src = new SqlServerHistorianDataSource(c, boot, new SqlServerTagCatalog(c, boot));
var e = (await src.ReadEventsAsync("Plant/Line/Eq", T.AddMinutes(-1), T.AddMinutes(1), 0, CancellationToken.None))
.Events.ShouldHaveSingleItem();
e.EventTypeName.ShouldBe("LimitAlarm");
e.ConditionName.ShouldBe("HiTemp");
e.AlarmId.ShouldBe("alarm-1");
}
[Fact]
public async Task A_batch_is_one_statement_per_chunk_and_a_redelivery_converges()
{